Generating WinCC Alarm Messages for Drive Interlock Trip Conditions in SIMATIC PCS 7
In SIMATIC PCS 7 Advanced Process Library (APL), interlock blocks (such as Intlk02, Intlk04, Intlk08) are pure logic blocks and do not contain integrated Alarm_8P message blocks; consequently, configuring alarms directly inside the interlock block is not supported. To generate an alarm in WinCC Runtime when an interlock trips a motor, connect the inverted output of the interlock block (or dedicated trip condition) to an external message input on the motor block (such as MotL.ExtMsg1, ExtMsg2, or ExtMsg3). In the motor block's message configuration dialog, assign the message text (e.g. 'Interlock Tripped: Lubrication Low'). This routes the alarm directly under the motor tag, triggering faceplate alarm badges and group display updates.
Table of Contents
- Why Interlock Blocks Do Not Generate Native WinCC Alarms
- Architecture of External Messages (ExtMsg1..3) on Drive Blocks
- Step-by-Step CFC Interconnection and Message Setup Workflow
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Why Interlock Blocks Do Not Generate Native WinCC Alarms
In SIMATIC PCS 7 process automation architectures, software design balances diagnostic visibility against controller memory and Process Object (PO) consumption. Interlock blocks (Intlk02, Intlk04, Intlk08, Intlk16) are designed as lightweight combinational logic blocks.
If every interlock block contained native Alarm_8P message routines, controller execution cycles would slow down and each interlock instance would consume additional AS and OS Process Objects. Therefore, Siemens engineered interlock blocks to evaluate logic (In01..In08) and pass a single consolidated boolean status (Out = 0 or 1) to the technological actuator block.
When an interlock trips a drive, the operator must know which specific field condition tripped the motor without having to open engineering CFC charts. This is accomplished using the actuator block's external message architecture.
Architecture of External Messages (ExtMsg1..3) on Drive Blocks
APL drive and actuator blocks—such as MotL (FB1850), MotRevL (FB1851), MotSpdCl (FB1856), and VlvL (FB1899)—incorporate native Alarm_8P instances with pre-allocated external message channels:
SIG4$$BlockComment$$ External message 1SIG5$$BlockComment$$ External message 2SIG6$$BlockComment$$ External message 3By tying interlock trip states to ExtMsg1..3, the generated alarm inherits the technological tag name of the motor (e.g., 101_PUMP_01). This ensures that:
- The WinCC alarm line displays the motor tag name and description.
- The motor block's Group Display (
@PG_GroupDisplay) in the overview area illuminates with an active alarm icon. - Clicking the alarm line in the OS alarm banner opens the motor faceplate directly.
Step-by-Step CFC Interconnection and Message Setup Workflow
To configure an interlock trip alarm for a motor in CFC, execute the following technical procedure:
-
Connect Interlock Output to Motor Interlock Input: In CFC, connect
Intlk04.OuttoMotL.Intlock(orProtect/Permit, depending on whether it is a running interlock, safety interlock, or start permissive). -
Invert Signal for External Message: An interlock healthy state is
Out = 1, and trip state isOut = 0. ConnectIntlk04.OuttoMotL.ExtMsg1. Click on the connection pin atExtMsg1and pressCtrl+I(or right-click and selectInvert Input) so that when the interlock trips (0), the input pin reads1. -
Configure Alarm Message Text: Right-click
MotLand selectObject Properties. Click the 'Messages...' button. -
Edit Signal 4 (SIG4): In the message table, locate the row corresponding to
SIG4(External Message 1):
- Set the Message Class (e.g.Alarm - HighorAS Process Control Fault).
- In the Event column, replace the default text with the specific interlock description:Interlock Trip: Lubrication Pressure Low. -
Compile and Download: Save the dialog. Execute
Chart -> Compile -> Chart as Program -> Changes Onlyand download to the AS. Execute an OS compile (Compile OS -> Changes Only) to update WinCC Alarm Logging.
Verification
Verify that interlock trips generate clear WinCC alarms through these testing steps:
- Simulate Interlock Trip: In CFC Test Mode, force the input signal feeding the interlock (
Intlk04.In01) to0. - Actuator Reaction: Verify that
MotL.Fwddrops to0, stopping the motor, and the red interlock badge appears on the faceplate. - WinCC Alarm Display: In WinCC OS Runtime, observe the alarm banner. Confirm that an alarm appears reading:
[Tag: 101_PUMP_01] Interlock Trip: Lubrication Pressure Low - Group Display Hierarchy: Verify that the picture icon containing the motor displays a flashing red alarm badge in the top overview hierarchy.
Limitations and Operational Precautions
When engineering interlock alarms, adhere to these operational and alarm management standards:
- Alarm Flood Prevention (ISA-18.2): Do not create separate alarms on both the transmitter (
MonAnL) and the motor (MotL.ExtMsg1) if they report the exact same event. If the lubrication pressure transmitter already generates an alarm, consider settingExtMsg1to a lower priority or routing it to the process log. - First-Out Interlock Identification: If multiple interlock conditions feed a single
Intlk08block, use the APL First-In First-Out (FirstIn) feature. The interlock faceplate will highlight which exact sensor caused the trip. - Inversion Accuracy: Ensure input inversion is properly applied; failing to invert
ExtMsg1will generate a persistent standing alarm when the interlock is healthy.
Engineer FAQ
Why can I not find a 'Messages' button on the Intlk04 block in CFC?
The Intlk04 block is an algorithmic logic block without Alarm_8P message capability. Only technological blocks (MotL, VlvL) possess the message configuration interface.
Can I pass the name of the failing interlock input dynamically into the alarm?
Yes. By interconnecting the interlock status word to the motor's associated values (ExtVa104..07), dynamic text placeholders can insert the failing signal tag into the alarm text.
What is the difference between Intlock, Permit, and Protect on MotL?
Permit is a start permissive (only checked prior to starting). Intlock is an operating interlock with automatic reset. Protect is a safety interlock requiring manual operator reset.
Technical References
- SIMATIC Process Control System PCS 7 Advanced Process Library (APL) Manual (A5E39140304)
- ISA-18.2: Management of Alarm Systems for the Process Industries
- SIMATIC Process Control System PCS 7 Operator Station Engineering Manual (A5E36173004)
Related Articles
- Preserving Motor Command States and Operating Modes After Fault Reset in APL Block MotSpdCl.md
- Enabling Operator Input Request Messages (Bedienanforderung) on APL Block MonDiL in SIMATIC PCS 7.md
- Clearing Non-Acknowledged and Unacknowledged Phantom Alarms in SIMATIC PCS 7 OS Runtime.md