Expanding Interlock Capacity in SIMATIC PCS 7 APL Faceplates: Upgrading Intlk02/04 to Intlk08 and WinCC Tag Integration
To add three additional interlock conditions to an existing motor or valve in SIMATIC PCS 7 APL, replace the existing Intlk02 or Intlk04 block in CFC with an Intlk08 block. Reconnect the existing inputs and wire the new interlocks to In05, In06, and In07. Connect the Out pin of Intlk08 to the drive's interlock input (e.g., Permit, Intlock, or Protect), and reconnect the drive's LockAct output to Intlk08.LockAct. Execute a CFC compilation with 'Generate Module Drivers' and run Compile OS. The WinCC APL drive faceplate dynamically adapts its Interlock view to display all eight interlocks without manual PDL graphic editing.
Table of Contents
- APL Dynamic Interlock Architecture and Faceplate Adaptation
- Block Type Selection: When to Migrate from Intlk04 to Intlk08
- CFC Engineering Workflow: Block Replacement and Pin Reconnection
- WinCC Tag Management and OS Compile Synchronization
- APL Interlock Block Migration Comparison
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
APL Dynamic Interlock Architecture and Faceplate Adaptation
In traditional DCS graphics, modifying an interlock display required manually editing graphic screens (.pdl), adding text fields, and binding new tags to screen objects. In the SIMATIC PCS 7 Advanced Process Library (APL), faceplates are completely dynamic and data-driven.
APL drive blocks (MotL, MotRevL, MotSpdL, VlvL, Vlv2WayL) feature dedicated interlock inputs: Permit (start permissive), Intlock (interlock without reset), and Protect (interlock with reset / protection). When an APL interlock block (Intlk02, Intlk04, Intlk08, Intlk16) is connected to one of these inputs, the OS compilation engine automatically structures the WinCC tags so that the drive faceplate reads the interlock block's configuration and dynamically renders the exact number of active input rows.
Block Type Selection: When to Migrate from Intlk04 to Intlk08
Standard equipment templates often ship configured with an Intlk04 block (providing 4 inputs: In01 through In04). When process modifications demand additional trip criteria (such as adding high bearing temperature, seal water pressure low, and motor winding vibration), the 4-input capacity is exceeded.
Instead of cascading multiple Intlk04 blocks (which complicates faceplate navigation and requires operators to drill through nested faceplates), the recommended engineering practice is to replace Intlk04 with a single Intlk08 block. This keeps all interlock statuses consolidated on a single, clean faceplate screen.
CFC Engineering Workflow: Block Replacement and Pin Reconnection
Follow this procedure in Continuous Function Chart (CFC) to upgrade the interlock block:
- Document Existing Parameters: Open the CFC chart containing the motor drive and existing
Intlk04. Note down inverted pins (InvIn01..04), configured text strings (OS_Perm, custom texts), andFeaturebit settings (e.g.,Feature.Bit31for First-In). - Insert Intlk08: Drag
Intlk08(FB1825) from the APL library catalog into the CFC chart. - Reconnect Existing Signals: Reconnect field digital signals to
In01throughIn04. Wire the three new trip signals intoIn05,In06, andIn07. SetInvInxxparameters for any normally closed (NC) fail-safe inputs. - Reconnect Drive Handshake Pins:
- ConnectIntlk08.OuttoMotL.Intlock(orPermit/Protect).
- ConnectMotL.LockActtoIntlk08.LockAct(essential for interlock feedback processing). - Configure Feature Bits: Enable
Feature.Bit31if First-In alarm latching is required. - Delete Obsolete Intlk04: Delete the old
Intlk04block from the chart.
WinCC Tag Management and OS Compile Synchronization
After logic modification in CFC, the operator station database must be synchronized:
- CFC Compile: Compile the CFC charts. A delta compile is permitted if the AS remains in RUN.
- Execute OS Compile: In SIMATIC Manager, right-click the OS project and select Compile. Choose 'Changes' (Delta Compile) or 'Entire project'.
- Tag Generation: The compiler updates the WinCC Tag Management database, creating the new tag structure for
Intlk08and updating the internal pointer on the motor drive block. - No Graphic Editing Required: You do not need to open Graphics Designer or edit
@PG_MotL_Interlock.pdl. When the faceplate opens at runtime, the standard APL C-script reads the interconnected block type and renders eight rows with live status LEDs.
APL Interlock Block Migration Comparison
The following table compares parameters between Intlk04 and Intlk08 during block migration:
In01..In04)In01..In08)In01..04; connect new signals to In05..07InvIn01..InvIn04InvIn01..InvIn08OutOutPermit, Intlock, or ProtectLockActLockActLockAct outputFirstIn1 (DWORD)FirstIn1 (DWORD)Feature.Bit31 = TRUEVerification
Verify the expanded interlocks through the following procedure:
- Open the CFC chart online and verify that inputs
In01throughIn07display active live statuses (16#80). - Verify that
Intlk08.Out = 1andMotL.Intlock = 1. - In WinCC Runtime, open the motor faceplate. Click the Interlock button to open the Interlock view.
- Confirm that the faceplate displays all eight input rows, with the new interlock descriptions clearly visible.
- Trip one of the newly added inputs (e.g.,
In06). Confirm that the motor stops immediately and that the faceplate indicates the tripped condition on line 6.
Limitations and Operational Precautions
Consider these operational rules when expanding interlocks:
-
Never Leave Unused Inputs Floating: On
Intlk08, if inputIn08is unused, ensure it defaults to1(healthy) and is not inverted (InvIn08 = 0); otherwise, the block will permanently remain tripped. -
Online Delta Download Safety: In older PCS 7 versions (prior to V8.0), replacing a block type in CFC could require an AS stop. In PCS 7 V8.1 and V8.2, deleting an
Intlk04and inserting anIntlk08can be performed via Delta Download in RUN, provided work memory and block numbers are available. -
Signal Status Processing: Always ensure analog threshold comparisons (from
MonAnLorCompAn02) provide valid signal status (ST = 16#80) intoIntlk08to prevent nuisance trips.
Engineer FAQ
Can I assign custom text labels to each interlock input on the faceplate?
Yes, in CFC open block properties, navigate to inputs In01..In08, and configure the 'Identifier' or 'OS Additional Text' attribute to display custom field instrument tag names.
How do I add more than 8 interlocks if Intlk08 is full?
You can migrate to Intlk16 (FB1826) which provides 16 inputs, or cascade two Intlk08 blocks by connecting the Out of the first into In01 of the second.
Does changing from Intlk04 to Intlk08 require updating the Master Data Library?
No, both Intlk04 and Intlk08 are standard blocks already present in the PCS 7 APL library. Simply place Intlk08 from the library into the chart.
Technical References
- SIMATIC Process Control System PCS 7 Advanced Process Library (APL) Function Manual (Entry ID: 109780813)
- APL Interlock Blocks: Intlk02, Intlk04, Intlk08, Intlk16 Reference Manual
- SIMATIC PCS 7 OS Engineering Manual: Dynamic Faceplate Generation and AS-OS Tag Structures
- Siemens Industry Online Support: Migrating and Cascading APL Interlock Blocks
Related Articles
- Configuring First-In Detection (Feature Bit 31) and Interlock Diagnostics in PCS 7 APL
- Configuring Direction-Dependent Interlocks for CEMAT Bi-Directional Drive C_DRV_2D
- Connecting CEMAT C_DRV_1D Instance Data Blocks to WinCC Diagnostic Faceplates