Generating Fixed-Duration Pulses in SIMATIC PCS 7 CFC - TimerP and Pulse Configuration
In SIMATIC PCS 7 CFC, generating a fixed-duration pulse from either a momentary trigger or a sustained continuous signal is implemented using the standard Advanced Process Library (APL) block TimerP (FB1810) or CFC system block TIMER_P (FB5). By configuring the block in Pulse Mode (Mode 0), TimerP produces an output pulse of exactly the configured duration (Ti) upon detecting a rising edge (0 to 1 transition) on the input, regardless of whether the input signal remains high or drops immediately. The configured pulse duration must be greater than or equal to the cyclic interrupt execution interval of the host organization block (e.g. OB35).
Table of Contents
- Pulse Generation Mechanics in Continuous Process Control
- Configuring TimerP (FB1810) and TIMER_P (FB5) for Fixed Pulses
- CFC Signal Flow and Timing Diagram
- PCS 7 Pulse Block Operational Modes Comparison
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Pulse Generation Mechanics in Continuous Process Control
In process automation, discrete control tasks frequently require fixed-duration actuation signals:
* Sampler Valves: Opening an automated grab sampler valve for exactly 3.0 seconds upon laboratory request.
* Filter Bag Pulse Cleaning: Actuating reverse-jet compressed air solenoid valves for exactly 200 ms.
* Third-Party Handshakes: Triggering external packaging machines or weight hoppers with a guaranteed 1.0 second reset pulse.
If an operator holds a pushbutton in WinCC, or if a field limit switch remains permanently closed, the actuation signal must not remain energized. A pulse timer guarantees deterministic duration regardless of input signal retention.
Configuring TimerP (FB1810) and TIMER_P (FB5) for Fixed Pulses
In SIMATIC PCS 7, two primary standard blocks provide pulse timing:
1. TimerP (FB1810) - APL (Advanced Process Library):
* In (BOOL): Input trigger signal.
* Ti (TIME): Configured pulse duration (e.g. T#2s).
* Mode (INT): Operating Mode:
* Mode = 0: Pulse (TP). A rising edge on In drives output Out to TRUE for duration Ti. Subsequent input changes during the pulse are ignored.
* Mode = 1: Extended Pulse. A rising edge on In starts the pulse; re-triggering In during the pulse restarts the timer from zero.
* Mode = 2: On-Delay (TON).
* Mode = 3: Off-Delay (TOF).
* Out (BOOL): Pulse output signal.
2. TIMER_P (FB5) - CFC Standard Library:
* Uses identical mode enumeration and is intended for non-APL or legacy S7 program charts.
CFC Signal Flow and Timing Diagram
The execution behavior in Mode 0 (Pulse) operates deterministically as follows:
Input Signal (In)
┌─────────┐ ┌──────────────────────────────┐
───┘ └────────────────┘ └─────────
Timer Output (Out) - Mode 0 (Fixed Pulse Duration Ti = 2s)
┌────────────────┐ ┌────────────────┐
───┘ └─────────┘ └───────────────────────
◄────── Ti ──────► ◄────── Ti ──────►
(Input drops early) (Input held permanently HIGH)
Notice that even when In remains TRUE indefinitely, Out de-energizes precisely when Ti expires, preventing actuator damage.
PCS 7 Pulse Block Operational Modes Comparison
Compare the operational modes of TimerP (FB1810) to select the correct timing behavior:
Mode)Out = TRUE for TiTiOut = TRUE for TiTiOut = TRUE after TiTiOut = TRUE immediatelyIn is TRUETi after falling edgeVerification
To confirm proper fixed pulse generation in CFC:
1. In CFC Editor, place TimerP (FB1810) into a chart assigned to OB35 (100 ms).
2. Set parameter Mode := 0 and Ti := T#3s.
3. Switch CFC to Test Mode online.
4. Toggle In := TRUE for 0.5 seconds, then return to FALSE; verify that Out remains TRUE for exactly 3.0 seconds.
5. Toggle In := TRUE and leave it permanently TRUE; verify that Out de-energizes after exactly 3.0 seconds.
6. Connect Out to the field output channel driver (Pcs7DiOu); confirm on the physical card LED that the pulse terminates on schedule.
Limitations and Operational Precautions
The configured pulse duration Ti must be significantly longer than the cyclic interrupt sampling time of the execution OB. For example, if TimerP is scheduled in OB35 (100 ms execution), configuring Ti = T#50ms will result in erratic pulse lengths (or missed pulses) due to execution discretization. For high-speed sub-millisecond pulses, use specialized hardware counter or pulse-train output modules (e.g. FM 350-1 or ET 200M fast pulse outputs).
Engineer FAQ
What happens if a new trigger pulse arrives while the timer is still timing?
In Mode 0 (Pulse), the block ignores all input transitions until the configured time Ti has completely expired. In Mode 1 (Extended Pulse), a new rising edge restarts the timing interval.
Can I reset an active pulse before it finishes?
Yes. In APL TimerP, asserting the input Reset := TRUE immediately de-energizes Out and resets elapsed time to zero.
Why did the pulse output fail to energize on a fast 20 ms field pulse?
If the block is installed in OB32 (1000 ms scan rate), a 20 ms field pulse arriving between OB scans will be missed completely. Move the channel driver and TimerP to OB35 (100 ms) or use process interrupt OB40.
Where is TimerP located in the PCS 7 catalog?
In the CFC catalog, navigate to Libraries -> PCS 7 AP Library V82 -> Blocks -> Math / Time -> TimerP (FB1810).
Technical References
- SIMATIC Process Control System PCS 7 Advanced Process Library (APL) Manual - A5E36188448-AC
- SIMATIC Process Control System PCS 7 CFC for S7 Manual - A5E36188448-AA
- Siemens Industry Online Support (SIOS) Entry ID 109780813 - TimerP Block Description
Related Articles
- Developing Custom SCL Function Blocks with Multi-Instance Timers (TIMER_P) in SIMATIC PCS 7
- CFC vs SFC in SIMATIC PCS 7 - Continuous Process Control vs Sequential Batch Architecture
- Calculating Process Value Standard Deviation in SIMATIC PCS 7 CFC for Tank Leak Detection
Related Tags
- TimerP
- Pulse Generation
- APL FB1810
- TIMER_P
- CFC Timing