Creating Custom APL-Style Faceplate Popups and Block Icons in SIMATIC PCS 7 WinCC

Creating Custom APL-Style Faceplate Popups and Block Icons in SIMATIC PCS 7 WinCC

Developing custom APL-style faceplate popups and block icons in SIMATIC PCS 7 WinCC requires synchronizing controller SCL function blocks with the WinCC Faceplate Designer and template graphic libraries. Engineers must structure block interfaces with system attributes (such as S7_m_c for OS communication), define matching structured tag types in WinCC Tag Management, design custom block icons in @PCS7Typicals.pdl, and create modular faceplate views (@PG_.pdl). When an operator clicks the block icon, standard APL C-scripts parse the technological tag prefix and dynamically launch the popup window.

Table of Contents

Architecture of APL Faceplates and Technological Popups

In SIMATIC PCS 7, operator interaction conforms to the Advanced Process Library (APL) window management architecture:

  • Block Icon (@PCS7Typicals.pdl / @Template.pdl): A compact graphic object placed on process screens showing equipment status, alarms, and operating modes.
  • Faceplate Top Container (@PG_<Type>.pdl): The master window frame containing the title bar, view selection buttons (Standard, Alarm, Trend, Parameter, Memo), and authorization icons.
  • Standard View (@PG_<Type>_Standard.pdl): The primary interactive popup showing live telemetry (e.g., three timestamps and three analog values) and command buttons.
  • Dynamic Tag Binding via Tag Prefix: APL faceplates do not contain hardcoded tag names. When an operator clicks a block icon, the internal C-script APL_OpenFaceplate() retrieves the technological tag name (e.g., Unit1/Motor01) and assigns it as the Tag Prefix of the popup window, dynamically binding all controls to the target block instance.

STEP 7 Block Interface Design and S7_m_c Attributes

To enable automatic WinCC tag generation and faceplate connectivity, create the custom SCL function block (FB) with proper system attributes:

FUNCTION_BLOCK FB2001
TITLE = 'CustomMultiValMon'
{ S7_m_c := 'true' }
AUTHOR : 'Eng'

VAR_INPUT
   Val1 { S7_m_c := 'true' } : REAL := 0.0;
   Val2 { S7_m_c := 'true' } : REAL := 0.0;
   Val3 { S7_m_c := 'true' } : REAL := 0.0;
   Time1 { S7_m_c := 'true' } : DATE_AND_TIME;
   Time2 { S7_m_c := 'true' } : DATE_AND_TIME;
   Time3 { S7_m_c := 'true' } : DATE_AND_TIME;
   Op_Level { S7_m_c := 'true' } : INT := 5;
END_VAR

VAR_OUTPUT
   QError { S7_m_c := 'true' } : BOOL := FALSE;
END_VAR

When the CFC chart is compiled and the OS is compiled, the compiler automatically creates a structured tag type named CustomMultiValMon in WinCC Tag Management.

Designing Custom Block Icons in @PCS7Typicals.pdl

To ensure the OS compiler automatically generates block icons during compilation:

  1. In WinCC Graphics Designer, open the master template picture @PCS7Typicals.pdl (or @PCS7Typicals_Custom.pdl).
  2. Copy an existing APL block icon (e.g., @MonAnL/1) to serve as the design foundation.
  3. Open Object Properties for the new customized object:
    * type: Set to @CustomMultiValMon/1. The string before the slash must match your SCL block name exactly.
    * servername: Set to PCS7 CustomMultiValMon Control.
    * tag: Connect to a sample tag or leave as template property.
  4. Add the click event: Under Event -> Mouse -> Mouse Click, verify that the APL standard C-script is called:
    c // APL Standard Icon Click Action #include "apdefap.h" void OnClick(char* lpszPictureName, char* lpszObjectName, char* lpszPropertyName) { PCS7_OpenInputBox(lpszPictureName, lpszObjectName); }
  5. Save @PCS7Typicals.pdl.

