Configuring Modbus TCP Client Communication from S7-400 to Weidmuller UR20 Couplers in PCS 7

Configuring Modbus TCP Client Communication from S7-400 to Weidmuller UR20 Couplers in PCS 7

Integrating a Weidmuller UR20-FBC-MOD-TCP-V2 remote I/O station into SIMATIC PCS 7 V9.1 requires configuring an Open User Communication S7 connection and parameterizing the licensed SIMATIC Modbus/TCP Redundant or Single library blocks (MB_CPCL / MB_REDSV). In the CFC chart, engineers define remote IP addresses, Modbus register offset mappings for Weidmuller analog and digital slices, and register polling cycles to unpack distributed field variables into standard PCS 7 channel drivers.

Table of Contents

Architecture of Modbus TCP Integration in SIMATIC PCS 7

In process facilities, third-party remote I/O stations (such as Weidmuller u-remote UR20 series) provide distributed digital and analog interfacing over Ethernet:
* The Weidmuller UR20-FBC-MOD-TCP-V2 operates as a Modbus TCP Server (Slave), listening on standard TCP port 502.
* The SIMATIC S7-400 or CPU 410 station acts as the Modbus TCP Client (Master), initiating cyclical read and write transactions to exchange I/O image data.
* Communication executes over an Industrial Ethernet communications processor (CP 443-1) or CPU integrated PROFINET interface using the official Siemens SIMATIC Modbus/TCP block library.

Hardware Profile: Weidmuller UR20-FBC-MOD-TCP Coupler and I/O Mapping

The Weidmuller UR20 station maps physical slice modules (AI, AO, DI, DO) into continuous Modbus register tables configured via its internal web server:
* Digital Inputs (DI): Mapped to Discrete Inputs (Function Code 02, address range 10001+) or packed into Input Registers (FC04, address range 30001+).
* Analog Inputs (AI): Mapped to Input Registers (Function Code 04, address range 30001+ or Holding Registers 40001+). Each analog channel occupies one 16-bit word (INT).
* Digital Outputs (DO): Mapped to Coils (Function Code 01/15, address range 00001+).
* Analog Outputs (AO): Mapped to Holding Registers (Function Code 03/16, address range 40001+).

Configuring the S7-400 Modbus TCP Client Block (MB_CPCL / MB_REDSV)

To configure Modbus polling in a CFC chart:
1. Network Connection: In NetPro, establish an unspecified TCP connection (or configure dynamic Open User Communication parameters in the data block).
2. Instantiate Driver Block:
* In CFC, instantiate MB_CPCL (Modbus Client via CP) or MB_REDSV (Redundant Modbus Server/Client) from the SIMATIC Modbus/TCP library.
* Schedule the block in a dedicated cyclic interrupt OB (typically OB35 at 100 ms or OB34 at 200 ms).
3. Parameterize the MODBUS_PARAM Data Block:
* IP_ADDR: Set the IPv4 address of the Weidmuller coupler (e.g., 192.168.1.50).
* PORT: Set remote TCP port to 502.
* UNIT_ID: Typically set to 1 (or 255).
* DATA_TYPE: Select Modbus function code (e.g., 16#04 for Read Input Registers).
* START_ADDR: Define starting register address (e.g., 0 or 1).
* LENGTH: Define number of words to read (e.g., 16 words for 16 analog channels).
4. License Registration:
* Enter the Siemens Modbus runtime license key into the license parameter block (LICENSED = TRUE), preventing the driver from generating unlicensed demo timeout errors.

Mapping Modbus Register Buffers to PCS 7 Channel Drivers

Once data is cyclically read into the S7 communication data block:
* Signal Unpacking: Use an SCL unpacking block or standard CFC conversion blocks to separate individual words and bits from the receiving array.
* APL Channel Driver Interconnection:
* For analog inputs, route the 16-bit integers to standard Pcs7AnIn or FbAnIn blocks, applying engineering unit scaling (e.g., 0 to 27648 or 4000 to 20000).
* For digital signals, unpack boolean bits and route them to Pcs7DiIn blocks or directly to technological interlocks (Interlck, MonDiL).
* Quality Code Handling: If the Modbus block reports communication error (ERROR = 1), pass bad signal status (16#00) to the channel drivers to trigger fail-safe hold or substitute values.

Verification

  • In SIMATIC Manager Variable Table (VAT), monitor the Modbus receive data block: verify that raw register values change when field voltages or contacts toggle.
  • In CFC dynamic test mode, confirm that MB_CPCL.DONE = 1 and ERROR = 0.
  • In Weidmuller web server diagnostics, verify that active TCP connections report established status with zero CRC frame errors.
  • In WinCC OS runtime, verify that process values display smoothly on APL faceplates.

Limitations and Operational Precautions

  • SIMATIC Modbus/TCP blocks require a runtime software license per CPU; running without a valid license causes the block to stop communicating after a trial period.
  • Modbus TCP communication is non-deterministic compared to native PROFINET IO; avoid using Modbus TCP for fast safety-instrumented shutdown loops.
  • Set appropriate TCP keep-alive and connection timeout parameters to ensure the S7-400 detects coupler power loss within 2 to 3 seconds.

Engineer FAQ

  • What port does the Weidmuller UR20 Modbus TCP coupler listen on?
    Standard Modbus TCP port 502.
  • What S7 block library is used for Modbus TCP communication in PCS 7?
    The official Siemens SIMATIC Modbus/TCP library (e.g., Modbus/TCP CP or Modbus/TCP RED V2).
  • Does Modbus TCP require a hardware communications processor?
    It can communicate via an Ethernet CP (e.g., CP 443-1) or directly through the integrated PN interface of CPU 410-5H.
  • How is licensing handled for SIMATIC Modbus/TCP blocks?
    Each CPU requires an individual runtime license registered via an activation key matched to the CPU hardware serial number.
  • What function code reads analog inputs from the Weidmuller coupler?
    Function Code 04 (Read Input Registers) or Function Code 03 (Read Holding Registers).
  • What happens if the Weidmuller coupler loses Ethernet connectivity?
    The Modbus block sets ERROR = 1 with an error status word, and channel drivers transition to bad quality code.
  • Can I write digital outputs to the Weidmuller coupler?
    Yes, using Function Code 05 (Write Single Coil) or Function Code 15 (Write Multiple Coils).
  • What is the Unit ID parameter in Modbus TCP?
    It represents the internal device slave address, typically set to 1 for standalone modular couplers.
  • How do I configure multiple read/write requests with a single Modbus client block?
    Configure a state machine or request scheduler in CFC that cycles through multiple MODBUS_PARAM records sequentially.
  • Can Weidmuller UR20 integrate via PROFINET instead of Modbus TCP?
    Yes, Weidmuller provides a PROFINET coupler (UR20-FBC-PN) that integrates directly into HW Config using a standard GSDML file.

Technical References

  • Siemens SIMATIC Modbus/TCP Communication Manual
  • Weidmuller u-remote UR20-FBC-MOD-TCP System Manual
  • Siemens Industry Online Support Entry: Modbus TCP Client Configuration in S7-400 (Entry ID 299185)
  • SIMATIC PCS 7 Advanced Process Library (APL) Function Manual

Related Articles

Related Tags

PCS 7, Modbus TCP, S7-400, Weidmuller, UR20, MB_CPCL, Industrial Ethernet, Remote IO, Open User Communication, Licensing