Designing Redundant Terminal Bus in SIMATIC PCS 7 - Intel NIC Teaming vs SOFTNET-IE RNA (PRP) and SCALANCE X-204RNA
To establish a redundant terminal bus between SIMATIC PCS 7 OS Servers and Clients, two primary architectures are supported: Intel NIC Teaming (using certified Intel multi-port server adapters and Intel ANS drivers) or Parallel Redundancy Protocol (PRP according to IEC 62439-3) using SIMATIC NET SOFTNET-IE RNA software. Standard commercial adapters (such as Realtek RTL8139) cannot utilize Intel Teaming drivers; they require SOFTNET-IE RNA for NDIS-level PRP bonding or connection through hardware redundancy boxes such as SCALANCE X-204RNA.
Table of Contents
- Architecture of the PCS 7 Redundant Terminal Bus
- Intel NIC Teaming vs SOFTNET-IE RNA (PRP IEC 62439-3)
- Comparison Table: Intel Teaming vs SOFTNET-IE RNA vs SCALANCE X-204RNA
- Single Attached Nodes (SAN) and Dual Attached Nodes (DAN) Topologies
- Step-by-Step Procedure to Implement SOFTNET-IE RNA on OS Stations
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Architecture of the PCS 7 Redundant Terminal Bus
The terminal bus in SIMATIC PCS 7 interconnects Engineering Stations (ES), redundant OS Server pairs, OS Clients, BATCH Servers, Route Control, and Process Historian:
* The Redundancy Objective:
A single network cable disconnect, switch failure, or adapter defect must not sever communication between the operating consoles and the plant automation servers.
* Separation of Terminal Bus and Plant Bus:
The Plant Bus connects OS Servers and Engineering Stations to controllers (S7-400 / CPU 410-5H) using CP 1623 / CP 1628 or standard network cards with Industrial Ethernet. The Terminal Bus operates as a separate logical and physical network to handle high-bandwidth operator graphics, trend streaming, and SQL database synchronization without impacting real-time controller polling.
Intel NIC Teaming vs SOFTNET-IE RNA (PRP IEC 62439-3)
Two distinct technological methods exist for establishing terminal bus adapter redundancy:
1. Intel NIC Teaming (Adapter Fault Tolerance - AFT / Switch Fault Tolerance - SFT):
* Mechanism: Operates via proprietary Intel ANS (Advanced Network Services) drivers. Two physical ports form a single logical adapter with a shared IP and MAC address. One link remains active while the standby link monitors connectivity via test beacons.
* Hardware Restriction: Supported only on certified Intel server-grade network chipsets (e.g., Intel I210, I350, PRO/1000). Commercial chipsets such as Realtek, Broadcom, or Marvell cannot use Intel ANS teaming.
2. Parallel Redundancy Protocol (PRP according to IEC 62439-3):
* Mechanism: Operates using SIMATIC NET SOFTNET-IE RNA (6GK1780-0AA00 / 6GK1780-0AA08-0AA0). SOFTNET-IE RNA creates a virtual network adapter above two independent standard NDIS physical Ethernet adapters.
* Operation: Transmits every Ethernet packet simultaneously across two independent physical LAN rings/switches (LAN A and LAN B). The receiving station accepts the first arriving frame and discards the duplicate. Switchover time is literally zero milliseconds (bumpless).
* Adapter Independence: Works with standard NDIS-compliant network cards, including non-Intel adapters, making it versatile across diverse PC station hardware.
Comparison Table: Intel Teaming vs SOFTNET-IE RNA vs SCALANCE X-204RNA
The table below outlines technical and commercial differences between terminal bus redundancy solutions:
6GK1780-0AA08-0AA0)6GK5204-0BA00-2KB2)Single Attached Nodes (SAN) and Dual Attached Nodes (DAN) Topologies
When implementing a redundant terminal bus across an entire facility:
* Dual Attached Nodes (DAN P):
Stations equipped with two physical network cards running SOFTNET-IE RNA or Intel Teaming. Both OS Servers and primary OS Clients connect directly to both LAN A and LAN B switches.
