Integrating SIMATIC S7-1200 Controllers into PCS 7 via S7 Communication and Open OS

Integrating SIMATIC S7-1200 Controllers into PCS 7 via S7 Communication and Open OS

SIMATIC S7-1200 basic controllers cannot be configured or programmed directly inside SIMATIC PCS 7 CFC, as they do not belong to the qualified PCS 7 automation system family. To integrate an S7-1200 into a PCS 7 plant, establish peer-to-peer S7 Communication between the S7-400 and S7-1200 using an Unspecified S7 Connection with PUT/GET (SFB14/SFB15) or BSEND/BRECV blocks, configure PROFINET I-Device coupling via GSDML, or integrate the controller into the PCS 7 OS using SIMATIC PCS 7 Open OS.

Table of Contents

Architectural Boundary Between S7-1200 (TIA Portal) and PCS 7

In process automation facilities operating SIMATIC PCS 7, auxiliary package units (skids, vendor packages, chiller units, or small water treatment skids) are frequently equipped with SIMATIC S7-1200 basic controllers (such as CPU 1214C MLFB 6ES7214-1AG40-0XB0 or CPU 1215C MLFB 6ES7215-1AG40-0XB0).

A fundamental engineering boundary exists between these platforms:
1. PCS 7 Ecosystem: Programmed and maintained exclusively within STEP 7 V5.x, CFC, SFC, and the Advanced Process Library (APL) running on S7-400 / S7-410 controllers. S7-1200 hardware cannot be inserted into the PCS 7 hardware catalog or programmed via CFC.
2. S7-1200 Ecosystem: Configured and programmed exclusively within TIA Portal (Totally Integrated Automation Portal) using LAD, FBD, or SCL.

To integrate S7-1200 process data, alarms, and control interlocks into the main PCS 7 DCS, automation engineers must implement deterministic cross-platform communication architectures without compromising the integrity of the process control system.

Integration Architecture Comparison Matrix

Evaluate the three standard methods for integrating S7-1200 data into a PCS 7 architecture:

Integration TopologyCommunication ProtocolConfiguration ToolsData Exchange CharacteristicsRecommended Plant ApplicationS7 Communication (PUT/GET)S7 Protocol / ISO-on-TCP (RFC 1006)NetPro (PCS 7) & TIA PortalAsynchronous block transfer via DBs; up to 160 bytes per telegramGeneral parameter exchange, skid status monitoring, setpoint transferPROFINET I-Device CouplingDeterministic PROFINET IO (RT)GSDML Export in TIA -> HW ConfigDeterministic cyclic I/O mirror (1-10 ms); direct peripheral addressingHigh-speed safety interlocks, fast digital trips, continuous analog loopsSIMATIC PCS 7 Open OSWinCC Channel / OPC / S7 ProtocolOpen OS Component ConfiguratorDirect integration of S7-1200 into WinCC with APL-like faceplatesComprehensive skid visualization with centralized operator controlsPROFIBUS-DP Slave (CM 1242-5)PROFIBUS DP-V1GSD file in HW ConfigDeterministic cyclic slave communication up to 12 MbpsLegacy plants lacking Industrial Ethernet plant bus extensions

Procurement and hardware notice: S7 communication requires no additional hardware; PROFIBUS coupling requires communication module CM 1242-5 (6GK7242-5DX30-0XE0). Always verify specifications with authorized Siemens distributors.

