Configuring WinCC as an OPC UA Client to Exchange Data with S7-1500 in SIMATIC PCS 7
In SIMATIC PCS 7 V8.1, integrating an S7-1500 controller via OPC UA is implemented at the WinCC OS layer using the native WinCC OPC UA Client channel rather than at the S7-400 AS level. WinCC Tag Management connects directly to the S7-1500 integrated OPC UA Server endpoint over Industrial Ethernet, allowing process tags to be browsed, read, and written securely using digital certificates without requiring third-party middleware or hardware gateways.
Table of Contents
- OPC UA Integration Architecture in PCS 7 Environments
- Step-by-Step Procedure to Configure WinCC OPC UA Client
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
OPC UA Integration Architecture in PCS 7 Environments
Integrating modern S7-1500 controllers into an established SIMATIC PCS 7 V8.1 architecture involves distinct architectural considerations:
* AS-Level Limitations: S7-400 and S7-410 automation stations running standard PCS 7 libraries cannot act as native OPC UA clients within CFC charts. While AS-to-AS data exchange can be performed via S7 communication (BSEND/BRECV) or Modbus TCP, exchanging data with an S7-1500 via OPC UA is hosted at the WinCC Operator Station (OS) level.
* WinCC OPC Communication Channel: SIMATIC WinCC V7.3 (the underlying SCADA engine of PCS 7 V8.1) incorporates a native OPC Channel supporting both Classic OPC (DA, HDA, A&E) and OPC Unified Architecture (OPC UA).
* S7-1500 OPC UA Server: Starting with firmware V2.0, SIMATIC S7-1500 CPUs incorporate a built-in OPC UA Server compliant with IEC 62541, capable of exposing optimized and non-optimized data blocks directly over TCP port 4840.
+-------------------------------------------------------------+
| SIMATIC S7-1500 Controller (TIA Portal) |
| Integrated OPC UA Server (Endpoint: opc.tcp://192.168.1.50) |
+-------------------------------------------------------------+
|
v Industrial Ethernet (Port 4840)
+-------------------------------------------------------------+
| SIMATIC PCS 7 WinCC OS Server (WinCC V7.3) |
| WinCC Tag Management -> OPC Channel -> OPC UA WinCC Client |
+-------------------------------------------------------------+
|
v
+-------------------------------------------------------------+
| WinCC Runtime Graphics, Faceplates, and Tag Logging Archive |
+-------------------------------------------------------------+
Step-by-Step Procedure to Configure WinCC OPC UA Client
Follow this procedure to establish an authenticated OPC UA client connection from PCS 7 WinCC V8.1 to an S7-1500 CPU.
Prerequisites
- S7-1500 CPU configured in TIA Portal with OPC UA Server enabled, runtime license assigned, and DB tags set to "Accessible from HMI/OPC UA".
- Network routing and firewall rules configured to allow bidirectional traffic on TCP port 4840.
- Administrative privileges on the PCS 7 Engineering / OS Server station.
Step 1: Enable OPC UA Channel in WinCC Tag Management
- Open the target OS project in WinCC Explorer.
- Right-click Tag Management and select Add new driver.
- In the driver selection dialog, select OPC.chn and click Open.
- The OPC communication driver appears in the Tag Management tree with sub-nodes for
OPC ClassicandOPC UA WinCC Channel.
Step 2: Configure OPC UA Server Connection
- Expand the
OPCdriver node, right-click OPC Groups (OPC UA WinCC Channel), and select System Parameter. - In the OPC UA Configuration dialog, navigate to the Server tab.
- Click Add Server and enter the connection details:
* Server Name: Enter a descriptive tag (e.g.,S7_1500_Packaging).
* Server URL: Enter the endpoint URL:opc.tcp://<S7-1500_IP_Address>:4840 - Select the desired Security Policy:
* For testing:None
* For production:Basic256Sha256with message securitySign & Encrypt. - Under Authentication, select
Anonymousor enter user credentials configured in the S7-1500 security settings.
