Historical Deprecation and Migration of Ethernet Communication Blocks FB205 and FB206 Across PCS 7 Versions
In legacy SIMATIC PCS 7 systems, function blocks FB205 (FR_AGSEN) and FB206 (FR_AGRCV) originated in the obsolete PCS 7 V5.2 Communication Library to provide a simplified CFC interface for CP 443-1 Ethernet communications. These wrapper blocks are absent from all modern PCS 7 libraries (V6.0, V7.x, V8.x, V9.x) because Siemens discontinued the dedicated Communication Library in favor of direct utilization of standard SIMATIC NET communication functions FC5 (AG_SEND) and FC6 (AG_RECV) from the SIMATIC_NET_CP library, or native S7 fault-tolerant connections (BSEND/BRCV). Furthermore, in modern PCS 7 Basis Libraries, block numbers FB205 and FB206 were reassigned to completely different system blocks (OB_BEGIN_HPN and MOD_CENTRAL), making migration to standard FC5/FC6 mandatory to prevent compiler collisions.
Table of Contents
- Historical Context: The PCS 7 V5.2 Communication Library
- Why FR_AGSEN and FR_AGRCV Were Removed in Modern Releases
- Block Number Reassignment in Modern PCS 7 Basis Libraries
- Migration Workflow to Standard FC5 and FC6 (SIMATIC_NET_CP)
- Comparison of Communication Block Architectures Across PCS 7 Eras
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Historical Context: The PCS 7 V5.2 Communication Library
During the late 1990s and early 2000s, SIMATIC PCS 7 V5.0 to V5.2 introduced Ethernet-based controller networking via CP 443-1 communication processors. In that era, the Step 7 standard communication functions AG_SEND (FC5) and AG_RECV (FC6) required engineers to manage manual pulse triggering, ANY pointers, and complex error return codes in STL.
To simplify engineering within Continuous Function Chart (CFC), Siemens authored the 'PCS 7 Communication Library', supplying two wrapper blocks:
1. FB205 FR_AGSEN: Handled cyclic scheduling and transmission buffer pointers to the CP 443-1.
2. FB206 FR_AGRCV: Handled reception buffer pointers and incoming telegram decoding.
Why FR_AGSEN and FR_AGRCV Were Removed in Modern Releases
When PCS 7 V6.0 was released, Siemens overhauled the entire communication and driver philosophy:
- Modernized CFC Compiler: The CFC compiler gained native support for elementary functions (FCs), allowing FC5 and FC6 to be wired directly into charts without requiring wrapper FBs.
- Shift to S7 Configured Connections: For plant-wide automation, Siemens established S7 Connections using system function blocks SFB 12 (
BSEND) and SFB 13 (BRCV), which provide deterministic, high-throughput, fault-tolerant data exchange integrated with the OS Server. - Retirement of the Library: The separate Communication Library was eliminated from the installation media to enforce standardization.
Block Number Reassignment in Modern PCS 7 Basis Libraries
A dangerous trap for engineers migrating legacy projects into PCS 7 V8 or V9 is block number reassignment:
- FB205: Reassigned in modern
PCS_7_BASISLIBRARYtoOB_BEGIN_HPN(H-CPU diagnostic function block). - FB206: Reassigned in modern
PCS_7_BASISLIBRARYtoMOD_CENTRAL(Non-diagnostic central module supervisor).
If an engineer attempts to compile a migrated V5 project containing legacy FR_AGSEN while the modern Basis Library is present, the Step 7 compiler detects an irreconcilable symbol clash, aborting compilation.
Migration Workflow to Standard FC5 and FC6 (SIMATIC_NET_CP)
To modernize legacy communication charts:
- Open the project in SIMATIC Manager on the updated Engineering Station.
- Open the SIMATIC_NET_CP library under CP 400 > Blocks.
- Copy FC5 (
AG_SEND) and FC6 (AG_RECV) into the S7 program's offline block folder. - Open the CFC charts. Delete the obsolete FB205 and FB206 instances.
- In CFC, select Options > Block Types... and clean up FB205 and FB206 from the chart database.
- Place FC5 and FC6 into the chart. Reconnect the Connection ID (
ID), Hardware Address (LADDR), and Data Pointer (DATA). - Recompile the CFC charts with scope 'Entire program'.
Comparison of Communication Block Architectures Across PCS 7 Eras
The following table compares Ethernet communication approaches across different generations of SIMATIC PCS 7:
FR_AGSEN / FR_AGRCV (FB205/206)AG_SEND / AG_RECVBSEND / BRCV (SFB 12 / SFB 13)OB_BEGIN_HPN / MOD_CENTRALVerification
Verify modern communication function execution in CFC:
1. In SIMATIC Manager, verify that the offline block folder contains FC5 and FC6 and no longer references legacy FB205/FB206 wrappers.
2. Open the CFC chart online in Test Mode; confirm that AG_SEND (FC5) pulses DONE = 1 and ERROR = 0 on each transmission trigger.
3. Confirm that the remote partner receives the data payload accurately.
4. Verify that AG_RECV (FC6) updates the target DB buffer with valid process bytes upon packet arrival.
Limitations and Operational Precautions
Never attempt to import archived V5.2 .bin block files for FB205/FB206 into a modern PCS 7 project. Doing so overwrites the modern Basis Library's OB_BEGIN_HPN block, causing catastrophic controller driver generation failures during AS compilation. If communicating with another SIMATIC S7 station, always prioritize configured S7 connections (BSEND/BRCV) over raw AG_SEND/AG_RECV to take full advantage of controller redundancy and diagnostic logging.
Engineer FAQ
Why did Siemens delete the PCS 7 Communication Library after V5.2?
It was redundant. Step 7 introduced native CFC support for FCs, allowing engineers to call the official SIMATIC NET blocks (FC5/FC6) directly without extra wrapper layers.
Can I use FC5 and FC6 with redundant S7-400H CPUs?
Yes, but you must configure redundant CPs and program application-level connection monitoring. For redundant systems, configured S7 Fault-Tolerant Connections using BSEND/BRCV are strongly recommended because switchover is handled automatically in hardware.
Where are FC5 and FC6 located in Step 7?
In the standard library SIMATIC_NET_CP inside the folder CP 400 > Blocks.
Technical References
- SIMATIC NET Program Blocks for SIMATIC NET S7-CPs Manual
- SIMATIC Process Control System PCS 7 Software Update Guide (V5.2 to V6.1)
- SIMATIC S7-400 Industrial Communication System Manual
Related Articles
- Migrating Legacy Ethernet Communication Blocks FB205 (FR_AGSEN) and FB206 (FR_AGRCV) to AG_SEND and AG_RECV in PCS 7
- Identifying Replacements for Obsolete FB205 and FB206 During PCS 7 V5.2 to V6.1 Migration
- Monitoring Redundant S7-400H Controller Connections in SIMATIC PCS 7 Using System Diagnostics vs CONEC and SFC 87