Configuring Permanent Column Widths in PCS 7 WinCC AlarmControl
To prevent column widths in the SIMATIC PCS 7 alarm system from reverting to defaults every time an operator closes and reopens the alarm window, configure the column dimensions centrally in SIMATIC Manager or adjust the AlarmControl inheritance properties in WinCC. By default, the WinCC AlarmControl enforces 'Apply project settings' (Projekteinstellungen übernehmen), which overwrites manual runtime resizing with central project parameters. To establish permanent column widths across all Operator Stations, navigate to 'Options -> PCS 7 message system -> Configure...' in SIMATIC Manager, select 'Configure message lists', define fixed column widths in pixels, and run the OS Project Editor to deploy the standardized layout.
Table of Contents
- Runtime Resizing vs Project Inheritance in WinCC AlarmControl
- Why Column Widths Reset Upon Window Reopening
- Central Message Configuration vs Local Picture Properties
- Comparison of Column Width Configuration Approaches
- Step-by-Step Procedure to Set Permanent Alarm Column Widths
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Runtime Resizing vs Project Inheritance in WinCC AlarmControl
In SIMATIC PCS 7, the alarm banner and dedicated message screens are rendered by the WinCC AlarmControl active component. During commissioning, operators frequently drag column borders with the mouse to expand truncated event texts or date/time strings. However, as soon as the operator navigates to another graphic picture and returns to the alarm screen, the columns snap back to their original narrow widths.
This behavior is governed by the design principle of Basic Process Control (BPC). PCS 7 enforces central template inheritance to ensure that all operator stations in a control room present identical, standardized alarm views regardless of local user actions.
Why Column Widths Reset Upon Window Reopening
Understanding the property hierarchy inside WinCC AlarmControl explains the reset mechanism:
-
Apply Project SettingsFlag: In AlarmControl properties underMessage blocks, the optionApply project settings(Projekteinstellungen übernehmen) is enabled by default. Whenever the picture window loads, AlarmControl queries the central project configuration and applies those widths, overriding local runtime modifications. -
Write-Protected Alarm Logging: In PCS 7, column properties inside the classic WinCC Explorer Alarm Logging editor are write-protected (assigned author ID
CREAT_ID = 10210). Direct editing in Alarm Logging is blocked to prevent conflicts with the OS Project Editor. -
Persistence Mechanism: To make column widths permanent, changes must be injected either through SIMATIC Manager's central configuration dialog or by decoupling local AlarmControl objects from project inheritance.
Central Message Configuration vs Local Picture Properties
Engineers have two methods to achieve stable column sizing:
-
Central PCS 7 Configuration (Recommended): Using
SIMATIC Manager -> Options -> PCS 7 message system -> Configure.... This tool sets uniform column widths across all OS Servers and Clients, guaranteeing total multiproject consistency. -
Local Picture Modification: Opening
@messageview.pdlin the WinCC Graphics Designer, uncheckingApply project settingsin AlarmControl, and saving custom pixel widths directly into the PDL. While effective for single stations, this requires manual maintenance on every OS.
Comparison of Column Width Configuration Approaches
The table below contrasts the different methods of adjusting alarm column widths in SIMATIC PCS 7.
SIMATIC Manager -> Options -> Message System@messageview.pdl)dbo.MSBlock editStep-by-Step Procedure to Set Permanent Alarm Column Widths
Follow this procedure to configure permanent alarm column widths using the official Siemens central configuration workflow:
-
Open Central Message Configuration in SIMATIC Manager:
- In SIMATIC Manager, select menuOptions -> PCS 7 message system -> Configure.... -
Configure Target Message Lists:
- Switch to theConfigure message lists(Meldelisten konfigurieren) tab.
- For each message list (e.g.,Alarm list,Acknowledged alarm list,Long-term archive list), check theConfigurecheckbox.
- The WinCC AlarmControl properties dialog opens. -
Set Column Widths in Pixels:
- In the AlarmControl dialog, switch to theMessage liststab.
- UnderDisplayed columns, select a column (e.g.,Event textorDate).
- Adjust theWidthparameter (e.g., increaseEventfrom 150 pixels to 280 pixels, or set character width appropriately).
- Repeat for all required columns and clickOK. -
Activate and Rebuild Screens:
- Ensure theActivatecheckbox is selected for all modified lists in the SIMATIC Manager dialog.
- ClickOKto commit changes to the multiproject database.
- Open WinCC Explorer on the target OS: run the OS Project Editor and clickOKto regenerate standardized screens.
- Download the OS project to the target operator stations.
Verification
Verify alarm column formatting through the following checks:
1. Launch WinCC Runtime: open the main alarm screen and verify that columns display the wider pixel widths.
2. Close the alarm screen, navigate through several plant graphic screens, and return to the alarm screen: confirm that column widths remain stable.
3. Trigger an alarm with long descriptive text: verify that the text displays cleanly without truncation or ellipsis (...).
4. Verify that all OS Clients connected to the server display identical, aligned column dimensions.
Limitations and Operational Precautions
Avoid setting column widths excessively wide on low-resolution displays (e.g., 1024x768). Overly wide columns will force the horizontal scrollbar to appear, requiring operators to scroll sideways to view timestamps or acknowledgment statuses during plant emergencies. Always balance column expansion against total available horizontal screen resolution.
Engineer FAQ
Can operators save their personal column widths at runtime?
No. In standard PCS 7 Basic Process Control, runtime column layout persistence per operator is intentionally blocked to ensure standardized situational awareness across shifts.
Why is the Alarm Logging editor column width field greyed out in WinCC?
PCS 7 marks the alarm blocks as read-only (CREAT_ID = 10210) because they are managed centrally by the OS Project Editor and SIMATIC Manager.
Does changing column width require stopping WinCC Runtime?
No. The OS Project Editor can update screen templates while runtime is active, but a screen reload (or project download) is required to apply the new visual framework.
Technical References
- SIMATIC Process Control System PCS 7 Operator Station Manual - Alarm System
- SIMATIC PCS 7 Compendium Part A - Handling the Message System V9.0
- Siemens Technical Support: Adjusting Column Widths in WinCC AlarmControl (SIOS Entry ID 109756485)
Related Articles
- Deactivating Batch Name and Custom Columns in PCS 7 Message Lists
- Configuring Analog Alarm Limits and Messages in PCS 7 CFC vs WinCC
- Displaying Single Process Alarms Across Multiple Plant Hierarchies and Control Rooms