Converting BCD Timestamp Formats to S7 DATE_AND_TIME in S7-410H and PCS 7 V9.0

Converting BCD Timestamp Formats to S7 DATE_AND_TIME in S7-410H and PCS 7 V9.0

To convert individual Binary Coded Decimal (BCD) timestamp bytes into a standard S7 DATE_AND_TIME (DT) structure in SIMATIC PCS 7 V9.0, no mathematical BCD-to-integer decoding is necessary because the S7 DATE_AND_TIME data type is natively stored in BCD format. An S7 DATE_AND_TIME variable consists of exactly 8 consecutive bytes: Byte 0 (Year 00-99), Byte 1 (Month 01-12), Byte 2 (Day 01-31), Byte 3 (Hour 00-23), Byte 4 (Minute 00-59), Byte 5 (Second 00-59), Byte 6 (Milliseconds MSB), and Byte 7 (Milliseconds LSB + Day of Week). To combine discrete BCD bytes into a unified DT variable, map the incoming bytes directly into an 8-byte global DB or SCL structure using byte MOVE operations or an SCL AT-overlay construct.

Table of Contents

Executive Summary

In high-accuracy Sequence of Events (SOE) applications with ET 200SP HA time-stamped digital inputs or third-party serial power meters, field hardware frequently delivers event timestamps as individual BCD-encoded byte streams. Automation engineers implementing custom timestamp logging in PCS 7 V9.0 often attempt complex mathematical conversions (multiplying tens by 10 and adding units) to assemble S7 timestamps. However, the S7-400 / CPU 410-5H operating system fundamentally defines the DATE_AND_TIME primitive as an 8-byte packed BCD structure. This guide explains the exact internal bit layout of DATE_AND_TIME, demonstrates the most efficient SCL assembly pattern, and outlines best practices for routing timestamps to WinCC Alarm Logging.

Architecture and Fundamental Mechanics

Internal Structure of S7 DATE_AND_TIME (DT)

In SIMATIC S7-400 and CPU 410-5H architectures, the DATE_AND_TIME data type occupies 8 consecutive bytes in memory, formatted as follows:

+-------------------------------------------------------------------------+
|                   S7 DATE_AND_TIME (8 Bytes / 64 Bits)                  |
+-------------------------------------------------------------------------+
| Byte | Field        | Format | Valid Range | Example (2026-10-14 23:00) |
|------|--------------|--------|-------------|----------------------------|
| 0    | Year         | BCD    | 00 - 99     | B#16#26 (Year 2026)        |
| 1    | Month        | BCD    | 01 - 12     | B#16#10 (October)          |
| 2    | Day          | BCD    | 01 - 31     | B#16#14 (14th)             |
| 3    | Hour         | BCD    | 00 - 23     | B#16#23 (11 PM)            |
| 4    | Minute       | BCD    | 00 - 59     | B#16#00 (00 minutes)       |
| 5    | Second       | BCD    | 00 - 59     | B#16#15 (15 seconds)       |
| 6    | Millisec MSB | BCD    | 00 - 99     | B#16#02 (200 ms)           |
| 7    | Millisec LSB | BCD    | Bit 4-7: BCD| B#16#51 (50 ms + Sun=1)    |
|      | Day of Week  | BIN    | Bit 0-3: 1-7| (1=Sun, 2=Mon... 7=Sat)    |
+-------------------------------------------------------------------------+

Direct Byte Mapping Mechanics

Because the incoming field data is already in BCD format, performing an arithmetic conversion to integer and then calling Step 7 conversion functions (such as FC3 D_TOD_DT) is computationally wasteful and introduces conversion overhead. Instead, by writing the raw BCD bytes directly into the 8 memory addresses allocated to a DATE_AND_TIME variable, the S7 CPU instantly interprets the bytes as a valid timestamp.

Step-by-Step Implementation Procedure

Step 1: Create a Shared Data Block for Timestamp Construction

  1. In SIMATIC Manager, open the S7 Program block container.
  2. Create a new Data Block: DB150.
  3. Open DB150 in the DB Editor and declare the variables:
    - Raw_Bytes: Array [0..7] of BYTE
    - Event_DT: DATE_AND_TIME
  4. Alternatively, declare a user-defined type (UDT) matching the 8-byte structure.

