How to Troubleshoot WinCC Error While Opening the Project: Unspecified on OS Clients
The error 'Error while opening the project: Unspecified' on SIMATIC WinCC V7.5 SP2 and PCS 7 V9.1 OS Clients occurs when the client station is unable to establish an authenticated Microsoft SQL Server connection, attach the remote project runtime database (*.mdf), or resolve Server Message Block (SMB) network shares. In multi-user domain environments running Windows Server 2019 and Windows 10, this intermittent failure is primarily triggered by stopped SQL Server Browser services, asymmetric Active Directory reverse DNS lookups, or Windows power management placing client network interface cards into sleep mode. To resolve this error without rebooting the server, verify network adapter power management, confirm bidirectional hostname resolution, restart the SQL Server (WINCC) and SQL Server Browser services, and regenerate client database binding files.
Table of Contents
- Root Cause Analysis: Why OS Clients Fail with 'Unspecified Error'
- Active Directory Domain and DNS Resolution Discrepancies
- Network Adapter Power Management and Energy Efficient Ethernet
- Method: Step-by-Step Diagnostic and Recovery Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Root Cause Analysis: Why OS Clients Fail with 'Unspecified Error'
In a PCS 7 multi-user client-server architecture, an OS Client does not run a standalone process control database. When an operator opens a client project (*.mcp), WinCC initiates a complex initialization sequence:
1. Network Discovery: The client uses Simatic Shell to verify server availability via UDP Port 5227.
2. File Sharing (SMB): The client attaches to the server's shared project directory (<ProjectName>.WinCC).
3. Database Connection: The client contacts the Microsoft SQL Server instance on the server (WINCC) via TCP Port 1433 and SQL Browser (UDP Port 1434) to query runtime archives and process tags.
If any link in this authentication and network chain breaks, the WinCC client runtime initialization engine (CCClient.exe) throws a generic catch-all exception:
Error while opening the project: Unspecified.
Active Directory Domain and DNS Resolution Discrepancies
In modern industrial facilities governed by Active Directory domain controllers, name resolution latency is the most common cause of intermittent client disconnects:
* Forward vs. Reverse Lookup: WinCC components strictly require that forward DNS resolution (nslookup OS_SERVER1) and reverse DNS resolution (nslookup 192.168.1.10) return identical, case-insensitive fully qualified domain names (FQDN) and NetBIOS hostnames.
* DNS Caching and Scavenging: If the domain DNS server experiences replication delays, or if dynamic DNS updates are blocked by firewall rules between the terminal bus and corporate domain controllers, reverse lookups time out.
* Simatic Shell Lockout: When a reverse lookup fails, Simatic Shell cannot verify that the incoming client belongs to the authorized Windows group SIMATIC HMI, blocking the client and causing the 'Unspecified' open error.
Network Adapter Power Management and Energy Efficient Ethernet
A widespread issue on Windows 10 OS Clients is the default operating system power-saving configuration for commercial network interface cards (NICs):
* Energy-Efficient Ethernet (EEE): Modern Intel and Realtek Gigabit NICs feature power-saving states (Green Ethernet / EEE). During idle periods (such as overnight or low-operator activity), Windows lowers the link power or enters low-power sleep states.
* Socket Severing: When link power fluctuates, the persistent TCP socket connection between the client and Microsoft SQL Server on the OS server drops without a clean TCP FIN packet.
* Ghost Locks: On the server, SQL Server retains the client's session lock. When the operator attempts to restart the client, SQL Server rejects the new session because the old connection is still marked active, producing the 'Unspecified' error until the server is rebooted.
Method: Step-by-Step Diagnostic and Recovery Procedure
To permanently resolve intermittent client disconnects and recover from the 'Unspecified' error without rebooting the server:
Step 1: Disable Network Adapter Power Management (All Clients)
- On each Windows 10 OS Client, right-click the Start menu and select Device Manager.
- Expand Network adapters, right-click the terminal bus NIC, and select Properties.
- On the Power Management tab:
- Uncheck Allow the computer to turn off this device to save power. - On the Advanced tab:
- Disable Energy Efficient Ethernet, Green Ethernet, and Gigabit Lite.
