Displaying Motor Restart Lockout Countdown Timers on WinCC Faceplates for CEMAT C_DRV_1D
To display a motor restart lockout countdown timer on a WinCC V7.4 faceplate for CEMAT block C_DRV_1D, you cannot use standard APL UserAna1/UserAna2 pins because CEMAT utilizes an independent block architecture. Instead, implement one of two supported engineering methods: (1) In CFC, interconnect the elapsed or remaining time output of the start-interlock timer (e.g., TimerP or C_TIM_P) into a companion CEMAT analog measurement block (C_MEASUR) and link it as an associated value to the drive; or (2) In WinCC Graphics Designer, customize the C_DRV_1D standard faceplate (@PG_C_DRV_1D.pdl) by inserting an I/O Field dynamically bound to the timer's remaining time tag, formatted as an integer seconds or mm:ss countdown display.
Table of Contents
- Executive Summary
- Architecture and Fundamental Mechanics
- Step-by-Step Implementation Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Executive Summary
In cement, mining, and heavy material handling plants operating under the SIMATIC PCS 7 CEMAT industry standard, large medium-voltage (MV) crusher and mill motors require thermal restart lockout protection. To prevent motor stator and rotor overheating caused by frequent starts, engineering logic incorporates a cooldown timer (typically 15 to 30 minutes) into the start interlock (EBM/ESB) of the single-direction drive block C_DRV_1D. While the interlocking timer operates reliably in the AS controller, operators are left blind if the WinCC faceplate merely indicates 'Start Interlock Active' without displaying the remaining countdown time. Because CEMAT blocks lack standard APL auxiliary display inputs (UserAna1), automation engineers must implement specialized CEMAT measurement links or customize the WinCC faceplate.
Architecture and Fundamental Mechanics
The display architecture of CEMAT faceplates differs fundamentally from standard APL blocks:
-
APL vs. CEMAT Faceplate Philosophy:
- In standard PCS 7 APL blocks (e.g.,MotL), Siemens provides auxiliary inputs (UserAna1,UserAna2). Any analog value wired to these pins automatically renders in the faceplate standard view with engineering units without touching WinCC graphics.
- In CEMAT (e.g.,C_DRV_1D), the block is designed around industry-specific mineral processing workflows. It does not provideUserAna1pins. Faceplate data exchange is governed by dedicated structure tags, status words, and associated measurement blocks. -
The CEMAT Associated Measurement Concept (
C_MEASUR):
- CEMAT coordinates multi-variable drive monitoring by associating specialized satellite blocks with the parent drive.
- AC_MEASURblock represents analog values (bearing temperatures, motor current, vibration, or countdown timers). In the CFC chart, theC_MEASURblock is linked toC_DRV_1Dvia technological hierarchy assignment or parameter linking.
- The standard CEMAT faceplate includes an 'Associated Values' button that opens the linked analog measurement faceplate, displaying the countdown timer with trend and limit monitoring. -
Direct WinCC Faceplate Customization (
@PG_C_DRV_1D.pdl):
- If plant operators require the countdown timer to appear directly on the main faceplate canvas, the faceplate graphic file (@PG_C_DRV_1D.pdlor its standard view@PG_C_DRV_1D_STANDARD.pdl) can be edited in WinCC Graphics Designer.
- By adding an I/O Field configured with a tag prefix link, the faceplate dynamically reads the remaining time tag directly from the timer's instance DB.
Step-by-Step Implementation Procedure
Implement the restart lockout countdown display using one of the following methods:
Method 1: Faceplate Customization in WinCC Graphics Designer (Direct Countdown View)
-
Expose Timer Remaining Time in CFC:
- In the motor CFC chart, locate the timer block driving the start interlock (e.g.,TimerPorC_TIM_P).
- Note the parameter outputting remaining time: forTimerP, useP_Time(or remaining time calculationTi - Time).
- Ensure the parameter has{ S7_m_c := 'true' }enabled so it is transferred to WinCC Tag Management during OS compilation. -
Modify the CEMAT Faceplate in Graphics Designer:
- In WinCC Explorer, open Graphics Designer.
