Calculating Fail-Safe Rate of Change for F_CH_AI in SIMATIC S7 F-Systems
To calculate the rate of change (dPV/dt) from an F_CH_AI channel driver within a certified SIMATIC S7 F-Systems safety program, use the standard fail-safe delay block F_DEADTM (FB 320) from the F-Systems Library. Because safety runtime groups forbid uncertified SCL code or standard APL derivative blocks, rate-of-change logic must be constructed using certified F-blocks: feed the analog value into F_DEADTM to buffer it over a configured delay window (T_DELAY), subtract the delayed output from the live value using F_SUB_R (FB 347), and divide by the elapsed time using F_DIV_R to obtain a verified, SIL 3 compliant rate of change.
Table of Contents
- Functional Safety Constraints in S7 F-Systems Runtime Groups
- Mathematical Principle of Discrete Rate of Change Calculation
- Step-by-Step CFC Implementation with F_DEADTM and Arithmetic F-Blocks
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Functional Safety Constraints in S7 F-Systems Runtime Groups
In industrial safety applications governed by IEC 61508 / IEC 61511 (e.g., detecting rapid pressure surges in chemical reactors or rate of temperature rise in exothermic processes), measuring the rate of change ($
rac{dPV}{dt}$) is a common trip requirement.
However, within SIMATIC S7 F-Systems (V6.x / F-Library V1.3):
* All blocks placed inside the Safety Runtime Group (executed typically in OB35 with fail-safe signatures) must be TÜV-certified fail-safe blocks (prefixed with F_).
* Standard CFC blocks (such as Derivative, RateLim, or standard math functions) are strictly prohibited inside F-runtime groups; the safety compiler will abort with compilation error Block not permitted in F-Program.
* Custom SCL code cannot be inserted unless written and compiled under the specialized S7 F-Systems Safety Programming Environment with certified safety signatures.
Therefore, engineers must implement rate-of-change algorithms using pre-certified modular building blocks provided by the standard F-Library.
Mathematical Principle of Discrete Rate of Change Calculation
In discrete sampled systems, the time derivative of a continuous analog signal is approximated using backward finite differences:
$$
rac{dPV}{dt} pprox
rac{PV(t) - PV(t - \Delta t)}{\Delta t}$$
Where:
* $PV(t)$: The current, live process value output by the fail-safe analog channel block F_CH_AI.V.
* $PV(t - \Delta t)$: The historical process value captured $\Delta t$ seconds in the past.
* $\Delta t$: The measurement time base (e.g., 5 seconds, 30 seconds, or 1 minute).
To obtain $PV(t - \Delta t)$ safely without uncertified circular buffers, the F-Systems Library provides the certified delay block F_DEADTM (FB 320).
Step-by-Step CFC Implementation with F_DEADTM and Arithmetic F-Blocks
Follow this engineering workflow to construct a SIL 3 rated rate-of-change evaluation circuit in CFC:
- Place Fail-Safe Blocks in the Safety Chart:
* Open the safety CFC chart.
* From theF-AppLib/F-Systemscatalog, insert:F_DEADTM(FB 320 - Dead Time / Delay block).F_SUB_R(FB 347 - Fail-Safe Real Subtraction).F_DIV_R(FB 348 - Fail-Safe Real Division).F_LIM_RorF_CMP_R(FB 342 - Comparator to evaluate trip limits).
- Configure Signal Connections:
* ConnectF_CH_AI.V(the live analog floating-point value) to:F_DEADTM.INF_SUB_R.IN1(current value $PV(t)$).- Connect the delayed output
F_DEADTM.OUTtoF_SUB_R.IN2(historical value $PV(t - \Delta t)$).
- Configure Dead Time and Scaling:
* SetF_DEADTM.TIMEto your target measurement window (e.g.,T#10sfor rapid surges, orT#60sfor slow thermal drift).
* Connect the difference outputF_SUB_R.OUT($\Delta PV$) toF_DIV_R.IN1.
* ConfigureF_DIV_R.IN2with the numerical time constant representing $\Delta t$ in seconds or minutes (e.g.,10.0or1.0). - Link to Safety Interlocks:
* Feed the rate-of-change result fromF_DIV_R.OUTintoF_CMP_Rto compare against your maximum allowable rate threshold (e.g., $> 5.0^\circ ext{C/min}$).
* Interconnect the comparator output to your fail-safe shutdown matrix or emergency depressurization valve logic.
Verification
- In SIMATIC CFC, open the safety chart in dynamic test mode.
- Force a step change or ramp on the input signal of
F_CH_AI. - Verify that:
F_DEADTM.OUTtrails the live input by exactly the configured delay time.- During a steady ramp,
F_SUB_R.OUTdisplays a stable non-zero delta proportional to ramp velocity. - When the signal is constant, the calculated rate of change drops cleanly to
0.0. - Compile the safety program. Confirm that the F-Compiler calculates valid safety CRC signatures with zero errors.
Limitations and Operational Precautions
F_DEADTMutilizes internal ring buffer memory. Configuring excessively long dead times (e.g., several hours) consumes significant safety work memory.- High-frequency sensor noise on analog signals can cause artificial spikes in rate-of-change calculations. Filter raw input signals using the fail-safe smoothing block
F_PT1prior toF_DEADTMif electrical noise is present. - Ensure that division by zero is mathematically impossible: never assign
0.0toF_DIV_R.IN2.
Engineer FAQ
- Why can't I use the standard PCS 7 Derivative block (Derivative)?
Standard APL blocks lack fail-safe self-testing, redundant memory checking, and safety signatures. Placing a standard block in an F-runtime group invalidates the safety certificate of the entire CPU. - What happens to F_DEADTM during a safety CPU restart?
During a restart,F_DEADTMinitializes its buffer with the current input value, preventing false transient rate spikes during plant startup. - Is F_DEADTM certified for SIL 3 applications?
Yes.F_DEADTMis an official component of the TÜV-certified SIMATIC S7 F-Systems library, suitable for SIL 3 / Category 4 safety functions.
Technical References
- SIMATIC S7 F/FH Systems - Configuring and Programming Manual (A5E00278788).
- SIMATIC S7 F-Systems Library Description and Block Reference.
- IEC 61508 / IEC 61511: Functional Safety of Safety-Instrumented Systems for the Process Industry.
Related Articles
- Filtering High-Frequency Process Noise in S7 F-Systems Analog Safety Loops.
- Sizing Execution Cycle Times for Safety Runtime Groups in CPU 410-5H.
Related Tags
PCS 7, S7 F-Systems, F_CH_AI, F_DEADTM, Safety Integrated, SIL 3, Rate of Change, CFC