Adding Interlock Bypassed Indicators to CEMAT Motor Block Icons in PCS 7
To display an interlock bypassed indicator on a CEMAT Minerals motor block icon without losing tag connections during screen updates, create a custom block icon template file named '@PCS7Typicals_Custom.pdl' in the WinCC GraCS directory rather than directly editing the factory '@PCS7Typicals.pdl'. In the custom template, copy the target drive icon (e.g., @C_DRV_1D/1), assign a unique variant type (such as @C_DRV_1D/25), and embed an Extended Status Display or bitmap layer linked to the drive's maintenance status tag (.STATUS3 or .MAINT). Assign this new type in the CFC block properties and run 'Create/Update Block Icons' to preserve dynamic tags permanently.
Table of Contents
- CEMAT Block Icon Architecture and Typical File Integrity
- Why Dynamic Tags Disappear During Direct Template Edits
- CEMAT Status Word Bitmasking for Interlock Bypassing
- Comparison of Standard vs Custom Block Icon Customization
- Step-by-Step Procedure to Add Bypass Indicators to CEMAT Icons
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
CEMAT Block Icon Architecture and Typical File Integrity
In SIMATIC PCS 7, block icons represent technological field devices on WinCC operator process screens. The automatic generation and synchronization of these icons is driven by template files located in the project's GraCS directory. In standard systems, this is @PCS7Typicals.pdl or @PCS7Typicals_APL.pdl; in cement and mining installations, it is governed by @PCS7Typicals_CEMAT.pdl.
When engineers attempt to customize block icons—such as adding a visual indicator (a yellow hand or wrench icon) to warn operators that an electrical or process interlock is bypassed—they often edit the factory template directly or paste unconfigured graphic objects into process screens. This causes dynamic tag links to vanish as soon as the SIMATIC Manager block icon generator runs.
Why Dynamic Tags Disappear During Direct Template Edits
Understanding the WinCC Block Icon Generator rules prevents tag loss:
-
Template Overwriting by Project Editor: Whenever the WinCC OS Project Editor runs, factory files beginning with
@(such as@PCS7Typicals.pdl) are completely overwritten by pristine versions from the Siemens installation directory. Any direct modifications made to factory files are deleted. -
Relative Tag Resolution: Inside a typical picture, dynamic tag properties must use relative tag syntax (beginning with a dot, e.g.,
.STATUS3or.STATUS1). If an icon is copied across screens without proper grouping, the wizard strips the dynamic dialog because the parent group properties (type,tag,tagstructure) are missing or unlinked. -
Custom Typicals Priority: SIMATIC Manager searches for custom templates adhering to the naming convention
@PCS7Typicals_<CustomName>.pdl(e.g.,@PCS7Typicals_CEMAT_Plant.pdl) and merges them into the block icon catalog without risk of overwriting.
CEMAT Status Word Bitmasking for Interlock Bypassing
In CEMAT Minerals (C_DRV_1D), status reporting is handled by 32-bit double words. The table below illustrates the structure of CEMAT status words and how bypass indicators should be extracted.
.STATUS1.STATUS2.STATUS3.STATUS3.MAINTComparison of Standard vs Custom Block Icon Customization
The table below contrasts standard CEMAT block icon behavior with properly engineered custom block icons.
@PCS7Typicals_CEMAT.pdl@PCS7Typicals_Custom.pdl@C_DRV_1D/1, /2)@C_DRV_1D/25)Create/Update Block IconsStep-by-Step Procedure to Add Bypass Indicators to CEMAT Icons
Follow this procedure to permanently add an interlock bypass badge to CEMAT motor block icons:
-
Create Custom Typicals Picture:
- In WinCC Graphics Designer, open@PCS7Typicals_CEMAT.pdl.
- Save the file as@PCS7Typicals_Custom.pdlinside the project'sGraCSdirectory. -
Customize the Drive Block Icon:
- Locate the target motor icon (e.g.,@C_DRV_1D/1). Select and duplicate it (Ctrl + D).
- Open object properties of the duplicated group: change propertytypeto@C_DRV_1D/25.
- Ungroup the icon temporarily or open group editing mode.
- Insert a Status Display object (or Extended Status Display) positioned in the upper right quadrant of the motor symbol.
- Connect the status display's tag property to relative tag.STATUS3.
- Configure bitmask evaluation: when Bit 12 = 1 (or.MAINTBit 0 = 1), display the yellow hand or wrench bitmap image.
- Regroup all objects into a single unified graphic object. -
Assign New Type in CFC:
- In Continuous Function Chart, open the object properties of the targetC_DRV_1Dblock.
- In theAttributestab, set attributetypeto@C_DRV_1D/25. -
Execute Block Icon Update:
- In SIMATIC Manager, select the plant hierarchy folder and runOptions -> Plant Hierarchy -> Create/Update Block Icons.
- Confirm the update: the wizard parses@PCS7Typicals_Custom.pdland places the customized icon with dynamic tags fully resolved.
Verification
Verify custom block icon functionality through the following checks:
1. In WinCC Graphics Designer, open the target process screen: confirm that the block icon has type @C_DRV_1D/25 and dynamic tag properties point to the real motor tag.
2. Launch WinCC Runtime: verify that the motor icon displays normal idle/running colors without visual defects.
3. In the field or online test mode, activate an interlock bypass on the associated C_INTERL block: verify that the yellow hand/wrench icon immediately appears on the motor symbol.
4. Clear the bypass: verify that the bypass badge clears instantly.
Limitations and Operational Precautions
Never modify factory graphics in C:\Program Files (x86)\Siemens\WinCC\Options\PDL\.... Always maintain custom templates within the specific WinCC project GraCS folder and back them up before performing any PCS 7 software upgrade. Additionally, ensure that custom bitmap files (e.g., Bypass_Hand.emf or Wrench.bmp) are copied to the GraCS folder on all OS Servers and OS Clients to avoid missing image placeholders during runtime.
Engineer FAQ
Why did copying and pasting an icon directly onto a process picture fail?
Copying an icon directly bypasses the SIMATIC Manager Block Icon Generator. Without the wizard resolving relative tag paths (e.g., .STATUS3 to Area/Unit/Motor.STATUS3), the tags remain unbound and disappear.
How many custom typicals files can I create in a WinCC project?
SIMATIC PCS 7 allows multiple custom typical files following the naming format @PCS7Typicals_<Name>.pdl. The generator parses them in alphabetical order.
Can I use this procedure for valve blocks (C_VALVE)?
Yes. The same workflow applies to C_VALVE, C_DAMPER, and standard APL blocks (MotL, VlvL) using their respective status tags.
Technical References
- Siemens Technical Support: How do you create your own block icons with SIMATIC PCS 7 (SIOS Entry ID 26514219)
- SIMATIC PCS 7 Minerals (CEMAT) V8.2 Engineering Manual
- SIMATIC Process Control System PCS 7 Graphics Designer Manual
Related Articles
- Restoring Missing Interlock Bypass Icons on CEMAT Motor Faceplates in PCS 7
- Assigning and Changing APL Block Icon Variants in Continuous Function Chart (CFC)
- Preventing Block Icon Layer Reset to Layer 0 During Create and Update Block Icons