Activating the 'Select I/O' Function in SIMATIC PCS 7 Process Object View (Parameters and Signals Tabs)
The 'Select I/O' function in SIMATIC Manager appears disabled (greyed out) when the user is viewing the project in Component View or Plant View, or when the Process Object View is open on an unsupported tab (such as 'General' or 'Messages'). To activate 'Select I/O', open the Process Object View by selecting 'View > Process Object View' (or pressing the Process Object View icon), navigate to the 'Parameters' or 'Signals' tab in the right-hand pane, and select a folder or chart in the plant hierarchy. The 'Select I/O...' button in the toolbar and context menu will become immediately active, allowing bulk selection of block pins for mass editing.
Table of Contents
- Process Object View Architecture and Bulk Engineering Capabilities
- Why 'Select I/O' Appears Greyed Out: View and Tab Dependencies
- Configuring Displayed Parameters on the Parameters and Signals Tabs
- Step-by-Step Procedure to Enable and Use 'Select I/O'
- Process Object View Tab Capability Comparison
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Process Object View Architecture and Bulk Engineering Capabilities
In large SIMATIC PCS 7 facilities containing thousands of I/O points, individually opening hundreds of Continuous Function Charts (CFC) to parameterize alarms, tune sample times, or map signal interconnects is prohibitively slow and error-prone. To streamline mass engineering, Siemens provides the Process Object View (POV) within SIMATIC Manager.
Process Object View aggregates block parameters, signal connections, message definitions, picture assignments, and archive tags into structured, spreadsheet-like tabular grids. Engineers can edit hundreds of block attributes simultaneously, paste data from Microsoft Excel, and execute mass find-and-replace operations across the entire plant hierarchy.
Why 'Select I/O' Appears Greyed Out: View and Tab Dependencies
Engineers frequently encounter situations where the menu option Edit > Select I/O... or the toolbar button remains stubbornly greyed out. This occurs due to strict structural prerequisites in SIMATIC Manager:
-
Component View / Plant View Active: The user is browsing the project inside the traditional Component View (which shows hardware stations, CPU folders, and S7 programs) or the standard Plant View. The 'Select I/O' utility is an exclusive feature of the Process Object View and cannot execute in other views.
-
Unsupported Tab Selected: Even inside Process Object View, the right pane features multiple functional tabs:
General,Blocks,Parameters,Signals,Messages,Picture Objects, andArchive Tags. The 'Select I/O' command is functional only on the Parameters tab and Signals tab, where block inputs and outputs are manipulated. On tabs likeMessagesorPicture Objects, 'Select I/O' is intentionally disabled by the editor.
Configuring Displayed Parameters on the Parameters and Signals Tabs
By default, the Parameters tab displays only standard visible block parameters (such as SP_Int, Gain, TI). When an engineer needs to modify hidden or specialized pins across dozens of motor or valve blocks (e.g., configuring Feature bits, Monitor times, or SampleTime):
- The Select I/O dialog queries the Master Data Library block definitions.
- The engineer selects the specific block type (e.g.,
MotLFB1823) and checks which additional input and output pins should be displayed as columns in the table. - Once applied, the Process Object View expands to include the selected pins as editable table columns for all instances.
Step-by-Step Procedure to Enable and Use 'Select I/O'
Follow this sequence to activate and configure 'Select I/O':
- Switch to Process Object View: In SIMATIC Manager, select View > Process Object View (or click the Process Object View icon on the main toolbar).
- Select Plant Hierarchy Folder: In the left pane, select the plant hierarchy folder (e.g.,
Plant1 > AreaA) containing the target CFC charts. - Click the Parameters Tab: In the right-hand table, click the Parameters tab (or Signals tab).
- Launch Select I/O: Click the Select I/O... button on the Process Object View toolbar, or right-click any column header and select Select I/O....
- Filter and Add Pins: In the dialog, select the block type. Check the desired pins (e.g.,
Feature,OS_Perm,SimOn). Click OK. - Bulk Edit Values: The newly added pins appear as columns. Modify values directly in the grid, copy down columns, or copy/paste from an external Excel engineering spreadsheet.
Process Object View Tab Capability Comparison
The following table compares Process Object View tabs and their support for the 'Select I/O' function:
GeneralBlocksParametersSignalsMessagesPicture ObjectsVerification
Verify Process Object View functionality through the following steps:
- Confirm that clicking 'Select I/O...' opens the dialog displaying block types and parameter trees.
- Add a parameter (e.g.,
MonTiDynamic) to the view. Verify that a new column appears across all relevant block rows. - Edit a value in the table (e.g., change
3.0to5.0). Press Enter. - Open the corresponding CFC chart. Verify that the block pin reflects the new value (
5.0) immediately. - Save the project and confirm that changes persist across SIMATIC Manager sessions.
Limitations and Operational Precautions
Consider these operational rules when using Process Object View:
-
Avoid Overloading Table Columns: Adding dozens of large structures or string pins to the Process Object View table can slow down table rendering on very large projects (thousands of charts); select only necessary I/O pins.
-
CFC Locking During Bulk Edits: When editing parameters in Process Object View, ensure the corresponding CFC charts are not currently opened by another engineer on a shared network, which would block database commits.
-
Delta Compilation Required: Modifying block parameters in Process Object View updates offline chart databases and requires a subsequent CFC Delta Compile and Download Changes in RUN to take effect in the controller.
Engineer FAQ
How do I display hidden block parameters in Process Object View?
Open the Parameters tab, click 'Select I/O...', select the block type, check the desired parameters, and click OK to add them as columns in the table.
Does editing values in Process Object View modify the CFC charts?
Yes, Process Object View directly writes to the underlying CFC chart database; changes appear immediately inside the graphical charts.
Can I filter blocks by type in Process Object View?
Yes, Process Object View includes column filters allowing you to filter rows by block type (e.g., showing only MotL or PIDConL blocks).
Technical References
- SIMATIC Process Control System PCS 7 Engineering System Compendium Part A (Entry ID: 109780813)
- SIMATIC PCS 7 Process Object View Operation Manual
- STEP 7 V5.5 / V5.6 System Manual: Plant Hierarchy and Mass Engineering
- Siemens Technical Guidelines: Efficient Bulk Engineering with Process Object View
Related Articles
- Expanding Interlock Capacity in SIMATIC PCS 7 APL Faceplates
- CFC Parameter Readback: Safety, Feasibility, and Consistency Rules
- Resolving CPU 410-5H Object Properties Greyed Out and Read-Only in HW Config
Related Tags
- Process Object View
- Select I/O
- Bulk Engineering
- Parameters Tab
- CFC Engineering
- SIMATIC Manager