Differentiating SIMATIC PDM Integration in STEP 7-PCS 7 vs SIMATIC PDM PCS 7 Software
The key difference between 'SIMATIC PDM Integration in STEP 7/PCS 7' (6ES7658-3BX58-2YB5) and 'SIMATIC PDM Software PCS 7' (6ES7658-3LD58-0YA5) is that PDM Software PCS 7 is a complete, standalone engineering base package, whereas PDM Integration is merely an add-on option. PDM Software PCS 7 contains the full application suite: PDM Basic, PDM Extended, Integration in STEP 7/PCS 7, S7 Routing, Communication Foundation, and a 100-TAG runtime license. Conversely, PDM Integration is an add-on package intended only for users who already possess standalone PDM Basic and wish to embed it into SIMATIC Manager.
Table of Contents
- Functional Overview of SIMATIC PDM (Process Device Manager)
- Detailed Analysis: SIMATIC PDM Software PCS 7 (Base Package)
- Detailed Analysis: SIMATIC PDM Integration in STEP 7/PCS 7 (Add-On)
- Tag Counting Rules and Device Sizing Structure
- Procurement Comparison Matrix: PDM Packages and Options
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Functional Overview of SIMATIC PDM (Process Device Manager)
SIMATIC PDM (Process Device Manager) is a universal, manufacturer-neutral tool for configuring, parameterizing, commissioning, and diagnosing intelligent field instruments (transmitters, actuators, analyzers) communicating over HART, PROFIBUS DP, PROFIBUS PA, and Foundation Fieldbus (FF).
In SIMATIC PCS 7, PDM can be executed as a standalone application on service laptops or fully integrated into the central Engineering Station (ES) to enable plant-wide parameterization directly through S7-400 controller routing.
Detailed Analysis: SIMATIC PDM Software PCS 7 (Base Package)
The product SIMATIC PDM, SOFTWARE PCS 7 (e.g. V9.0 6ES7658-3LD58-0YA5 or V8.1 6ES7658-3LD18-0YA5) is the complete, all-in-one software license engineered for PCS 7 Engineering Stations. It bundles:
- SIMATIC PDM Basic: Core parameterization and Electronic Device Description (EDD) interpretation engine.
- SIMATIC PDM Extended: Advanced reporting, calibration logs, and project export utilities.
- SIMATIC PDM Integration in STEP 7 / PCS 7: Embeds PDM directly inside SIMATIC Manager, HW Config, and Plant View.
- SIMATIC PDM Routing: Enables communication from the ES across Industrial Ethernet, through S7-400 CPUs, DP/PA links, down to field instruments.
- 100 TAG License: Includes base authorization for up to 100 intelligent field devices.
Detailed Analysis: SIMATIC PDM Integration in STEP 7/PCS 7 (Add-On)
The product SIMATIC PDM, SOFTWARE INTEGRATION IN STEP 7/PCS 7 (e.g. 6ES7658-3BX58-2YB5) is strictly an optional functional expansion:
- It is designed for engineers who already own a standalone license (e.g.,
SIMATIC PDM BasicorSIMATIC PDM Service) and wish to upgrade their standalone software to embed within the SIMATIC Manager project tree. - Ordering only
6ES7658-3BX58-2YB5on a new Engineering Station without a base PDM license will result in licensing errors, because the core PDM engine, device libraries, and routing drivers are completely missing.
Tag Counting Rules and Device Sizing Structure
In SIMATIC PDM, every physical field instrument configured with an Electronic Device Description (EDD) consumes 1 PDM TAG:
- 1 HART temperature transmitter = 1 PDM TAG.
- 1 PROFIBUS PA control valve positioner = 1 PDM TAG.
- When plant instrument count exceeds the initial 100 TAG allocation included in
6ES7658-3LDxx-0YA5, engineers must order SIMATIC PDM TAG Expansion Packs (e.g., 100 TAGs6ES7658-3XC00-2YB5, 1,000 TAGs6ES7658-3XD00-2YB5).
Procurement Comparison Matrix: PDM Packages and Options
The table below details component scope and order numbers for SIMATIC PDM:
Verification
Verify PDM license validity in Automation License Manager (ALM):
- Open ALM on the Engineering Station; verify keys for
SIMATIC PDM PCS 7,Integration in STEP 7/PCS 7, andPDM Routingshow statusValid. - Open SIMATIC Manager, select
View > Process Device Plant View. - In HW Config, double-click a HART or PROFIBUS PA field instrument.
- Verify that SIMATIC PDM launches seamlessly within the STEP 7 shell, opening the instrument parameter view.
- Execute a diagnostic read (
Device > Read from Device); confirm live parameters upload from the field device.
Limitations and Operational Precautions
Observe the following commercial and operational safeguards:
- Commercial Procurement Guardrail: Sizing PDM requires exact manufacturer documentation. Never order
6ES7658-3BXxx-2YB5for a new ES station; always specify the complete package6ES7658-3LDxx-0YA5and verify against the Siemens Industry Mall. - TAG Exceeded Warnings: If the number of field devices in the project exceeds the licensed TAG count, PDM operates in demo mode, restricting online write and calibration capabilities.
- EDD Device Library Updates: Always install the official Siemens PDM Device Library (Device Catalog) DVD to ensure device description profiles match installed field sensor revisions.
Engineer FAQ
Can I buy only 'SIMATIC PDM Integration' (6ES7658-3BX58-2YB5) for my new PCS 7 Engineering Station?
No. 6ES7658-3BX58-2YB5 is an option package that requires an existing PDM Basic license. For a new Engineering Station, you must order the complete base package 'SIMATIC PDM Software PCS 7' (6ES7658-3LD58-0YA5).
What constitutes 1 TAG in SIMATIC PDM licensing?
Every physical field device (e.g. pressure transmitter, temperature sensor, positioner, radar level gauge) configured in the PDM project tree consumes exactly 1 PDM TAG.
Does SIMATIC PDM Software PCS 7 include S7 routing to field instruments?
Yes. The base package 6ES7658-3LD58-0YA5 includes the 'PDM Routing' option, allowing the ES to route across Industrial Ethernet through S7-400 CPUs to PROFIBUS and HART devices.
Technical References
- SIMATIC PDM Delivery Release and Ordering Overview: SIOS Entry ID 109748101
- SIMATIC PDM The Process Device Manager Manual: https://support.industry.siemens.com/cs/ww/en/view/109780813
- SIMATIC PCS 7 Ordering and Catalog Guide: https://support.industry.siemens.com/cs/ww/en/view/109748473
Related Articles
- Configuring DP-PA Link and Field Instruments in SIMATIC PDM via S7-400 Routing
- Integrating Endress+Hauser Waterpilot FMX167 Level Transmitters into SIMATIC PDM
- Sizing and Licensing Rules for Redundant OS Servers and Fault-Tolerant AS in PCS 7 V8.1