Step 3: Certificate Exchange and Trust Validation
- If using encrypted security profiles, initiate a connection test. The S7-1500 will reject the initial connection because the WinCC client certificate is untrusted.
- In TIA Portal, open the S7-1500 CPU properties under OPC UA -> Server -> Certificate Manager. Move the WinCC client certificate from
Rejected CertificatestoTrusted Certificates. - On the WinCC OS Server, open the OPC UA certificate store (located in
C:\ProgramData\Siemens\OPC\PKI\rejected) and move the S7-1500 server certificate into thetrustedfolder.
Step 4: Browse and Map S7-1500 Tags
- In WinCC Tag Management, right-click the configured connection and select Browse Server.
- The OPC UA address space loads dynamically, displaying the S7-1500 PLC data blocks under
Objects -> PLC -> DataBlocksGlobal. - Select the required process tags and click Add Tags. WinCC automatically creates the corresponding internal process tags with appropriate data types.
Verification
- In WinCC Explorer, activate Runtime.
- Open the WinCC Channel Diagnosis tool (
WinCC Explorer -> Tools -> Channel Diagnosis). - Locate the
OPCchannel and expand the OPC UA connection. Verify that the channel status reportsReadywith a green checkmark and that the read/write counter increments continuously. - Create a test graphic in Graphics Designer with an I/O field linked to an S7-1500 process tag; verify that live process values update dynamically.
Limitations and Operational Precautions
- Tag Licensing: Tags mapped from the S7-1500 via the OPC UA channel consume WinCC OS Runtime process tag licenses. Ensure your WinCC license size covers the added tags.
- Update Frequency: Do not set OPC UA subscription scan rates faster than necessary; querying hundreds of tags at sub-100ms intervals can saturate the S7-1500 CPU communication budget.
- Certificate Expiration: Self-signed certificates generated in TIA Portal or WinCC have finite validity periods (typically 1 to 5 years). Document expiration dates to prevent sudden communication failure upon certificate expiration.
Engineer FAQ
- Can S7-400 CFC blocks read S7-1500 tags via OPC UA directly?
No. S7-400 CPUs do not support native OPC UA client blocks in CFC. If AS-level logic requires S7-1500 data, configure S7 communication usingBSEND/BRECVblocks or Modbus TCP. - Does WinCC V7.3 support OPC UA historical data access (HDA)?
WinCC V7.3 supports OPC UA Data Access (DA) as a client. OPC UA HDA client capabilities are limited; historical values are typically logged within WinCC Tag Logging using cyclic DA acquisition. - Why does the OPC UA connection fail with 'BadSecurityChecksFailed'?
This error indicates an unexchanged or untrusted certificate, or a severe clock synchronization discrepancy (greater than 5 minutes) between the OS Server and S7-1500 CPU. - Can redundant PCS 7 OS servers connect to the same S7-1500 OPC UA server?
Yes. Both Master and Standby OS servers must have their individual client certificates trusted in the S7-1500 CPU. - Is an additional license required on the S7-1500 for OPC UA?
Yes. Enabling the OPC UA Server on an S7-1500 requires a SIMATIC OPC UA S7-1500 Small, Medium, or Large runtime license depending on the CPU model.
Technical References
- Siemens Industry Online Support Entry ID 109769234: Connecting S7-1500 to WinCC via OPC UA.
- Siemens Manual: WinCC V7.3 Communication Manual - OPC Channel.
- OPC Foundation Standard: IEC 62541 - OPC Unified Architecture Specification.
Related Articles
- [[Configuring OpenPCS 7 as an OPC UA Server for Third-Party Systems]]
- [[Establishing S7 Communication Between S7-400 and S7-1500 Controllers]]
- [[Managing Secure Digital Certificates in SIMATIC Industrial Networks]]