Convert F-CH_AI Raw Input Values to Engineering Units

Convert F-CH_AI Raw Input Values to Engineering Units

F_CH_AI processes an analog F-I/O raw value and presents a REAL process value at its V output; a displayed hexadecimal WORD is a bit representation of the raw channel value, not a floating-point engineering-unit value. Interpret the raw code using the selected analog module's range and channel configuration, then apply the block's configured engineering limits. When SIM_ON is active, SIM_V supplies the simulated value in the F-channel block's expected input-value range; it does not mean that a WORD should be reinterpreted as an IEEE-754 REAL.

Table of Contents

Raw channel value and engineering value are different

The input WORD represents the channel's raw digital code. Siemens analog documentation uses nominal bipolar values such as −27648 to +27648 for −100% to +100% in applicable ranges, but raw encoding depends on module type, selected range, and diagnostics. A code displayed in hexadecimal should first be interpreted according to the block/module data definition, including signedness; do not convert its displayed hex digits directly into a REAL bit pattern.

Understand the F_CH_AI output and scaling

The source reply describes F_CH_AI scaling the raw input to configured high and low engineering limits (VHRANGE and VLRANGE). The exact parameter names, data types, and block version must be confirmed in the installed F-library help. Conceptually, for an applicable linear range, raw input is normalized according to the configured module range and mapped to the engineering span. Bipolar and unipolar/live-zero ranges have different raw-to-percent relationships, so one generic raw formula cannot cover every channel.

Interpret simulated input

Siemens Safety Matrix documentation describes SIM_ON switching the F-channel driver to simulation and routes simulation values through SIM_V; where preprocessing is configured, the simulation value may first be transformed and inverse-transformed so it matches the F-channel driver's value range. Therefore, ensure the source value feeding SIM_V is expressed in the expected range for that specific block and signal path. Do not assume it is the final temperature or pressure unit unless the block documentation/configuration says so.

Practical conversion workflow

  1. Identify the exact F-module and analog channel, including configured measurement range and wiring mode.
  2. Check the module manual's raw-value representation and diagnostic/overflow codes for that range.
  3. Inspect the F_CH_AI version and its parameter help for raw input, SIM_V, SIM_ON, and output V behavior.
  4. Read the configured engineering high/low limits and any upstream preprocessing.
  5. For live data, compare the raw input and V against a known input or approved simulator. For simulation, enable it only in a controlled test and verify that changing the intended simulated value produces the expected V without affecting production operation.

Verification

Use the block online view and the module's diagnostic/status information to inspect raw input and converted V together. Confirm at least two safe, known points spanning the configured range and check the output unit. Test SIM_V separately from the live channel and verify simulation status. A plausible display at one point does not confirm correct range, polarity, wiring, or scaling.

Limitations and Operational Precautions

The source omits the F-module model, measurement range, F-library version, and exact hexadecimal example, so an exact conversion cannot be calculated. Siemens' ±27648 convention applies only to the relevant ranges; unipolar and live-zero channels differ. F-channel simulation and safety-related signals must be tested under the plant's approved safety and operating procedures. Do not force simulation or change range parameters on a live safety system without authorization and risk review.

Engineer FAQ

Is the WORD hexadecimal value already a REAL? No. It is a raw code representation; the engineering value is separately scaled and output as a REAL by the configured channel processing.

Can I always treat 0x9400 as −27648? No. Decode according to the defined signed representation and module/channel format, then confirm the configured range.

Does SIM_V take the final engineering-unit value? Only if the installed block and signal path specify that range; the F-channel block's input range may be different from a downstream preprocessed range.

What determines the conversion? The module's measurement range and raw encoding, the F_CH_AI version/configuration, its engineering limits, and any preprocessing.

Technical References

  • Siemens, SIMATIC S7 analog value processing application: raw value representation and nominal ±27648 scaling for the applicable range. Confirm module-specific details in the actual module manual: https://support.industry.siemens.com/cs/attachments/109748759/109748759_Application_Oversampling_V1_1_de.pdf
  • Siemens, PCS 7 V10.0 / SIMIT V11.2 Getting Started: describes conversion from raw channel values to process values; later release than the unspecified source configuration: https://support.industry.siemens.com/cs/attachments/109746485/109746485_PCS7_V100_SIMIT_V112_GS_DOC_V3_1_en.pdf
  • Siemens, Safety Matrix Programming and Operating Manual, 01/2019, simulation with SIM_ON and SIM_V: https://support.industry.siemens.com/cs/attachments/109766685/S7FSMUGB_en-US.pdf