Configuring Rising-Edge-Only Alarm Generation with ALARM_8P and Event Blocks in SIMATIC PCS 7

Configuring Rising-Edge-Only Alarm Generation with ALARM_8P and Event Blocks in SIMATIC PCS 7

In SIMATIC PCS 7, generating a process alarm strictly on the rising edge (0 to 1 transition) without an outgoing or leaving message requires configuring the message class in the S7 Message Configuration dialog or using dedicated event blocks such as Event (FB1811) or EventTs (FB1823). When using ALARM_8P (SFB35), configure the message class as an 'Operating Message' or 'Message without acknowledgment' without an outgoing state, or decouple the signal input using edge-evaluation logic to suppress the falling-edge trigger.

Table of Contents

Operating Principles of ALARM_8P Edge Evaluation in S7-400

The standard block message generator in SIMATIC S7-400 controllers is the system function block ALARM_8P (SFB35). ALARM_8P monitors up to eight binary signal inputs (SIG_1 through SIG_8) cyclically. By design, the block evaluates both signal transitions:
* Rising Edge (0 -> 1): Generates an Incoming (+) alarm state and initiates acknowledgment requirements.
* Falling Edge (1 -> 0): Generates an Outgoing (-) alarm state, clearing the active alarm in WinCC Alarm Logging.

When process engineers require an alarm or operator notification to trigger strictly on an instantaneous event (e.g., button pressed, cycle started, transient trip condition) without generating a cleared/leaving message or leaving an unacknowledged orphan alarm on the screen, relying on raw ALARM_8P behavior causes complications. If SIG_1 falls back to 0, WinCC records a leaving event. Furthermore, if SIG_1 remains 1 until acknowledged, the signal cannot re-trigger a new alarm upon subsequent process cycles without an explicit reset.

Alarm Block Selection Matrix for Edge and Operational Messaging

Select the appropriate messaging block and configuration method based on functional requirements:

Block Type / NumberLibrary OriginSignal EvaluationOutgoing (-) Message Generated?Best Use Case in PCS 7ALARM_8P (SFB35)S7 System Function BlockLevel with edge detection on 8 signalsYes (configurable by message class)Standard analog/digital threshold alarms with persistent trip statesEvent (FB1811)PCS 7 Advanced Process Library (APL)Edge-triggered notification on binary inputsOptional (suppressible via feature bit)Operator event logging, batch step execution notificationsEventTs (FB1823)PCS 7 APL LibraryHigh-precision time-stamped edge detectionOptional (suppressible via feature bit)Sequence of Events (SOE) millisecond recording for electrical tripsALARM_8 (SFB33)S7 System Function BlockLevel with edge detection (no associated values)YesSimple binary alarm generation without analog process tagsCustom Logic + SFB35User CFC Chart LogicR_TRIG or SR Flip-Flop gating SIG_xSuppressed via WinCC Message Class settingsLegacy system retrofit where standard APL blocks cannot be inserted

Licensing & PO notice: Standard APL Event blocks consume AS RT Process Objects when compiled with alarm attributes; verify license capacity before block expansion.

Configuring Rising-Edge Messaging in S7 Message Configuration

The cleanest method to eliminate outgoing messages without adding custom CFC logic is to adjust the message class inside the S7 Message Configuration:

  1. Open Block Message Properties in CFC:
    * Right-click the instance block calling ALARM_8P (or the block itself in the CFC chart).
    * Select Special Object Properties > Messages.
  2. Modify Message Class Assignment:
    * In the Message Configuration dialog, locate the specific signal row (SIG_1 to SIG_8).
    * By default, the Message Class is set to Alarm - High or Warning - High, which enforces both incoming and outgoing states.
    * Change the Message Class to:
    • Operating Message - Standard (or Operational Message), or
    • Message without acknowledgment - Incoming only.
    • In the WinCC message class configuration, messages configured under this class do not track or display a falling-edge state.
  3. Compile and Download OS:
    * In SIMATIC Manager, right-click the OS project and execute Compile OS.
    * Scope: Changes only. The compilation updates the WinCC Alarm Logging database to treat the message as an instantaneous incoming event.

Alternative Edge Logic Using CFC Flip-Flops and Event Blocks

If a custom block requires programmatic control over message resetting using controller logic:
1. Using APL Event Block (FB1811):
* Place Event (FB1811) in the CFC chart.
* Connect the process trigger to input In1.
* Configure Feature.Bit0 (Set message behavior) to evaluate rising edge only. The block automatically handles pulse shaping and sends the notification to WinCC without generating a leaving event.
2. Using CFC Logic with ALARM_8P and Flip-Flop (FC389 / SR):
* Insert an R_TRIG (Rising edge detector) or RS flip-flop ahead of SIG_1.
* Evaluate the ACK_STATE output of ALARM_8P. ACK_STATE contains bits 0-7 indicating the acknowledgment status of incoming messages for signals 1-8.
* Latch the input using the flip-flop upon process signal rising edge.
* Use the corresponding acknowledgment bit from ACK_STATE or a timer pulse to reset the flip-flop, ensuring the input returns to 0 cleanly before the next event occurs.

Verification

Verify rising-edge alarm behavior:
1. Trigger the process signal (0 -> 1 transition) on the controller.
2. Open the WinCC Alarm Control in Runtime. Confirm that an Incoming (+) alarm entry is registered with the current timestamp.
3. Return the process signal to 0.
4. Confirm that no Outgoing (-) entry appears in the WinCC Alarm Logging list.
5. Trigger the process signal a second time (0 -> 1) and confirm that a new Incoming (+) alarm is immediately logged without deadlocks.

Limitations and Operational Precautions

  • Operational messages configured as 'Incoming only' cannot be used for critical safety interlocks or shutdown trips where operators must be aware of persistent faulted states.
  • Generating rapid bursts of edge-triggered messages can flood the controller's communication buffer and WinCC Alarm Logging queue. Implement minimum re-trigger suppression timers (e.g., 500 ms) for fluttering signals.
  • When using ACK_STATE feedback logic, be aware that remote acknowledgment from WinCC can take several controller scan cycles to propagate back to the AS.

Engineer FAQ

Can ALARM_8P be triggered by a single-cycle pulse in CFC?

Yes. However, the signal pulse must remain active for at least one full execution cycle of the block's runtime group (OB 30-38). If the pulse is generated and cleared within an interrupt routine faster than the cyclic OB, ALARM_8P will miss the edge.

Why does WinCC show an unacknowledged alarm even after the signal returned to zero?

Standard PCS 7 alarm classes require operator acknowledgment regardless of whether the physical signal has cleared. To prevent this, use a message class that does not require acknowledgment (such as Log Message or Operational Message).

What is the difference between FB1811 (Event) and FB1823 (EventTs)?

FB1811 utilizes standard cyclic CPU timestamps. FB1823 (EventTs) interfaces with high-precision time-stamping hardware (e.g., ET 200M IM 153-2 with 1 ms SOE capability) to record exact field contact transition times.

Technical References

Related Articles

Related Tags

  • ALARM_8P
  • SFB35
  • Rising Edge
  • Event Block
  • FB1811
  • CFC Messaging
  • Alarm Logging