Decoding Error Output QGR_ERR on Legacy Siemens Motor Block FB66 (MOTOR_LS)

Decoding Error Output QGR_ERR on Legacy Siemens Motor Block FB66 (MOTOR_LS)

On the legacy SIMATIC PCS 7 Standard Library motor block FB66 (MOTOR_LS / MOTOR 'Motor with control signals'), output QGR_ERR represents a latched Group Error (Gruppenfehler). It activates (QGR_ERR = 1) whenever any monitoring or operational fault occurs, including runtime monitoring timeout (QMON_ERR), motor protection switch trip (MSS = 0), interlock trip (L_STOP = 0), or external error (EXT_ERR = 1). To clear QGR_ERR, verify that field feedback (ERM_ON), motor protection (MSS), and interlock signals are healthy, and apply a rising-edge pulse to the RESET input (RESET = 1) to clear the internal fault flip-flop.

Table of Contents

Functional Overview of Legacy Standard Library Motor Block FB66

In legacy SIMATIC PCS 7 installations (PCS 7 V6.x, V7.x, and legacy migrations in V8.x/V9.x), FB 66 represents the technological function block MOTOR_LS (Motor with control signals / Motor mit Steuersignal), derived from the classic PCS 7 Standard Library.

FB 66 coordinates unidirectional motor actuation, processing manual/automatic commands, feedback monitoring, interlocks, and alarm generation via Alarm_8P. The output pin QGR_ERR serves as the primary summary fault flag for plant interlocks and HMI group displays.

Root Causes Triggering Group Error Output QGR_ERR

The group error output QGR_ERR is the internal logical OR combination of four distinct operational faults:

$$\text{QGR_ERR} = \text{QMON_ERR} \lor \lnot \text{MSS} \lor \lnot \text{L_STOP} \lor \text{EXT_ERR}$$

  1. Runtime Monitoring Fault (QMON_ERR = 1): When a start command (QSTART) is issued, the feedback signal (ERM_ON) must arrive within the monitoring time parameter (TIME_MON, e.g. 5.0 s). If feedback fails or drops while running, QMON_ERR trips and latches.
  2. Motor Protection Switch Trip (MSS = 0): The motor circuit breaker or thermal overload contact is wired to MSS. Because MSS is active-high for healthy operation, an open contact (MSS = 0) triggers an immediate trip.
  3. Interlock Trip (L_STOP = 0): Interlock input for process stops. An active-low state (0) stops the motor and asserts QGR_ERR.
  4. External Fault (EXT_ERR = 1): A generic error input for third-party alarms or drive ready faults.

Detailed Analysis of Input Parameters Affecting QGR_ERR

To diagnose which input is tripping FB 66, monitor the block online in CFC and inspect these pins:

  • MSS (Motor Protection Switch): Must be 1 (healthy). If 0, check the field thermal overload relay.
  • ERM_ON (Feedback Run): Must transition to 1 following QSTART = 1. If ERM_ON is delayed past TIME_MON, increase TIME_MON.
  • L_STOP / L_OFF (Interlock Stop): Must be 1. If 0, trace upstream interlocking logic in the CFC chart.
  • EXT_ERR (External Error): Must be 0. If 1, check external trip signals connected to this terminal.
  • RESET (Reset Fault): Input used to unlatch the error flip-flop after healthy conditions are restored.

Reset and Fault Clearance Procedure in CFC and Faceplates

Because FB 66 contains an internal latched SR flip-flop, simply restoring healthy field inputs will NOT clear QGR_ERR:

  1. Verify that MSS = 1, L_STOP = 1, and EXT_ERR = 0 online in CFC.
  2. In WinCC OS Runtime, open the motor faceplate and click the Reset button.
  3. If operating without an OS faceplate (e.g. testing in CFC), right-click the RESET input in CFC, toggle value to 1, execute a CPU cycle, and toggle back to 0.
  4. Confirm that QGR_ERR transitions to 0 and QMON_ERR transitions to 0.

Comparison: Classic FB66 MOTOR_LS vs Modern APL MotL

The table below contrasts the legacy FB66 block with the modern APL equivalent:

| Block Parameter | Classic FB66 (MOTOR_LS) | Modern APL MotL (FB 1850) |
|---|---|---|---|
| Group Error Output | QGR_ERR (Boolean) | GrErr (Structure: Value + Status) |
| Feedback Input | ERM_ON (Single bit) | FbkRun (Structure: Value + Status) |
| Motor Protection | MSS (Active-high bit) | Trip (Active-low bit) |
| Monitoring Time | TIME_MON (Seconds) | MonTiDynamic (Seconds) |
| Fault Reset | RESET (Pulse input) | RstOp (Faceplate) / RstLi (Logic) |
| Faceplate Template | @PG_MOTOR.pdl | @PG_MotL.pdl |

Verification

Verify fault clearance and motor operation in CFC:

  1. Open the CFC chart online with FB 66 in test mode (Test > Watch).
  2. Confirm that MSS = 1, L_STOP = 1, and EXT_ERR = 0.
  3. Apply a pulse to RESET = 1 then 0.
  4. Verify that QGR_ERR changes from 1 to 0.
  5. Issue a start command (AUT_ON = 1 or manual start); confirm QSTART = 1 and ensure ERM_ON = 1 arrives within TIME_MON without re-triggering QGR_ERR.

Limitations and Operational Precautions

Review the following legacy library precautions:

  • Migration Planning: The PCS 7 Standard Library (FB 66) is legacy software. For new projects or plant expansions, Siemens strongly recommends migrating to the PCS 7 Advanced Process Library (MotL FB 1850).
  • Inverted Logic Checks: Pay close attention to active-low pins (MSS, L_STOP); a disconnected or uninitialized pin evaluates as 0, immediately tripping the block.
  • Monitoring Time Margin: Ensure TIME_MON accounts for physical contactor pull-in times and auxiliary contact bounce (typically 2 to 5 seconds).

Engineer FAQ

What does QGR_ERR stand for on FB 66?

QGR_ERR stands for 'Quittierbarer Gruppenfehler' (Acknowledgeable Group Error). It indicates a latched summary fault on the motor block.

Why doesn't QGR_ERR clear when the motor protection switch (MSS) is closed?

Because FB 66 latches fault states into an internal flip-flop. Even after MSS returns to 1, an explicit rising edge on the RESET input is required to clear the error.

Which monitoring timer controls the feedback check on FB 66?

The parameter TIME_MON (in seconds) defines the maximum allowable time between issuing QSTART and receiving the ERM_ON feedback contact.

Technical References

Related Articles

Related Tags

  • FB 66
  • MOTOR_LS
  • QGR_ERR
  • Standard Library
  • Feedback Monitoring
  • CFC Diagnostics