How to Troubleshoot Project Archive and Retrieval Failures in SIMATIC PCS 7
In SIMATIC PCS 7 V8.1, project archiving or retrieval ('Unarchive') failures displaying 'Impossible to open the project' or stalling mid-archive typically occur due to three issues: (1) Windows file path lengths exceeding the 255-character API limit when archived to the Desktop or deeply nested folders, (2) read-only file attributes or insufficient NTFS permissions on the project directory, or (3) internal database inconsistencies caused by orphaned file locks (.lck). To resolve this, archive projects directly to root directory paths (e.g., C:\Archives), remove the read-only flag from the project folder in Windows Explorer, execute 'Save As with Reorganization (Slow)' to repair internal tables, or extract the ZIP file using standard decompression utilities.
Table of Contents
- SIMATIC Manager Archiving Architecture: PKZip Engine and Path Limits
- Root Causes of 'Impossible to Open the Project' During Retrieval
- Resolving Windows Path Length Violations and Desktop Traps
- Purging Read-Only Attributes and Repairing Databases via Reorganization
- Comparison of Project Backup and Extraction Utilities
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
SIMATIC Manager Archiving Architecture: PKZip Engine and Path Limits
In SIMATIC PCS 7, multi-project backup and transfer is managed by the integrated archiving engine (File > Archive... and File > Retrieve...):
* Internal Decompression Engine: SIMATIC Manager utilizes an embedded PKZip-compatible algorithm to compress multi-project folders, S7 programs, and WinCC SQL databases into a single .zip file.
* The 255-Character Path Limit (MAX_PATH):
* Windows Win32 file APIs impose a maximum path limitation of 255 characters.
* A PCS 7 multi-project contains deeply nested subdirectories (e.g., \wincproj\OS(1)\GraCS\@pg_@vlv_standard.pdl).
* If an engineer archives or retrieves the project to a user's Desktop:
* Path prefix: C:\Users\ExtremelyLongUserName\Desktop\CustomerProjectFolder\...
* The combined character count rapidly exceeds 255 characters, causing the extraction engine to crash mid-stream and leave an incomplete, unopenable project.
Root Causes of 'Impossible to Open the Project' During Retrieval
Forensic analysis reveals four distinct triggers for retrieval failures:
1. Desktop Path Overflow: Extracting directly to the Windows Desktop or My Documents folder.
2. Read-Only Attribute Flag: Copying an archive from a CD/DVD or USB backup drive frequently marks all extracted files with the Windows Read-only attribute. SIMATIC Manager requires full write access to database files and blocks project opening.
3. Corrupted Archive File: Network dropouts during file transfer or incomplete compression left the .zip archive truncated.
4. Active Database File Locks: Attempting to archive while SIMATIC Manager, WinCC Explorer, or background processes (s7oemax.exe) hold open file handles.
Resolving Windows Path Length Violations and Desktop Traps
To eliminate path length violations:
- Create Short Root Directory:
* Create dedicated top-level directories on driveC:\orD:\:C:\Archives\(for storing compressed ZIP files)C:\Projects\(for extracting and working on active projects)
- Execute Retrieve to Short Path:
* In SIMATIC Manager, selectFile > Retrieve....
* Browse to the archive inC:\Archives\.
* When prompted for destination directory, selectC:\Projects\.
* By keeping the base path under 15 characters, nested WinCC and CFC files remain safely below the 255-character threshold.
Purging Read-Only Attributes and Repairing Databases via Reorganization
If the project folder was copied from an external drive and refuses to open:
- Clear Read-Only Flag in Windows Explorer:
* Open Windows Explorer: navigate toC:\Projects\.
* Right-click the multi-project folder: selectProperties.
* Under the General tab, locateAttributes:
* Uncheck theRead-onlycheckbox.
* Click Apply. In the confirmation dialog, choose:Apply changes to this folder, subfolders and files.
* Click OK. - Execute Project Reorganization:
* Open the project in SIMATIC Manager.
* SelectFile > Save As....
* CheckWith reorganization (slow).
* Choose a new folder name:C:\Projects\Project_Repaired.
* This aligns internal relational tables and purges orphaned pointer gaps.
Comparison of Project Backup and Extraction Utilities
The table below compares backup and extraction tools for SIMATIC PCS 7 multi-projects.
File > Retrieve)Verification
To confirm that the project archive is healthy and unarchives cleanly:
1. In SIMATIC Manager, execute File > Retrieve... targeting C:\Projects\.
2. Verify that the extraction progress bar advances to 100% without throwing file access or path length errors.
3. When prompted 'Do you want to open the project now?', click Yes.
4. Confirm that the multi-project tree opens completely, displaying all AS stations, OS servers, and master data libraries.
5. Open HW Config, CFC charts, and WinCC Explorer: confirm that all editors open cleanly without database context or missing component warnings.
Limitations and Operational Precautions
- Never extract or work on active PCS 7 projects stored on mapped network drives (e.g.,
Z:\), USB flash drives, or cloud-synced folders (Dropbox / OneDrive); latency and file locks can permanently corrupt database tables. - Always close SIMATIC Manager before compressing a project manually with 7-Zip or WinRAR to avoid capturing locked, inconsistent files.
- Ensure that the target engineering station possesses software licenses and version service packs equal to or newer than the station where the archive was generated.
- Always validate final software licensing and system documentation against the applicable Siemens catalog and authorized distributor quotation.
Engineer FAQ
Can I extract a PCS 7 archive using 7-Zip or WinRAR?
Yes. PCS 7 .zip archives are standard ZIP files. You can right-click the file and extract it using 7-Zip directly into C:\Projects\, then open the .s7p or .mcp file via File > Open in SIMATIC Manager.
Why did the archive stop at 80% with an error?
The archiving engine encountered a locked file (typically a running WinCC SQL database or an unclosed block editor) or ran out of disk space on the target drive.
Can I open a PCS 7 V8.1 project in PCS 7 V7.1?
No. SIMATIC projects are strictly backward-incompatible; an archive created in PCS 7 V8.1 cannot be retrieved or opened on a PCS 7 V7.1 engineering station without version upgrade.
Technical References
- SIMATIC Process Control System PCS 7 Engineering System Manual
- Siemens Industry Online Support FAQ: Archiving and Retrieving STEP 7 Projects
- Siemens Industry Online Support: Troubleshooting Long File Paths in Windows
Related Articles
- How to Perform Complete System Backups, Parameter Readbacks, and Version Trail Archiving in SIMATIC PCS 7
- How to Fix Error 256 -72 'Unable to Close Table YDBS-YLinklist' During Project Reorganization in SIMATIC STEP 7
- How to Resolve WinCC Database Context Errors and User Rights During ES to OS Project Download
Related Tags
- Archiving
- Retrieval
- Path Length Limit
- Read-Only
- Multi-Project