Creating and Assigning Custom APL Block Icon Variants in SIMATIC PCS 7
In SIMATIC PCS 7, creating and assigning custom APL block icon variants for technological objects (such as motors, valves, or analog indicators) requires defining unique icon variants within project typical files and linking them via the CFC block instance properties. In the template file (@PCS7Typicals_Project.pdl), the Customized Object property 'type' is formatted as @/ (for example, @MotL/2 or @MotL/custom1). In Continuous Function Chart (CFC), the engineer specifies this variant number in the block properties under 'Create block icon'. When the OS compilation wizard 'Create/Update Block Icons' is executed, WinCC scans the CFC chart, locates the matching variant in the typical template, instantiates the graphic, and automatically maps the instance tag prefix.
Table of Contents
- APL Block Icon Variant Architecture in SIMATIC PCS 7
- Template Configuration: System Typicals vs. Project Typicals
- Block Icon Type Definition and Property Mapping Matrix
- Step-by-Step Procedure to Create and Assign Custom Icon Variants
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
APL Block Icon Variant Architecture in SIMATIC PCS 7
The SIMATIC PCS 7 Advanced Process Library (APL) provides multiple visual representations (variants) for standard technological blocks. For instance, the standard motor block MotL includes variants such as @MotL/1 (standard horizontal orientation with status symbols), @MotL/2 (vertical orientation), @MotL/3 (compact square icon for dense mimic displays), and @MotL/4 (high-performance HMI style).
Each variant is implemented as a WinCC Customized Object (Anwenderobjekt) residing within a typical picture file. The core mechanism linking a controller block in CFC to a specific graphic representation is the Type String defined on the Customized Object: @<BlockType>/<VariantNumber>.
When an engineer designs a plant schematic in Graphics Designer, they do not manually copy and interconnect individual block icons. Instead, they assign a variant index to the block instance in CFC, assign the process picture to the Plant Hierarchy folder, and allow the Create/Update Block Icons wizard to generate and position the icons deterministically.
Template Configuration: System Typicals vs. Project Typicals
To ensure that customized block icons survive software updates and migrations, engineers must adhere to Siemens template hierarchy rules:
-
System Typicals (
@PCS7TypicalsAPLV8.pdl/@PCS7TypicalsAPLV9.pdl): These files are installed and managed by Siemens. During PCS 7 updates, OS Project Editor executions, or service pack installations, these files are silently overwritten. Custom modifications made directly inside system typicals will be lost. -
Project Typicals (
@PCS7Typicals_Project.pdlor@PCS7Typicals<Name>.pdl): WinCC searches all files in the OS project'sGraCSdirectory whose names begin with@PCS7Typicals. If a block type variant exists in both a project typical file and a system typical file, the wizard prioritizes the project-specific file, allowing engineers to override standard Siemens graphics safely. -
Customized Object Interface Consistency: When altering shape dimensions, colors, or fonts, the internal attribute connections (
type,tag,servername,TagLowLimit,TagHighLimit) must remain intact to allow the OS wizard to inject instance tag paths.
Block Icon Type Definition and Property Mapping Matrix
The following table details the property requirements and CFC linkages across standard and custom APL icon variants:
@<BlockType>/<Variant> (e.g., @MotL/5)5) or texttag.)<Chart>/<Block> at compileGeneralPCS7 <BlockType> ControlLinks.Status1, .Status2, .Status3GraCS Directory@PCS7Typicals_Project.pdlStep-by-Step Procedure to Create and Assign Custom Icon Variants
To create a custom block icon variant and assign it to a CFC instance:
-
Create the Project Typical File:
- In WinCC Explorer on the Engineering Station, open Graphics Designer.
- Open@PCS7TypicalsAPLV8.pdl(or V9) from the projectGraCSfolder.
- Select File -> Save As, and save the file as@PCS7Typicals_Project.pdl. -
Create and Customize the New Icon Variant:
- Inside@PCS7Typicals_Project.pdl, locate the standard motor icon@MotL/1.