* Single Attached Nodes (SAN):
Devices with only one network port (e.g., office printers, panel PCs, legacy engineering laptops). A SAN cannot connect to both LANs directly:
* If plugged into LAN A only, communication is lost if LAN A switches fail.
* Solution: Connect the SAN device through a SCALANCE X-204RNA (6GK5204-0BA00-2KB2) Redundancy Box (RedBox). The RedBox connects to LAN A and LAN B, duplicating outgoing frames and eliminating duplicate incoming frames transparently for the single-port node.
Step-by-Step Procedure to Implement SOFTNET-IE RNA on OS Stations
- Install Physical Network Adapters:
Install two independent PCIe Ethernet adapters (or dual-port card) in the OS Server and OS Client stations. - Install SIMATIC NET SOFTNET-IE RNA:
Install the SOFTNET-IE RNA software package and transfer the license via Automation License Manager (6GK1780-0AA08-0AA0). - Configure the RNA Virtual Adapter:
* Open the RNA configuration utility in Windows Control Panel / SIMATIC NET.
* Bind Adapter 1 toRNA Network Aand Adapter 2 toRNA Network B.
* Create the virtual adapterRNA0. - Assign IP Parameters:
Assign the plant static IP address, subnet mask, and default gateway to the virtualRNA0adapter in Windows Network Connections. The physical adapters (Adapter 1 and Adapter 2) must have IP protocols disabled or set to unmanaged bindings. - Configure Network Switches:
Connect Adapter 1 ports to SCALANCE X switch infrastructure for LAN A. Connect Adapter 2 ports to independent SCALANCE X infrastructure for LAN B. Ensure no cross-links exist between LAN A and LAN B. - Set Simatic Shell Adapter:
Open Simatic Shell in Windows Explorer. Right-click and select Settings. Set the network adapter binding to the virtualRNA0adapter. Restart the station.
Verification
To verify redundant terminal bus operation:
1. Open Simatic Shell on an OS Client. Confirm that the redundant OS Server pair is visible and accessible.
2. Start WinCC OS Runtime and open process graphic screens.
3. Initiate a continuous ping from the client to the server virtual RNA IP address: ping -t <Server_RNA_IP>.
4. Disconnect the physical network cable from Adapter 1 (LAN A).
5. Verify that zero ping packets are dropped, process graphic values continue updating without interruption, and no disconnection alarms appear in WinCC.
6. Reconnect Adapter 1 and disconnect Adapter 2 (LAN B). Confirm bumpless continuity.
Limitations and Operational Precautions
- Commercial NIC Limitations: Consumer-grade NICs (such as Realtek RTL8139) lack industrial galvanic isolation and high-precision interrupt moderation, which can result in frame drops during high-volume SQL replication between WinCC servers. Use Siemens-approved industrial adapters.
- No Inter-Switch Links: Under PRP / SOFTNET-IE RNA, LAN A and LAN B must remain completely isolated from each other. Never bridge LAN A and LAN B switches with a trunk cable, as this causes catastrophic broadcast storms.
- Licensing Disclaimer: Final license quantities and MLFBs for SIMATIC NET SOFTNET-IE RNA (
6GK1780-0AA08-0AA0) must be validated against the applicable Siemens catalog and authorized distributor quotation.
Engineer FAQ
Technical References
- SIMATIC Net Fault-Tolerant Communication with SOFTNET-IE RNA Manual (A5E02697841-07)
- SIMATIC PCS 7 Fault-Tolerant Process Control Systems Manual (A5E35802288-AB)
- Industrial Ethernet SCALANCE X-200RNA Operating Instructions (C79000-G8976-C278-05)
Related Articles
- Configuring Fault-Tolerant S7 Connections on Virtualized WinCC OS Servers (VMware vSphere)
- Diagnosing WinCC Redundancy Alarms - Loss of Connection Between Redundant OS Servers
- Time Synchronization in SIMATIC PCS 7 - Configuring Controllers as Time Masters vs External GPS Masters