Integrating Danfoss VLT Frequency Converters into SIMATIC PCS 7: APL FbDrive and MotSpdL Implementation
To integrate Danfoss variable frequency drives (such as VLT FC 202 or FC 302 with MCA 101 PROFIBUS or MCA 120 PROFINET) into SIMATIC PCS 7, configure the drive in HW Config using Standard Telegram 1 (or Telegram 20) and connect it in CFC using the standard APL channel block FbDrive (FB1881) paired with MotSpdL (FB1856). In HW Config, install the Danfoss GSD/GSDML file and assign matching input/output addresses. In CFC, connect the drive's first process data word (PZD1 / LAddr) to FbDrive; the PCS 7 driver generator automatically interconnects module diagnostics during compilation, providing speed setpoint control, status monitoring, and faceplate visualization.
Table of Contents
- Fieldbus Architecture for Third-Party Variable Frequency Drives
- Danfoss MCA 101/120 Communication Profiles: Standard Telegram 1 vs 20
- APL Driver Concept: Pairing FbDrive (FB1881) with MotSpdL (FB1856)
- Automated Driver Generation and Address Interconnection Rules
- Danfoss Integration Specification and Telegram Parameter Matrix
- Step-by-Step CFC Configuration and Engineering Workflow
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Fieldbus Architecture for Third-Party Variable Frequency Drives
In industrial facilities automated with SIMATIC PCS 7, third-party variable speed drives—such as Danfoss VLT AQUA Drive (FC 202) or AutomationDrive (FC 302)—frequently control centrifugal pumps, mixers, and conveyor belts. To incorporate these drives into the high-availability DCS environment, communications are established over PROFIBUS DP (using Danfoss MCA 101 interface cards) or PROFINET IO (using Danfoss MCA 120 interface cards).
Rather than writing custom communication ladders or STL pointers, PCS 7 engineers utilize standard Advanced Process Library (APL) technological blocks designed to interface PROFIdrive-compliant equipment directly.
Danfoss MCA 101/120 Communication Profiles: Standard Telegram 1 vs 20
The Siemens APL channel block FbDrive (FB1881) is strictly engineered to evaluate standardized PROFIdrive telegram types:
- Standard Telegram 1: Transfers 2 Process Data Words (PZD) input and 2 PZD output (4 bytes each):
- Setpoint Telegram (AS to Drive): PZD1 = Control Word (STW1), PZD2 = Speed Reference (
NSOLL_A). -
Actual Telegram (Drive to AS): PZD1 = Status Word (ZSW1), PZD2 = Actual Speed (
NIST_A). -
Standard Telegram 20: Standard VIK-NAMUR telegram, transmitting 2 PZD output and 6 PZD input (including fault codes and motor current).
In the Danfoss drive parameter setup, configure parameter 8-10 (Control Word Profile) to PROFIdrive standard to ensure bit-level compatibility with Siemens command words.
APL Driver Concept: Pairing FbDrive (FB1881) with MotSpdL (FB1856)
APL enforces an object-oriented two-tier block hierarchy for speed-controlled motors:
-
Channel Block (
FbDrive): Interfaces directly with physical fieldbus I/O addresses. It scales raw frequency integers (0–16384 hex4000H= 100% nominal speed) into percentage or engineering units, extracts drive trip codes, and generates diagnostic quality codes. -
Technological Block (
MotSpdL): Implements operating modes (Manual, Automatic, Local), ramp rate limits, interlock evaluation (Intlock,Protect,Permit), operator faceplates, and trending.
MotSpdL interconnects directly to FbDrive: control commands feed FbDrive.SP_Out and FbDrive.Fwd, while drive feedback routes to MotSpdL.Rbk and MotSpdL.FbkRun.
Automated Driver Generation and Address Interconnection Rules
During CFC compilation with the option 'Generate module drivers' enabled:
- The PCS 7 Driver Generator inspects the logical base address connected to
FbDrive.PZDIn1(orLAddr). - It identifies the Danfoss GSD slave from HW Config, verifies DP master diagnostics, and automatically instantiates helper blocks (
MOD_PAL0/MOD_D1) in chart@(1). - These diagnostic blocks continuously poll the health of the Danfoss communication card, setting
FbDrive.Bad = 1if the PROFIBUS connector is pulled or if the drive loses line power.