- Copy and paste the object to create a duplicate within the same picture.
- Right-click the duplicate object and select Configuration Dialog.
- Change the propertytypefrom@MotL/1to@MotL/5(or another unused variant number).
- If modifying graphics, right-click the object and select Customized Object -> Edit.
- Adjust rectangle sizes, fonts, or add static text indicators, then select all objects and choose Customized Object -> Finish Editing.
- Save and close@PCS7Typicals_Project.pdl. -
Assign the Variant Number in CFC:
- In SIMATIC Manager, open the CFC chart containing the motor block instance (MotL).
- Double-click theMotLblock header to open Block Properties.
- Ensure the checkbox Create block icon is checked.
- In the text box adjacent to the checkbox, enter the variant index:5.
- Click OK to close block properties. -
Generate Block Icons in WinCC:
- Ensure the CFC chart is placed inside a Plant Hierarchy folder assigned to a WinCC process graphic.
- In SIMATIC Manager, select the plant hierarchy folder, then select Options -> Plant Hierarchy -> Create/Update Block Icons.
- In the generation dialog, select your target OS and click OK.
- Open the destination process graphic in Graphics Designer; confirm that the custom@MotL/5icon is inserted with all tags connected.
Verification
Verify custom block icon functionality:
1. Open the process picture in Graphics Designer; select the generated block icon and verify that property tag is populated with the full instance tag path (e.g., Plant/Area/Line1_MotL).
2. Launch WinCC Runtime; verify that the custom icon displays active motor running states (green), stopped states (grey), and alarm frames.
3. Click the block icon in Runtime; confirm that the standard @PG_MotL.pdl faceplate opens cleanly.
4. Run a test OS Compile; confirm that compilation completes without block icon warnings and that custom graphics are preserved.
Limitations and Operational Precautions
- Never Overwrite Standard System Typicals: Do not modify
@PCS7TypicalsAPLV8.pdldirectly. All custom variants must reside in@PCS7Typicals_*.pdl. - Variant Number Collision: Ensure the variant number (e.g.,
/5) does not collide with existing Siemens variants (/1 through /4) to prevent unpredictable wizard instantiation. - Customized Object Integrity: Do not dissolve (ungroup) customized objects on process graphics, as ungrouping destroys the internal tag-binding interface and faceplate scripts.
Engineer FAQ
How does PCS 7 know which block icon variant to place on a picture?
The wizard matches the numeric index entered in the CFC block properties under 'Create block icon' with the suffix of the 'type' property (@/) in the typicals file.
Can I use alphanumeric variant names instead of numbers?
Yes. You can configure '@MotL/Small' in the typical file and enter 'Small' in the CFC block icon field.
Why did my custom block icon disappear after OS Compile?
If 'Create/Update Block Icons' was re-run without saving the icon in an '@PCS7Typicals_*.pdl' file, the wizard replaced the icon with a clean template from the system file.
Where should project-specific typical PDL files be saved?
Project typical files must be saved in the 'GraCS' directory of the master WinCC OS Server project on the Engineering Station.
Technical References
- SIMATIC PCS 7 APL Style Guide Engineering Manual (A5E03598762-01)
- SIMATIC HMI WinCC V7.4 Graphics Designer Manual (A5E37536408-AA)
- Siemens Industry Online Support: Customizing APL Block Icons and Typicals (Entry ID: 109780813)
Related Articles
- Developing Custom APL Block Icons and Faceplates Linked to SCL Function Blocks in PCS 7
- Preventing Value[X]BackColor Resets and Customizing APL Block Icon Colors in PCS 7
- Customizing APL Block Icons Without Breaking Automatic Wizard Interconnections in PCS 7
Related Tags
- Block Icons
- APL
- Customized Objects
- Typicals
- WinCC Graphics
- Plant Hierarchy