Establishing Fault-Tolerant S7 Connections Between CPU 410-5H and CPU 414-5H
Establishing a fault-tolerant S7 connection between a SIMATIC PCS 7 CPU 410-5H and a classic STEP 7 CPU 414-5H without communication loss requires configuring the connection in NetPro across a common Multiproject and ensuring subnets and IP gateways are aligned. Because CPU 414-5H provides only one onboard PROFINET interface (or requires an external CP 443-1 for redundant network routing) while CPU 410-5H provides dual interfaces, the fault-tolerant connection must be compiled and downloaded to both stations simultaneously via 'Selected Stations' or 'Connections and Gateways'. Runtime data exchange is executed using BSEND (SFB12) and BRCV (SFB13) with matching R_ID parameters.
Table of Contents
- S7 Fault-Tolerant Connection Topology: CPU 410-5H vs CPU 414-5H
- Interface Architecture and External CP 443-1 Requirements
- Communication Block Configuration: BSEND and BRCV (SFB12/13)
- Step-by-Step NetPro Configuration and Download Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
S7 Fault-Tolerant Connection Topology: CPU 410-5H vs CPU 414-5H
Connecting modern SIMATIC PCS 7 controllers (CPU 410-5H) with legacy or standalone manufacturing lines running S7-400H controllers (such as CPU 414-5H) requires establishing a high-availability S7 Fault-Tolerant Connection. A fault-tolerant connection establishes up to four underlying communication pathways (two controllers $\times$ two network subnets), enabling bumpless data exchange even if one controller or one physical network switch fails.
Engineers frequently struggle with this integration when the two systems are engineered in separate projects. S7 fault-tolerant connections cannot be negotiated dynamically as raw TCP sockets; both endpoints must be defined inside NetPro to generate the internal communication job tables.
Interface Architecture and External CP 443-1 Requirements
A vital hardware consideration differentiates CPU 410-5H from CPU 414-5H:
- CPU 410-5H: Features dual onboard PROFINET interfaces (Interface 1 and Interface 2, total 4 physical ports), supporting redundant plant bus connections natively without extra CP cards.
- CPU 414-5H: Possesses only a single onboard PROFINET interface (plus PROFIBUS DP). To achieve genuine 4-way media and controller redundancy across two separate Industrial Ethernet rings, the CPU 414-5H rack must be equipped with an external CP 443-1 (6GK7443-1EX30-0XE0).
If both stations share only a single flat Industrial Ethernet ring, a 2-way fault-tolerant connection can be configured using the onboard ports, provided both controller pairs share identical IP subnets.
Communication Block Configuration: BSEND and BRCV (SFB12/13)
The table below details communication function blocks, parameters, and roles for S7 fault-tolerant data exchange:
SFB12 (BSEND)SFB13 (BRCV)BSEND into a designated data block (DB).IDWORD Input16#0001R_IDDWORD Input16#...DONE / NDRBOOL OutputDONE indicates send complete; NDR indicates new data received.ERROR / STATUSSTATUS = 16#0000 indicates healthy transmission.Step-by-Step NetPro Configuration and Download Procedure
- Combine Projects into Common Multiproject:
- In SIMATIC Manager, selectFile -> New -> Multiproject.
- Add both the PCS 7 project (containing CPU 410-5H) and the STEP 7 project (containing CPU 414-5H) into this multiproject. - Harmonize Industrial Ethernet Subnet in NetPro:
- Open NetPro from SIMATIC Manager.
- Merge the Industrial Ethernet subnets of both projects so both controllers connect to the same logical subnet object (e.g.,PlantBus_1). - Insert S7 Fault-Tolerant Connection:
- Select the CPU 410-5H controller in the NetPro grid.
- In the connection table, insert a new connection: select the CPU 414-5H as the partner and choose S7 fault-tolerant connection.
- Note the assigned ConnectionID(e.g.,W#16#1). - Program BSEND and BRCV in CFC or STL:
- In the CPU 410-5H, instantiateSFB12 (BSEND): assignIDandR_ID = DW#16#10.
- In the CPU 414-5H, instantiateSFB13 (BRCV): assign matchingIDandR_ID = DW#16#10. - Compile and Download Network Connections:
- In NetPro, selectNetwork -> Save and Compile -> Compile completely.
- Select the CPU 410-5H station -> select PLC -> Download to Current Station -> Connections and Gateways.
- Select the CPU 414-5H station -> execute identical download of connections.
Verification
Verify fault-tolerant communication stability through the following checks:
1. In NetPro online mode (PLC -> Open Online Partner): verify that the S7 fault-tolerant connection displays status Established.
2. In CFC or LAD test mode, monitor BSEND.DONE and BRCV.NDR: confirm that new data pulses high cyclically with ERROR = FALSE.
3. Perform a redundancy switchover on CPU 410-5H: confirm that data transmission continues uninterrupted across the standby controller.
Limitations and Operational Precautions
Downloading connection tables (Connections and Gateways) to an S7-400H controller pair can be performed in RUN mode provided the station configuration was not drastically altered. However, never execute a 'Download Station' or 'Entire Hardware Config' without verifying that the partner CPU is synchronized in redundant mode; downloading uncompiled connection lists can force the controller into STOP. Always ensure that R_ID values are unique across all communication blocks on the same connection.
Engineer FAQ
Technical References
- SIMATIC S7-400H High Availability Systems Manual (A5E00267695)
- SIMATIC NET S7 Communication with S7-400 System Manual
- Siemens Technical Support: Configuring Fault-Tolerant S7 Connections in NetPro (SIOS Entry ID 109748968)
Related Articles
- Resolving Cyclic Communication Errors and Status Flickering in APL Rcv_AnaVal Blocks
- Interfacing PCS 7 V9.0 AS Controllers with Legacy S7-314 CPUs via S7 Communication
- Implementing One-Sided S7 Communication (PUT and GET) Between PCS 7 and Non-PCS 7 Controllers
Related Tags
- CPU 410-5H
- CPU 414-5H
- NetPro
- Fault-Tolerant Connection
- BSEND BRCV
- S7 Communication