How to Fix HW Config Error 1230 - 2000 'Unable to Create the Object' When Inserting CPU 410-5H in PCS 7 V8.1
In SIMATIC PCS 7 V8.1, HW Config errors '1230: 2000 Unable to create the object' or '2772:103 An error occurred creating the hardware' when inserting a CPU 410-5H (6ES7410-5HX08-0AB0) rack into a project indicate that the STEP 7 Hardware Catalog lacks the required Hardware Support Package (HSP), the CPU 410 engineering components were omitted during initial PCS 7 setup, or obsolete power supply modules are selected. To resolve this, update the Hardware Catalog via 'Options > Install Hardware Updates', install the dedicated CPU 410-5H HSP, verify power supply compatibility (replacing obsolete PS 405 modules with approved successors such as 6ES7405-0KA01-0AA0), and insert the station using the PCS 7 'Preconfigured Station' wizard.
Table of Contents
- Root Causes of HW Config Error 1230: 2000 and 2772:103
- Hardware Catalog Updates and CPU 410 Hardware Support Packages (HSP)
- Power Supply Module Compatibility and Replacement Standards
- Clean Station Insertion Workflow Using Preconfigured Stations
- Comparison of Hardware Support Package States and Error Signatures
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Root Causes of HW Config Error 1230: 2000 and 2772:103
The SIMATIC CPU 410-5H Process Automation controller (6ES7410-5HX08-0AB0) is a high-performance CPU designed specifically for PCS 7 systems. Because it utilizes a dynamic System Expansion Card (SEC) architecture for Process Object capacity scaling, its hardware configuration profiles differ significantly from classic S7-400 CPUs:
- Error 1230: 2000 (
Unable to create the object): Occurs when an engineer attempts to drag a CPU 410-5H from the hardware catalog into an empty rack slot, but the underlying STEP 7 COM object registration or hardware definition database file (.dat/.xml) is corrupt, missing, or blocked by Windows registry permissions. - Error 2772:103 (
An error occurred creating the hardware): Typically triggered when attempting to insert a 'Preconfigured Station' where referenced hardware elements (such as obsolete power supplies or incompatible sync modules) cannot be instantiated in the active hardware database. - Installer Omission: During custom installation of PCS 7 V8.1, if the engineer unchecks or omits the 'SIMATIC CPU 410-5H Support Package', the base STEP 7 installation will not contain the device descriptors required to create the controller object.
Hardware Catalog Updates and CPU 410 Hardware Support Packages (HSP)
To ensure the Engineering Station possesses all required device descriptions for the CPU 410-5H:
- Launch HW Config and Check Catalog Version:
* Open HW Config in any project.
* Check the catalog tree underSIMATIC 400 > CPU 400 > CPU 410.
* IfCPU 410-5His missing or missing firmware version profiles (e.g., V8.1 / V8.2), the catalog must be updated. - Download and Install HSP:
* In HW Config, select menuOptions > Install Hardware Updates....
* SelectDownload from Internet(or browse to a locally extracted HSP folder).
* Click Execute. LocateHSP 0244(or applicable CPU 410 HSP package).
* Check the package, click Download, and then click Install.
* Note: All open STEP 7 applications must be closed during the HSP installation process. - Re-Registering Corrupted Components:
* If HSP installation reports success but Error 1230 persists, insert the PCS 7 V8.1 installation DVD/USB, choose Modify/Repair, and explicitly select the SIMATIC S7-400 CPU 410-5H software component.
Power Supply Module Compatibility and Replacement Standards
A frequent hidden trigger of Error 2772:103 during station creation is the selection of legacy, obsolete power supply modules:
- The Obsolete Hardware Trap: Legacy projects often reference the discontinued DC 24V power supply module
PS 405 10A(6ES7405-0KA00-0AA0), which was declared obsolete and is not validated for pairing with the modern high-inrush current demands of CPU 410-5H. - Approved Successor Hardware:
- For DC 24V systems: Deploy the current
PS 405 10A(6ES7405-0KA01-0AA0) or redundantPS 405 10A R(6ES7405-0KR02-0AA0). - For AC 120/230V systems: Deploy
PS 407 10A(6ES7407-0KA02-0AA0) or redundantPS 407 10A R(6ES7407-0KR02-0AA0). - In HW Config, deleting the unassigned or obsolete power supply before inserting the CPU eliminates conflicts in the backplane power-budget calculation tables.
