How to Integrate SINAMICS G120 Drives via PROFIBUS in PCS 7 Without Drive ES Libraries
To integrate a SINAMICS G120 drive (e.g., CU240 or CU230P-2) into SIMATIC PCS 7 via PROFIBUS-DP without purchasing the Drive ES PCS 7 library, engineers can utilize standard GSD telegrams (such as Telegram 352 or Telegram 20) with direct peripheral addressing. In HW Config, insert the G120 from the standard PROFIBUS catalog and assign standard Telegram 352 (6 PZD words). In CFC, use standard APL channel drivers or custom SCL blocks to assemble the PROFIdrive Control Word 1 (STW1) and 16-bit speed setpoint (NSOLL_A scaled 0 to 16384 for 0% to 100%). Commanding STW1 = 16#047E (Ready to switch on) followed by STW1 = 16#047F starts the drive, while incoming words provide Status Word 1 (ZSW1), actual speed (NIST_A), motor current, and torque.
Table of Contents
- Drive ES PCS 7 Library vs Direct PROFIdrive GSD Telegrams
- Structure of Standard Telegram 352 (6 PZD / 6 PZD)
- PROFIdrive Control Word 1 (STW1) and Sequence Logic
- CFC Interfacing: Connecting Standard APL Blocks to Peripheral I/O
- Telegram 352 Parameter and Bit Assignment Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Drive ES PCS 7 Library vs Direct PROFIdrive GSD Telegrams
When connecting variable frequency drives (VFDs) to SIMATIC PCS 7, engineers typically choose between two engineering methodologies:
1. Drive ES PCS 7 Add-on Library (Automated Integration)
Siemens offers the commercial Drive ES PCS 7 software package containing specialized function blocks (e.g., DRIVE, FbDrive, and APL integration blocks) and pre-built WinCC faceplates. It provides automated driver generation in @ charts, acyclic fault buffer uploading, and parameterization via SIMATIC Manager.
2. Direct GSD / Telegram Integration (Zero-License Cost)
When Drive ES licenses are unavailable or when maintaining legacy projects (e.g., PCS 7 V6.1 / V7.x), engineers can integrate SINAMICS G120 drives directly using the manufacturer GSD file:
* Standard PROFIdrive telegrams (Telegram 1, 20, or 352) are assigned directly in HW Config.
* Cyclic control and status words are mapped to standard peripheral input/output words (PIW/PQW).
* A simple SCL or CFC wrapper converts APL motor commands into standard PROFIdrive bit patterns.
Structure of Standard Telegram 352 (6 PZD / 6 PZD)
Telegram 352 is the most widely utilized telegram for variable-speed process drives because it provides essential operating parameters without consuming excessive bus bandwidth:
- Setpoint Channel (AS -> Drive, 6 Words Output):
1.PZD1: Control Word 1 (STW1) - 16 boolean command bits.
2.PZD2: Main Speed Setpoint (NSOLL_A) - 16-bit signed integer (16#4000= 100% rated speed).
3.PZD3toPZD6: User-assignable process control words (e.g., torque limits, external faults). - Feedback Channel (Drive -> AS, 6 Words Input):
1.PZD1: Status Word 1 (ZSW1) - 16 boolean feedback bits.
2.PZD2: Actual Speed Feedback (NIST_A) - 16-bit signed integer.
3.PZD3: Actual Motor Current (IACT).
4.PZD4: Actual Motor Torque (M_ACT).
5.PZD5: Active Warning Code (WARN_CODE).
6.PZD6: Active Fault Code (FAULT_CODE).
PROFIdrive Control Word 1 (STW1) and Sequence Logic
To start and stop a SINAMICS drive conforming to the PROFIdrive profile, the control word must follow a strict state transition sequence:
- Static Enable Mask (
16#047E):
* Bit 1 (No Coast Stop /OFF2): Must be1.
* Bit 2 (No Quick Stop /OFF3): Must be1.
* Bit 3 (Enable Operation): Must be1.
* Bit 4 (Enable Ramp Generator): Must be1.
* Bit 5 (Continue Ramp Generator): Must be1.
* Bit 6 (Enable Speed Setpoint): Must be1.
* Bit 10 (Control by PLC): Must be1(mandatory16#0400to indicate mastership).
* Bit 0 (ON/OFF1): Remains0.
* The drive is now in 'Ready to Switch On' state. - Start Command (
16#047F):
* Toggling Bit 0 from0to1assertsON/OFF1.