- Set Energy Saving Mode to Disabled.
Step 2: Verify and Restart Server SQL Services
Instead of rebooting the production OS Server, restart the specific WinCC communication daemons:
1. On the OS Server, open services.msc.
2. Locate and inspect the following services:
- SQL Server (WINCC): Must be Running (Automatic).
- SQL Server Browser: Must be Running (Automatic).
3. If client connections are locked, right-click SQL Server Browser and select Restart.
4. Ensure the Windows service Workstation and Server (SMB file sharing) are operating normally.
Step 3: Enforce Local LMHOSTS Name Resolution
To prevent domain DNS timeouts from crashing Simatic Shell:
1. On all servers and clients, open C:\Windows\System32\drivers\etc\hosts and lmhosts with administrative privileges.
2. Add static IP and hostname entries for all servers, redundant partners, and clients:
text
192.168.1.10 OS_SRV1 #PRE
192.168.1.11 OS_SRV2 #PRE
192.168.1.20 OS_CLI1 #PRE
3. Open a command prompt and execute nbtstat -R to purge and reload the NetBIOS cache.
Step 4: Regenerate Client Project Binding Cache
If a specific client remains blocked:
1. On the OS Client, close all WinCC applications.
2. In Windows Explorer, navigate to the local client project directory.
3. Locate and delete the file <ProjectName>.dcf.
4. Relaunch WinCC Explorer and open the project. WinCC will automatically regenerate a clean .dcf database cache file.
Verification
To verify that the multi-user client connection is fully restored:
- Open a command prompt on the client and execute:
cmd ping OS_SRV1 -f -l 1472
Confirm zero packet loss and latency under 1 ms without packet fragmentation. - Open Simatic Shell in Windows Explorer on the client. Verify that all OS servers appear with blue computer icons. Right-click the server project and select Open.
- Verify that the client project opens immediately without displaying 'Error while opening the project: Unspecified'.
- Confirm that WinCC Graphics Runtime activates and displays live process values.
Limitations and Operational Precautions
- Do Not Restart Active Server During Plant Operation: While restarting SQL services resolves client locks, restarting
SQL Server (WINCC)on an active single server will interrupt SCADA data collection. On redundant server pairs, execute service maintenance on the standby server first. - Domain Controller Dependencies: If the industrial network domain controller fails or reboots, Kerberos authentication tickets expire. Ensure primary and secondary domain controllers are deployed on the industrial network.
- Windows Update Freezes: Ensure Windows 10 OS Clients do not execute uncontrolled background updates that reset network adapter driver properties to default power-saving states.
Engineer FAQ
Why does rebooting the OS server always temporarily fix the issue?
Rebooting the server terminates all hung SQL Server database locks, flushes orphaned network sessions, and forces the SQL Server Browser daemon to rebind to network interfaces.
Can an incorrect Simatic Shell network adapter selection cause this error?
Yes. If Simatic Shell on either the server or client is bound to the wrong network adapter (e.g., an unused secondary NIC or virtual adapter), broadcast discovery fails and triggers the error.
What user permissions are required to prevent this error?
All domain users logging into WinCC clients must be members of the local SIMATIC HMI group on both the local client PC and the remote OS Server.
Technical References
- Siemens Industry Online Support Entry ID 109742323: SIMATIC Process Control System PCS 7 OS Process Control Manual
- Siemens Industry Online Support Entry ID 109809264: WinCC Client-Server Communication and Name Resolution Guidelines
- SIMATIC HMI WinCC V7.5 SP2 Communication Manual (Document No. 6AV6392-1CA07-5AA0)
Related Articles
- https://industrialautomation.net/search?query=wincc+error+opening+project+unspecified
- https://industrialautomation.net/search?query=pcs7+client+sporadic+disconnect+sql+server
- https://industrialautomation.net/search?query=simatic+shell+network+adapter+power+saving
Related Tags
- https://industrialautomation.net/search?query=simatic+wincc
- https://industrialautomation.net/search?query=pcs7+v9.1
- https://industrialautomation.net/search?query=client-server
- https://industrialautomation.net/search?query=sql-server