Clean Station Insertion Workflow Using Preconfigured Stations
To avoid manual hardware linking errors and ensure all internal H-Sync and rack profiles are created flawlessly, use the Preconfigured Station workflow:
- Open SIMATIC Manager:
* Right-click the Multi-project folder (or sub-project).
* SelectInsert New Object > Preconfigured Station.... - Select CPU 410 Station Template:
* In the wizard dialog, selectSIMATIC PCS 7 Box / AS Station.
* ChooseAS 410 Single StationorAS 410 Redundant Station (H).
* Select the appropriate firmware revision (Firmware V8.1) and System Expansion Card (SEC) tier. - Compile and Save:
* Open the newly generated station in HW Config.
* Assign the physical rack slots, insert approved power supply modules, and configure the integrated PROFINET ports.
* ExecuteStation > Save and Compile. The station compiles cleanly with 0 Errors.
Comparison of Hardware Support Package States and Error Signatures
The table below outlines common HW Config error codes encountered during S7-400 and CPU 410-5H hardware engineering.
Verification
To confirm that CPU 410-5H hardware configuration is resolved:
1. In HW Config, verify that the CPU 410-5H (6ES7410-5HX08-0AB0) appears in Slot 3 (or Slot 4) of the UR2/CR3 rack without error alerts.
2. Double-click the CPU 410-5H: confirm that the Properties window opens correctly, displaying the PN-IO, Interface, and Cycle/Clock Memory tabs.
3. Select Station > Check Consistency. Verify that the compilation log window reports: Check consistency: 0 Error(s), 0 Warning(s).
4. Perform Station > Save and Compile. Confirm that hardware system data blocks (SDBs) generate successfully into the block folder.
5. In SIMATIC Manager, verify that the CFC chart folder and symbol table are successfully created under the S7 Program container.
Limitations and Operational Precautions
- Never attempt to force an incompatible legacy power supply into a CPU 410-5H rack; inadequate backplane power stability can cause controller warm-restart failures during heavy I/O polling.
- CPU 410-5H requires a valid physical System Expansion Card (SEC) inserted into the rear of the CPU module before power-up; without the SEC card, the CPU will remain in STOP mode.
- When updating Hardware Support Packages (HSP), always ensure that all engineering team members install the identical HSP version to prevent multi-project synchronization lockouts.
- Verify final hardware ordering numbers (MLFBs) and firmware revisions against the applicable Siemens catalog and authorized distributor quotation.
Engineer FAQ
Can CPU 410-5H run in PCS 7 V8.0?
CPU 410-5H was introduced in PCS 7 V8.0 SP1 with dedicated hardware support packages. However, PCS 7 V8.1 or higher is strongly recommended to utilize full firmware capabilities and dynamic Process Object expansion.
What is the order number for the successor to the obsolete PS 405 10A?
The legacy power supply 6ES7405-0KA00-0AA0 is replaced by approved successor module 6ES7405-0KA01-0AA0.
Why did repairing PCS 7 installation fix Error 1230: 2000?
The PCS 7 installer re-registers the STEP 7 ActiveX and COM automation libraries (s7hcompx.dll) and restores missing XML schema definitions that HW Config relies on to instantiate complex hardware objects.
Technical References
- SIMATIC Process Control System PCS 7 CPU 410-5H Process Automation System Manual
- Siemens Industry Online Support: Error 1230:2000 in STEP 7 HW Config
- Siemens Industry Online Support: Product Discontinuation of PS 405 10A Modules
Related Articles
- Hardware-in-RUN (H-CiR) on Redundant S7-400H and CPU 410 Systems
- How to Resolve HW Config Consistency Errors 'Unable to Find Corresponding Object' on Redundant S7-400H Systems
- Troubleshooting CFC Module Driver Generation Failures in PCS 7