Best Practices for Connecting Multiple Automation Stations to an OS Server Using Multiprojects in PCS 7
In SIMATIC PCS 7, connecting multiple Automation Stations (AS) to an Operator Station (OS) must always be structured within a unified Multiproject rather than an unmanaged single project. A Multiproject enables centralized management of Plant Hierarchy, Master Data Libraries, cross-project S7 connections, and OS Server data generation. Furthermore, direct chart-to-chart cross-AS interconnections in CFC are fully supported and automated within a Multiproject without requiring manual SFB/SFC programming, as SIMATIC Manager automatically creates the underlying cross-controller communication blocks (such as IK_SEND and IK_RCV) over the Plant Bus.
Table of Contents
- Single Project Limitations vs Multiproject Architecture
- Cross-AS Communication Mechanisms in SIMATIC CFC
- Step-by-Step Multiproject Assembly and Cross-AS Engineering Procedure
- Project Structure and Communication Method Comparison Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Single Project Limitations vs Multiproject Architecture
When engineering medium-to-large SIMATIC PCS 7 installations comprising multiple controllers (e.g., 5 S7-400 or CPU 410-5H automation stations) communicating with a central OS Server pair, engineers sometimes make the mistake of creating a single monolithic Step 7 project or separate isolated projects.
Engineers often worry: 'If I split my controllers into a Multiproject with a Plant Hierarchy, will I lose the ability to connect CFC block outputs from AS01 directly to inputs on AS02?'
The Multiproject Advantage
Siemens PCS 7 mandates the Multiproject structure for multi-station architectures:
1. Performance and Sizing: Isolating each AS and OS into its own sub-project within a multiproject container prevents project database bloat, speeds up CFC compilation, and allows multi-user engineering where different engineers edit separate controllers simultaneously.
2. Master Data Library (MDL): Enforces uniform block types, versions, and system attributes across all controllers.
3. Plant View Integration: The Plant Hierarchy spans the entire multiproject. Hierarchy folders map to specific controllers and OS servers, enabling the OS Compiler to aggregate all AS tags into a single unified WinCC runtime database.
Cross-AS Communication Mechanisms in SIMATIC CFC
In SIMATIC CFC, engineers can interconnect a block output in one controller directly to a block input in another controller (e.g., AS01/Area1/ChartA/Block1.Out connected to AS02/Area2/ChartB/Block2.In).
This is known as a Cross-AS Interconnection:
* Automated Infrastructure: You do not need to manually program communication system function blocks (SFB12 BSEND / SFB13 BRCV) in CFC.
* System-Generated Drivers: When the cross-AS interconnection is made and the charts are compiled, SIMATIC Manager automatically creates dedicated communication blocks (IK_SEND, IK_RCV or IK_CP_OUT, IK_CP_IN) in system charts.
* NetPro Coordination: SIMATIC Manager automatically configures the underlying S7 connections in NetPro across the shared Plant Bus.
* Data Integrity: Cross-AS communication includes data cycle stamping, communication failure monitoring, and fallback safe-state handling.
Step-by-Step Multiproject Assembly and Cross-AS Engineering Procedure
To properly structure multiple controllers and an OS Server within a Multiproject:
Step 1: Create the Master Multiproject
- In SIMATIC Manager, select File -> New....
- Select the Multiproject tab, name the project (e.g.,
Plant_Master_MP), and click OK. - Select File -> 'Save As' / Insert into Multiproject... to attach your existing AS projects and OS project into the multiproject container.
- Create a Master Data Library inside the multiproject to synchronize block types.
Step 2: Configure Plant Bus Subnets in NetPro
- In SIMATIC Manager, open NetPro.
- Merge the Industrial Ethernet subnets: ensure that the Plant Bus (e.g.,
Plant_Bus_Ethernet) is configured as a single shared subnet across all AS projects and the OS Server. - Select Network -> Save and Compile -> Check and compile all.
Step 3: Establish Cross-AS Interconnections in CFC
- Open a CFC chart in
AS01and a CFC chart inAS02simultaneously in CFC Editor. - Click the output pin on the block in
AS01, then click the input pin on the block inAS02. - CFC renders a green cross-chart margin connector displaying the full path:
AS01\ChartName\BlockName.PinName. - The connection is established.
Step 4: Map Plant Hierarchy and Compile OS
- Switch to Plant View.
- Assign each plant folder to its respective AS and to the central OS Server (
AS-OS Assignment). - Right-click the OS Server and select Compile:
* The compiler aggregates tags, alarms, and block icons from all 5 controllers into the single WinCC project.
Project Structure and Communication Method Comparison Matrix
The following table compares architectural approaches for multi-controller PCS 7 systems:
Adopting a Multiproject guarantees complete system scalability and automated network management.
Verification
To verify that multiple AS controllers communicate properly with the OS and with each other:
1. In NetPro, execute Network -> Check cross-project consistency; confirm zero errors.
2. Compile CFC on all AS controllers; verify that system communication charts (@Chart) are generated with valid S7 connections.
3. In CFC Editor on AS02, switch to Test Mode; confirm that live values transmitted from AS01 update dynamically.
4. Disconnect the network cable between AS01 and the switch; verify that the cross-AS input in AS02 detects communication timeout and asserts bad quality.
5. In WinCC Runtime, verify that process pictures display live data simultaneously from all 5 controllers.
Limitations and Operational Precautions
- Cross-AS communication over Industrial Ethernet consumes CPU communication resources; avoid routing high-frequency fast-control loops across controllers (keep fast loops within a single AS).
- For safety-instrumented systems (SIS), cross-AS communication between safety programs must utilize certified F_Send / F_Receive blocks with F-Connection safety CRC signatures.
- Always execute 'Update Block Types' from the Master Data Library across all projects in the multiproject to prevent block version drift.
- In redundant plant bus topologies, ensure all AS controllers and OS servers are connected to both redundant rings with proper subnet assignments.
Engineer FAQ
Does moving an existing project into a Multiproject break existing logic?
No. Moving projects into a Multiproject simply groups them under a common administrative umbrella. Existing CFC logic, HW Config, and connections remain completely intact.
How many AS controllers can be connected to a single PCS 7 OS Server?
A single PCS 7 OS Server (or redundant pair) can connect to up to 64 AS controllers, subject to overall Process Object (PO) and WinCC tag volume limits.
What block handles automated cross-AS communication in CFC?
Depending on library version, the CFC compiler automatically inserts IK_SEND and IK_RCV (or IK_CP_OUT / IK_CP_IN when communicating via CP 443-1) into system charts.
Technical References
- SIMATIC Process Control System PCS 7 Engineering System Manual
- SIMATIC PCS 7 Compendium Part A - Configuration Guidelines
- Siemens Industry Online Support FAQ: Multi-User and Multiproject Engineering in PCS 7
Related Articles
- How to Resolve Greyed Out Compile OS Scope and Missing Tags on Engineering Stations in PCS 7
- How to Measure and Analyze Network and Communication Bus Load in SIMATIC PCS 7
- How to Configure Controller and I/O Hardware Diagnostics on the WinCC OS in PCS 7