- Save a project backup copy of@PG_C_DRV_1D_STANDARD.pdlbefore modifying.
- Open@PG_C_DRV_1D_STANDARD.pdl.
- Insert anI/O Field(from Smart Objects) into an unused section of the faceplate.
- In Properties -> Low/High Limits, set format toDecimalorTime(e.g.,999 sormm:ss).
- In Properties -> Output Value, configure dynamic tag binding:- Use dynamic tag prefix substitution:
TagPrefix + '.Timer_P_Time'(or the symbolic tag name of the timer output). - In Properties -> Display / Visibility, bind visibility to a boolean flag: visible only when the timer is active (
Timer.Running == 1). - Add a static text label:
Restart Lockout:. - Save the PDL file in the local project
GraCSfolder.
- Use dynamic tag prefix substitution:
Method 2: The CEMAT Standard Associated Block Method (No Graphic Edits)
- In the motor CFC chart, insert a
C_MEASURblock. - Connect the timer remaining time output to
C_MEASUR.MV. - Set
C_MEASUR.UNITto's'or'min'. - In the
C_DRV_1Dblock properties, link theC_MEASURblock under the associated measurement list. - Compile the OS. The CEMAT faceplate automatically creates a navigation jump button to the timer's measurement display.
Verification
Verify countdown visualization and interlock coordination:
- Motor Stop Trigger: In WinCC Runtime, stop the motor. Confirm that the restart lockout timer starts immediately in the AS.
- Faceplate Countdown Inspection: Open the
C_DRV_1Dfaceplate. Confirm that the 'Restart Lockout' field illuminates, displaying the remaining seconds or minutes decrementing in real time. - Start Invalidation: Attempt to command a motor start while the countdown is active. Confirm that
C_DRV_1Drejects the command due to the active start interlock (EBM). - Timer Expiration: Allow the timer to reach zero. Confirm that the countdown field disappears (or indicates 0), the start interlock clears, and the motor command buttons return to active/ready status.
Limitations and Operational Precautions
If customizing @PG_C_DRV_1D_STANDARD.pdl directly, ensure you uncheck this picture in the OS Project Editor Basic Data tab; otherwise, future OSPE runs or CEMAT updates will overwrite your modifications. Furthermore, ensure timer data types match WinCC I/O Field formatting: S5TIME values must be converted to standard integers or REAL seconds before display in WinCC.
Engineer FAQ
Why doesn't C_DRV_1D have UserAna1 like standard APL blocks?
CEMAT was developed as an independent industry standard for minerals and cement before the APL style guide was established, utilizing associated measurement blocks (C_MEASUR) rather than internal auxiliary analog inputs.
How can I format S5TIME values into readable seconds in WinCC?
Convert the S5TIME or TIME value in the AS to a REAL or DINT representing total seconds (divide milliseconds by 1000.0) before transmitting to WinCC.
Will modifying @PG_C_DRV_1D affect all motors in the plant?
Yes. Modifying the standard faceplate template in the GraCS directory applies the new display field to all C_DRV_1D instances across the entire WinCC OS project.
Can the countdown timer display be hidden when the motor is running?
Yes. By binding the I/O Field's Visible property to the timer's active status bit, the field remains completely hidden during normal motor operation.
Does customizing the CEMAT faceplate require stopping the AS controller?
No. Customizing graphic faceplates in Graphics Designer is purely a WinCC HMI change and requires zero AS controller compilation or downtime.
Technical References
- SIMATIC PCS 7 CEMAT Drive and Valve Engineering Manual V8.2 / V9.0
- WinCC V7.4 Graphics Designer Faceplate Configuration Guide
- SIMATIC PCS 7 APL Style Guide: Creating and Modifying Faceplates
Related Articles
- Resolving CEMAT Check Tool Fault 65 and Fault 68 in CFC Run Sequence
- Activating Disabled APL_ANALOG_OP_DISPLAY and APL_OP_BUTTON Faceplate Controls
- Creating Custom Block Icons and Automating OS Picture Placement from CFC in PCS 7