Configuring DCOM Handshakes and OPC Core Components for OpenPCS 7
When connecting a third-party OPC DA client to an OpenPCS 7 Server over DCOM, the error 'the server did not indicate that it was ready to receive connections' occurs when the OpenPCS 7 service (sopc_server.exe) starts but aborts its DCOM class registration. This failure occurs if WinCC Runtime is not fully active, server data packages are missing, or DCOM Identity is misconfigured. Do not install third-party OPC Core Components on the OpenPCS 7 server; Siemens installs certified, tested versions automatically. Resolve the error by ensuring WinCC Runtime is active, configuring OpenPCS 7 Server DCOM Identity to 'The Interactive User' or a dedicated SIMATIC HMI user, and opening TCP port 135 and dynamic RPC ports.
Table of Contents
- OpenPCS 7 DCOM Architecture: Class Registration and OPCEnum
- Why Installing Third-Party OPC Core Components on Servers Is Discouraged
- Root Causes of 'Server Did Not Indicate Readiness' Errors
- Step-by-Step DCOM Configuration and Identity Tuning in dcomcnfg
- OpenPCS 7 Server DCOM and Network Configuration Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
OpenPCS 7 DCOM Architecture: Class Registration and OPCEnum
SIMATIC OpenPCS 7 (6ES7658-0CX58-0YB0) provides standard OPC interfaces (OPC DA, OPC HDA, OPC A&E, and OPC UA) to exchange live process telemetry, historical trends, and alarm messages with third-party MES, ERP, and SCADA systems. When operating classic OPC DA over Distributed Component Object Model (DCOM):
- The third-party client connects to the Windows RPC endpoint mapper (TCP port 135) on the OpenPCS 7 host.
- The client queries the
OPCEnumservice to resolve the ProgID (OPC.SimaticNET) to its Class ID (CLSID). - DCOM launches the OpenPCS 7 executable (
sopc_server.exe/sopcds.exe). - The OpenPCS 7 server initializes internal handles, connects to the local WinCC DataManager, and calls
CoRegisterClassObjectto signal readiness to DCOM. - If
sopc_server.exeaborts its startup handshake, DCOM returns the error: 'The server did not indicate that it was ready to receive connections' (Error code0x80004005orCO_E_SERVER_STOPPING).
Why Installing Third-Party OPC Core Components on Servers Is Discouraged
Engineers frequently ask whether they should download and install the generic OPC Core Components Redistributable from the OPC Foundation website onto the OpenPCS 7 server. In SIMATIC PCS 7, the official rule is:
Do NOT install standalone third-party OPC Foundation Redistributables on a Siemens OpenPCS 7 or WinCC server.
When OpenPCS 7 or WinCC is installed, the Siemens setup automatically installs certified, hardened builds of the OPC Core Components and OPCEnum. Installing third-party packages overwrites Siemens-registered proxy/stub DLLs (opcproxy.dll, opccmn_ps.dll) and can disrupt internal WinCC communications and HMI faceplate operation. The third-party client PC does require OPC Core Components, but the server must remain on Siemens-supplied binaries.
Root Causes of 'Server Did Not Indicate Readiness' Errors
Three predominant system conditions prevent OpenPCS 7 from completing its DCOM readiness handshake:
- WinCC Runtime Inactivity: OpenPCS 7 is an abstraction gateway; it does not store process tags. If WinCC Runtime is inactive, or if the OpenPCS 7 station has not imported server data packages (
*.pck) from the OS Servers,sopc_server.execannot attach to the WinCC DataManager and exits immediately. - DCOM User Identity Mismatch: If the DCOM identity in
dcomcnfgis configured as 'The Launching User', the server attempts to launch under the remote client's network credentials. If that user does not exist locally with identical passwords and membership inSIMATIC HMI, launch fails. - Missing OpenPCS 7 License: If the required OpenPCS 7 license key is missing in Automation License Manager, the server terminates after a brief startup check.
Step-by-Step DCOM Configuration and Identity Tuning in dcomcnfg
Configure DCOM properties on the OpenPCS 7 server machine to enable reliable third-party client connections:
- Launch Component Services: Press
Win+R, typedcomcnfg, and press Enter. - Navigate to DCOM Applications: Expand Console Root -> Component Services -> Computers -> My Computer -> DCOM Config.
- Configure OPCEnum Properties:
- LocateOPCEnum, right-click and select Properties.