Building Faceplate Views in Graphics Designer (@PG_*.pdl)

Create the faceplate view screens according to APL naming conventions:

  1. Create the Master View (@PG_CustomMultiValMon.pdl):
    * Copy @PG_MonAnL.pdl and save as @PG_CustomMultiValMon.pdl.
    * Configure view buttons to load @PG_CustomMultiValMon_Standard.pdl.
  2. Create the Standard View (@PG_CustomMultiValMon_Standard.pdl):
    * Create an empty picture sized 400x300 pixels.
    * Insert Static Text labels: "Timestamp 1", "Value 1", etc.
    * Insert I/O Fields for analog values:
    • Set Data Format to Floating-Point.
    • Under Output Value -> Dynamic, assign tag .Val1 (notice the leading period: .Val1 binds to <TagPrefix>.Val1).
    • Insert I/O Fields for timestamps:
    • Set Data Format to Date/Time.
    • Dynamically link to .Time1.
  3. Save all .pdl files in the WinCC project GraCS directory.

Verification

Confirm custom faceplate instantiation and operation:

  1. OS Compilation:
    * Instantiate the custom SCL block in a CFC chart within the Plant Hierarchy.
    * Compile charts and run Compile OS (Scope: Changes only).
    * Confirm that the compiler generates the block icon on the process screen.
  2. Runtime Interaction Test:
    * Open the WinCC process graphic in runtime.
    * Verify that the block icon displays live values.
    * Click the block icon: confirm that @PG_CustomMultiValMon.pdl opens promptly.
    * Verify that all three dates and three analog values display matching PLC data dynamically.

Limitations and Operational Precautions

  • Template Protection: Never modify @PCS7Typicals.pdl without maintaining backup copies; creating a project-specific @PCS7Typicals_Project.pdl is recommended to prevent OS Project Editor updates from overwriting custom icons.
  • Strict Tag Prefix Syntax: All dynamic links inside @PG_*_Standard.pdl must begin with a period (.Val1, .Time1) to allow dynamic binding to the window Tag Prefix.
  • Process Object Consumption: Custom technological function blocks configured with S7_m_c := 'true' consume standard AS Process Object (PO) licenses upon compilation.

Engineer FAQ

  • What system attribute in SCL exposes block parameters to WinCC?
    The attribute { S7_m_c := 'true' } placed on the block header and individual variables.
  • What naming convention is required for custom APL faceplates?
    The master container must be named @PG_<BlockType>.pdl and the standard view @PG_<BlockType>_Standard.pdl.
  • How do APL faceplates link to specific equipment instances dynamically?
    The block icon passes the instance tag name to the faceplate window as a Tag Prefix; controls inside the faceplate reference tags using relative syntax (e.g., .Val1).
  • Where are custom block icons stored so the OS compiler can find them?
    In @PCS7Typicals.pdl or a custom typicals file (e.g., @PCS7Typicals_Custom.pdl) in the project GraCS folder.
  • What attribute in the block icon links it to the SCL block type?
    The type property in the block icon must be set to @<BlockName>/<Variant>, such as @CustomMultiValMon/1.
  • Can custom faceplates display DATE_AND_TIME variables?
    Yes, WinCC I/O fields can be formatted as Date/Time to render S7 DATE_AND_TIME data structures natively.
  • Which script opens an APL faceplate when an icon is clicked?
    The standard APL script PCS7_OpenInputBox() or APL_OpenFaceplate() executed on the mouse click event.
  • Does creating a custom faceplate require C-scripting?
    Basic faceplates can be created using standard dynamic tag linking and WinCC Faceplate Designer without writing complex custom C-scripts.
  • How do I prevent my custom block icons from being overwritten during upgrades?
    Create a custom typicals file (e.g., @PCS7Typicals_MyPlant.pdl) and register it in the OS Project Editor.
  • What user authorization level is required to modify values on custom faceplates?
    Configuring the Op_Level parameter on the block allows mapping operations to WinCC authorization levels (1 to 16).

Technical References

  • Siemens Industry Online Support (SIOS) Portal: How do you create custom block icons and faceplates for SIMATIC PCS 7? (Entry ID: 68679830).
  • SIMATIC PCS 7 Faceplate Designer Manual, Siemens AG.
  • SIMATIC WinCC V7.5 Information System - Working with Process Pictures and ActiveX.

Related Articles

Related Tags

PCS 7, WinCC, APL, Faceplates, Block Icons, SCL, Graphics Designer, Custom Blocks