* The drive main contactor/inverter energizes and accelerates to setpoint according to its internal ramp rate. - Stop Command (
16#047E):
* Toggling Bit 0 back to0executes anOFF1controlled ramp-down to standstill.
CFC Interfacing: Connecting Standard APL Blocks to Peripheral I/O
In CFC, a standard APL motor block such as MotSpdCL (Speed-controlled motor) can be connected to the G120 without custom driver packages:
- Command Word Assembly:
Use an SCL block or logic gates to combineMotSpdCL.Startwith the static enable mask:
pascal IF MotSpdCL.StartAut THEN Output_STW1 := 16#047F; ELSE Output_STW1 := 16#047E; END_IF; - Speed Setpoint Normalization:
Scale the floating-point speed setpoint (MotSpdCL.SpdAut, 0.0 to 100.0%) to standard PROFIdrive integer units:
NSOLL_A := REAL_TO_INT(SpdAut * 163.84);(where100.0% * 163.84 = 16384 = 16#4000). - Output Routing:
RouteOutput_STW1toPQW xandNSOLL_AtoPQW x+2viaPcs7AnOuchannel blocks. - Feedback Parsing:
ReadPIW y(Status Word) and extract Bit 2 (Operation Enabled= Running feedback) to feedMotSpdCL.FbkRun.
Telegram 352 Parameter and Bit Assignment Matrix
The following table outlines the Telegram 352 structure, scaling factors, and bit functions:
STW1 / ZSW1NSOLL_A / NIST_A16#4000 (16384) = 100% rated motor RPMIACT16#4000 = 100% drive rated currentM_ACT16#4000 = 100% rated motor torqueWARN_CODEFAULT_CODEImplementing standard telegram structures preserves full drive diagnostics without requiring proprietary software options.
Verification
To verify direct G120 communication in CFC:
1. In HW Config online, verify that the SINAMICS G120 slave indicates 'Normal' on PROFIBUS.
2. In CFC test mode, assert a start command from MotSpdCL; verify that the outgoing control word transitions to 16#047F.
3. Confirm that the drive display shows 'RUN' and that motor speed accelerates to setpoint.
4. Verify that PIW y+2 returns the actual speed (e.g., 8192 for 50% speed) and that IACT registers actual motor amperage.
5. In WinCC, verify that the motor faceplate displays running status and dynamic speed feedback.
Limitations and Operational Precautions
- Direct peripheral addressing bypasses the automated CFC Driver Generator; hardware faults (e.g., bus disconnect) must be monitored via SFC 51 (
RDSYSST) and wired toMotSpdCL.CSF. - Bit 10 of
STW1('Control by PLC') must always be asserted (1); if Bit 10 drops to0, the drive ignores all PLC speed setpoints and commands. - Ensure drive parameter
p2000(Reference frequency / speed) in STARTER matches the maximum engineering scaling used in CFC. - Always validate final license quantities, module availability, and MLFBs against the applicable Siemens catalog and authorized distributor quotation.
Engineer FAQ
Why does the drive not start even though Bit 0 is ON?
PROFIdrive requires an edge transition on Bit 0 (0 -> 1). Furthermore, Bits 1, 2, 3, and 10 must already be 1. If Bit 10 is 0, the drive rejects the start command entirely.
Can I reset a drive fault without Drive ES?
Yes. Toggling Bit 7 of STW1 from 0 -> 1 pulses the fault acknowledge line, clearing transient inverter trip conditions over PROFIBUS.
What is the difference between Telegram 20 and Telegram 352?
Telegram 20 provides 2 PZD words output and 6 PZD words input (fixed monitoring), whereas Telegram 352 provides 6 PZD words bidirectional, allowing torque limiting setpoints.
Technical References
- SINAMICS G120 with Control Units CU240B/E-2 Operating Instructions
- Siemens Industry Online Support Entry 35934076: Commissioning CU230P-2 DP with PROFIBUS
- SIMATIC Process Control System PCS 7 Advanced Process Library Manual (MotSpdCL)
Related Articles
- How to Integrate Third-Party Field Hardware into SIMATIC PCS 7 Without Standard Module Drivers
- How to Configure and Troubleshoot APL MotSpdCL Speed Control Blocks in PCS 7
- Understanding PROFIdrive Profiles and Control Word Sequencing in SIMATIC Systems