- On the Security tab, under Launch and Activation Permissions, select Customize -> Edit.
- AddEveryone,ANONYMOUS LOGON, andInteractive User; grant Local Launch, Remote Launch, Local Activation, and Remote Activation. - Configure OpenPCS 7 Server Properties:
- LocateOpenPCS 7 Server(orSIMATIC OpenPCS 7).
- On the Identity tab, select The Interactive User (if an operator is always logged into the server desktop) or select This user and enter a dedicated local Windows administrator account that belongs toSIMATIC HMIandSIMATIC NET.
- On the Security tab, grant full Remote Access and Remote Activation permissions to the client user. - Windows Firewall Rules: Open TCP port
135(RPC Endpoint Mapper) and configure a rule allowingsopc_server.exeandopcenum.exethrough the firewall.
OpenPCS 7 Server DCOM and Network Configuration Matrix
The following table details system requirements and settings for OpenPCS 7 connectivity:
0x80004005)Activate in WinCC)SIMATIC HMI, Distributed COM0x80070005[!NOTE]
Commercial Accuracy Notice: SIMATIC OpenPCS 7 requires a dedicated software package license (6ES7658-0CX58-0YA5). > Client connections consume OpenPCS 7 tag/station authorizations. Always verify client connection limits and license > entitlements against official Siemens catalog documentation.
Verification
Verify that the third-party client connects cleanly to OpenPCS 7:
- Local OPC Scout Validation: On the OpenPCS 7 server, open SIMATIC NET OPC Scout V10. Browse local servers, connect to OpenPCS 7, and monitor tags. Confirm clean local acquisition.
- Remote Client Connection: Launch the third-party OPC client on the remote PC. Browse the server host via IP/hostname. Confirm that
OPCEnumsuccessfully discovers the OpenPCS 7 server CLSID. - Tag Subscription: Add process tags to an active group. Verify that tag values update cyclically with Quality
Goodwithout triggering DCOM timeout popups.
Limitations and Operational Precautions
Observe these guidelines when operating OpenPCS 7 with third-party clients:
- Avoid Workstation Multi-Tenancy: When OpenPCS 7 is installed on an active WinCC client workstation, configure DCOM identity carefully to ensure client crashes do not disrupt operator faceplate responsiveness.
- Prefer OPC UA for Modern Integration: Classic DCOM is notoriously sensitive to Windows security patches (such as Microsoft DCOM hardening updates CVE-2021-26414). For new integrations, deploy the OpenPCS 7 OPC UA Server interface to eliminate DCOM entirely.
- Network Routing: Ensure the Terminal Bus network provides low-latency communication (<10 ms) between client and server.
Engineer FAQ
Should I install the OPC Core Components on my OpenPCS 7 server?
No. The Siemens OpenPCS 7 setup installs certified, tested versions of OPC Core Components automatically. Installing generic third-party redistributables can overwrite Siemens DLLs and disrupt WinCC.
What does 'the server did not indicate that it was ready to receive connections' mean?
DCOM launched the server process, but the process aborted before registering its class with DCOM. The most common cause is WinCC Runtime being inactive or DCOM identity permissions being rejected.
Why can't my client browse the list of OPC servers on the machine?
OPCEnum is blocked by Windows Firewall, lacks DCOM launch permissions, or is disabled in Windows Services. Grant Remote Launch/Activation to Everyone in OPCEnum properties.
How do Microsoft DCOM Hardening patches affect OpenPCS 7?
Microsoft security updates require packet-level authentication (RPC_C_AUTHN_LEVEL_PKT_INTEGRITY). Verify that your third-party OPC client supports DCOM packet integrity, or migrate to OPC UA.
Technical References
- SIMATIC PCS 7 OpenPCS 7 Operating and Configuration Manual (Entry ID 109780813)
- WinCC V7.4 Communication Manual: OPC Interfaces and DCOM (Entry ID 109736225)
- Microsoft DCOM Hardening Guidance and PCS 7 Compatibility (Entry ID 109805988)
- Siemens Industry Online Support FAQ on OpenPCS 7 DCOM Troubleshooting (Entry ID 109756840)
Related Articles
- Architecture and Licensing of OpenPCS 7 V8.1 on SIMATIC IPC Bundles
- Configuring OS Simulation in SIMATIC PCS 7 Engineering Stations
- Resolving WinCC OS Server S7 Connection Failures After Adding New Plant Areas