Configuring Peer-to-Peer S7 Communication (PUT/GET) in NetPro and TIA Portal

Follow this verified procedure to establish bilateral data exchange using S7 communication:

  1. Configure S7-1200 in TIA Portal:
    * Open the S7-1200 project in TIA Portal.
    * Open CPU Device Configuration > Properties > Protection & Security > Connection Mechanisms.
    * Mandatory: Check the box: Permit access with PUT/GET communication from remote partner.
    * Create dedicated send and receive Data Blocks (e.g., DB100_SendToPCS7 and DB101_RecvFromPCS7).
    * In DB properties, uncheck Optimized Block Access (configure as standard S7-300/400 compatible DB structure).
  2. Configure Unspecified S7 Connection in NetPro (PCS 7):
    * On the PCS 7 Engineering Station, open NetPro.
    * Select the S7-400 CPU, right-click, and select Insert New Connection.
    * Connection Partner: Unspecified. Connection Type: S7 connection.
    * In Connection Properties:
    • Enter the IP address of the S7-1200 CPU.
    • Partner TSAP: Set to 03.01 (Rack 0, Slot 1 for S7-1200).
    • Local TSAP: Defaults to S7-400 CPU handle (e.g., 10.02).
    • Save and compile NetPro, then download network configuration to S7-400 in STOP or via CiR.
  3. Instantiate PUT/GET Blocks in S7-400 CFC:
    * Place PUT (SFB14) and GET (SFB15) into a cyclic CFC chart (OB 35).
    * Assign input ID to the connection ID generated in NetPro (e.g., W#16#0001).
    * Parameterize ADDR_1 pointing to the remote S7-1200 DB address (P#DB100.DBX0.0 BYTE 64).
    * Parameterize RD_1 / SD_1 pointing to the local S7-400 DB buffers.
    * Trigger the communication blocks with a 500 ms clock pulse.

Integrating S7-1200 into PCS 7 OS Using SIMATIC PCS 7 Open OS

If the S7-1200 package unit must be operated directly from PCS 7 WinCC OS stations:
1. In TIA Portal, export the S7-1200 tag and alarm data using the DB export utility.
2. In PCS 7, launch the SIMATIC PCS 7 Open OS configurator.
3. Import the tag mapping file to automatically generate WinCC tags, messages, and APL-style block icons for third-party packages.
4. Compile the OS to instantiate the package unit graphics within the PCS 7 Picture Tree navigation.

Verification

Verify cross-platform data exchange:
1. Online in TIA Portal: Force a known value (e.g., 123.45) in DB100_SendToPCS7.TestValue.
2. Online in PCS 7 CFC: Monitor the output of GET (SFB15); confirm that the data buffer registers 123.45 with output NDR = 1 (New Data Received) and ERROR = 0.
3. In S7-400 CFC: Write an integer command (e.g., 16#00FF) into PUT (SFB14); verify that the remote S7-1200 updates DB101_RecvFromPCS7 within 100 milliseconds.

Limitations and Operational Precautions

  • S7-1200 controllers do not support high-availability S7-REDCONNECT fault-tolerant connections; connecting an S7-1200 to an S7-400H cluster requires binding communication to a single CP or implementing dual independent connection logic.
  • Never enable PUT/GET communication across public corporate networks without industrial firewall protection (e.g., SCALANCE S615 6GK5615-0AA00-2AA2), as legacy S7 communication lacks cryptographic encryption.
  • S7-1200 standard CPUs do not support deterministic sequence of events (SOE) 1 ms timestamping within PCS 7.

Engineer FAQ

Can I program the S7-1200 using PCS 7 CFC Editor?

No. S7-1200 micro-architecture is incompatible with CFC and STEP 7 V5.x. All controller logic must be authored in TIA Portal.

Why does PUT/GET return error code 16#0001 or 16#0004?

Error 16#0001 indicates a communication timeout or invalid connection ID. Error 16#0004 indicates access violation, typically because 'Permit access with PUT/GET' was not enabled in S7-1200 CPU properties or the DB was configured with 'Optimized Block Access'.

Does S7-1200 integration consume PCS 7 Process Objects (PO)?

If data is routed through S7-400 CFC blocks (e.g., MotL, OpAnL), those CFC blocks consume AS RT Process Objects. If connected directly to WinCC via Open OS, only OS runtime tags are consumed.

Technical References

Related Articles

Related Tags

  • S7-1200
  • PCS 7 Integration
  • S7 Communication
  • PUT/GET
  • SFB14
  • Open OS
  • TIA Portal
  • NetPro