Danfoss Integration Specification and Telegram Parameter Matrix
The following table summarizes communication mapping between Danfoss VLT drives and PCS 7 APL blocks:
STW1)CtrlWordMotSpdL.Start / MotSpdL.StopNSOLL_A)SP_Li (via MotSpdL)MotSpdL.SP_OutZSW1)Status1MotSpdL.FbkRun / MotSpdL.TripNIST_A)ActSpdMotSpdL.Rbk (Readback)DiagWordMOD_PAL0 / FbDriveStep-by-Step CFC Configuration and Engineering Workflow
Follow this sequence to commission a Danfoss drive in PCS 7:
- Install Danfoss GSD File: Download the official GSD/GSDML file from Danfoss for MCA 101/120. In HW Config, install via Options -> Install GSD Files.
- Add Slave to HW Config: Drag the Danfoss drive onto the PROFIBUS DP master line. Insert Standard Telegram 1 into slot 1. Assign matching start addresses (e.g. Input
IW 512, OutputQW 512) in Process Image Partition 1 (TPA 1). - Configure Drive Parameters: On the drive LCP keypad, set parameter
8-10 = PROFIdrive,8-01 = Digital and control word, and verify bus baud rate. - Place Blocks in CFC: Insert
FbDrive(FB1881) andMotSpdL(FB1856) into a cyclic interrupt chart (OB35). - Interconnect Channel Block: Connect physical input
IW 512toFbDrive.PZDIn1. InterconnectFbDriveandMotSpdLcontrol/feedback pins. - Compile Charts and OS: Compile CFC charts with Generate module drivers. Compile WinCC OS.
- Runtime Operation: Open WinCC Runtime; test starting, stopping, speed ramping, and faceplate alarms.
Verification
Verify drive integration through these diagnostic tests:
- CFC Test Mode Online Check: Confirm
FbDrive.Bad = 0andActSpdreflects zero when stopped. - Start and Speed Reference Test: In manual mode on the
MotSpdLfaceplate, click Start and set 50% speed. Verify motor accelerates to half speed. - Readback Verification: Verify
MotSpdL.Rbkreads50.0%matching the physical shaft tachometer. - Bus Interruption Test: Unplug the PROFIBUS DP connector. Verify
FbDrive.Badtransitions to1, generating a drive communication fault alarm in WinCC.
Limitations and Operational Precautions
Observe the following operational constraints:
-
Telegram 1 Limitations: Standard Telegram 1 only passes 2 words each way; it does not transmit motor current (Amperes) or power (kW). If current monitoring is required, configure Standard Telegram 20 or use acyclic DP-V1 reading via
RDREC. -
Control Word Profile Selection: If parameter
8-10on the Danfoss drive is accidentally left in 'FC Profile' mode, bit mapping differs and the drive will refuse to start viaFbDrive. -
Commercial Accuracy Disclaimer: Software order numbers (MLFBs), package structures, and hardware capacity prerequisites vary across PCS 7 versions and hardware platforms. System integrators must confirm exact software entitlements and licensing requirements against the official Siemens Catalog CA 01 and obtain an authorized Siemens distributor quotation prior to purchasing.
Engineer FAQ
Do I need to interconnect all PZD words manually in CFC for FbDrive?
No. Interconnecting the first process input address (PZDIn1) is sufficient; the PCS 7 Driver Generator handles module diagnostic linkage automatically during chart compilation.
Is a separate Siemens library license required for third-party drives?
Using native APL blocks FbDrive and MotSpdL requires no extra software licenses; however, Siemens Industry Services sells optional dedicated third-party drive libraries with custom faceplates.
Can Danfoss drives communicate via PROFINET with FbDrive?
Yes. Danfoss MCA 120 PROFINET cards configured with Standard Telegram 1 or 20 interface with FbDrive identically to PROFIBUS.
Technical References
- Siemens Industry Online Support (SIOS) Application Guide: Configuring Frequency Converters with FbDrive (Entry ID: 68154057)
- SIMATIC PCS 7 Advanced Process Library (APL) Function Manual (Entry ID: 109746516)
- Danfoss VLT PROFIBUS DP MCA 101 Installation and Operating Instructions (Entry ID: 109740190)
- PROFIdrive Profile Drive Technology Technical Specification V4.1 (Entry ID: 109751825)
Related Articles
- Configuring Pre-Start Warning Alarms on SIMOCODE pro V with APL MotL and FbSwtMMS in SIMATIC PCS 7
- Detecting Automatic Mode in CEMAT Drive Blocks (C_DRV_1D)
- Displaying Motor Current Percentage in CEMAT C_DRV_1D Faceplates