Step 2: Implement Direct SCL Conversion Logic

  1. In the S7 SCL editor, create a dedicated function block: FB1150 (BCD_To_DT_Converter).
  2. Declare input parameters for each BCD byte: In_Year, In_Month, In_Day, In_Hour, In_Min, In_Sec, In_MS_High, In_MS_Low.
  3. Use an SCL AT overlay to construct the DATE_AND_TIME variable without arithmetic conversion:
    ```scl
    FUNCTION_BLOCK FB1150
    VAR_INPUT
    In_Year : BYTE; // BCD format e.g. 16#26
    In_Month : BYTE; // BCD format e.g. 16#10
    In_Day : BYTE; // BCD format e.g. 16#14
    In_Hour : BYTE; // BCD format e.g. 16#23
    In_Min : BYTE; // BCD format e.g. 16#00
    In_Sec : BYTE; // BCD format e.g. 16#15
    END_VAR
    VAR_OUTPUT
    Out_DT : DATE_AND_TIME;
    END_VAR
    VAR
    DT_Structure : ARRAY[0..7] OF BYTE;
    DT_Overlay AT DT_Structure : DATE_AND_TIME;
    END_VAR

BEGIN
DT_Structure[0] := In_Year;
DT_Structure[1] := In_Month;
DT_Structure[2] := In_Day;
DT_Structure[3] := In_Hour;
DT_Structure[4] := In_Min;
DT_Structure[5] := In_Sec;
DT_Structure[6] := 16#00; // Milliseconds high
DT_Structure[7] := 16#01; // Milliseconds low + Sunday

   Out_DT := DT_Overlay;

END_FUNCTION_BLOCK
```

Step 3: Integrate and Connect in CFC

  1. Compile the SCL block into the S7 Program.
  2. In CFC, drag FB1150 into the processing chart.
  3. Connect the BCD byte outputs from your communication or channel driver blocks into the corresponding inputs of FB1150.
  4. Route Out_DT to downstream recording blocks, sequence totalizers, or Alarm_8P associated values.
  5. Compile CFC via Changes Only and download to the AS.

Verification

  1. Variable Table (VAT) Monitor: Create a VAT in SIMATIC Manager. Add the output address of Out_DT and select display format DATE_AND_TIME. Confirm that the timestamp displays human-readable date and time (e.g., DT#2026-10-14-23:00:15.000).
  2. Plausibility Check: Test edge cases such as month transitions (e.g., month = 16#12 to 16#01) and leap years to confirm the CPU evaluates the reconstructed DT cleanly without generating area-length or data-type faults in the diagnostic buffer.
  3. WinCC Alarm Verification: Route the DT value to an alarm message block and verify that WinCC Alarm Logging displays the correct historical timestamp in the message list.

Limitations and Operational Precautions

  1. Century Representation: S7 DATE_AND_TIME stores years 90–99 as 1990–1999, and years 00–89 as 2000–2089. Verify that field devices follow this standard two-digit convention.
  2. Invalid BCD Trapping: If field hardware transmits an invalid BCD byte (such as 16#0A or 16#FF), standard S7 blocks handling DATE_AND_TIME will trigger an operating system error. Always filter incoming bytes with a nibble mask (Byte AND 16#0F <= 9) to ensure BCD plausibility.

Engineer FAQ

Why does DATE_AND_TIME not require BCD-to-integer conversion?

Because S7 DATE_AND_TIME is internally stored in packed BCD format; discrete BCD bytes match the memory representation directly.

How many bytes does DATE_AND_TIME occupy?

Exactly 8 bytes (64 bits) in S7-300, S7-400, and CPU 410-5H memory.

What does Byte 7 of DATE_AND_TIME contain?

The upper 4 bits contain the least significant digit of milliseconds; the lower 4 bits contain the day of the week (1 = Sunday, 7 = Saturday).

Can I move BCD bytes into a DB using standard ladder (LAD)?

Yes, you can use 8 consecutive MOVE instructions transferring each byte to the respective byte address of the DT variable.

How do I unpack a DATE_AND_TIME into BCD bytes?

Use the reverse process: read the 8 individual byte offsets of the DATE_AND_TIME variable in SCL or STL.

What happens if an invalid BCD digit (e.g. 16#1F) is loaded?

Standard Step 7 time functions will fail or report an invalid date, and WinCC may display a default 1970 timestamp.

Does ET 200SP HA time stamping require manual BCD conversion?

No. Standard PCS 7 time-stamping driver blocks (Pcs7DiIT) handle ET 200SP HA 1 ms SOE timestamps automatically without user conversion.

Can S7 DATE_AND_TIME represent microseconds?

Standard S7 DT has a resolution of 1 millisecond. Microsecond time stamping uses specialized 10-byte time structures in ET 200SP HA.

What SCL instruction overlays different data types?

The AT keyword allows declaring a variable view over an existing memory area with a different data type.

Is SFC1 (READ_CLK) output formatted in BCD?

Yes, the system function SFC1 READ_CLK outputs system time directly in standard S7 DATE_AND_TIME BCD format.

Technical References

Related Articles

Related Tags

  • DATE_AND_TIME
  • BCD Conversion
  • S7-410H
  • SCL
  • Time Stamping
  • ET 200SP HA
  • CFC Programming