Interconnecting Technological Blocks (CountOh) to SelFp1 on APL Motors in SIMATIC PCS 7
In SIMATIC PCS 7 Advanced Process Library (APL), connecting an auxiliary block like CountOh (Operating Hours) to the SelFp1 input of a motor (MotL) enables a direct 'Block Jump' navigation button on the motor faceplate. Because SelFp1 is an ANY pointer evaluated during OS compilation to resolve the partner block's instance name, any valid technological output pin (such as CountOh.Out or CountOh.HoursOut) can be connected.
Table of Contents
- The APL Block Jump Concept and Navigation Architecture
- Technical Role of the SelFp1 ANY Pointer Input
- Step-by-Step Interconnection and OS Compilation Procedure
- Auxiliary Technology Block and Faceplate Jump Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
The APL Block Jump Concept and Navigation Architecture
In modern process plant operations running SIMATIC PCS 7 Advanced Process Library (APL), operator efficiency depends on seamless navigation between related control objects without cluttering the screen with multiple open windows.
When an operator opens a motor faceplate (e.g. MotL for a pump or compressor), they frequently need access to related operational equipment:
* The Operating Hours and Maintenance Counter (CountOh) to view runtime hours, switching cycle counts, and upcoming maintenance schedules.
* A Dosing or Flow Measurement Block (CountScL or TotalL) tracking accumulated throughput.
* An auxiliary temperature or vibration monitoring block (MonAnL).
To accommodate this, Siemens APL incorporates the Block Jump architecture. Technological blocks provide dedicated input parameters—named SelFp1 and SelFp2 (Select Faceplate 1 and 2)—that generate navigation pushbuttons directly on the standard motor faceplate toolbar in WinCC Runtime. Clicking this button immediately opens the faceplate of the interconnected technological block.
Technical Role of the SelFp1 ANY Pointer Input
Beginner PCS 7 engineers frequently debate which specific output parameter of CountOh must be wired to SelFp1 (e.g., Ms_Release, Out, HoursOut, or DayCntOut):
-
Evaluation During OS Compilation:
* The parameterSelFp1has data typeANYin the AS block interface.
*SelFp1is not used for cyclic mathematical processing inside the controller. The motor block does not calculate operating hours or modify its speed based on this input.
* Instead, during Compile OS, the WinCC OS compiler parses the CFC chart database, traces the textual/block interconnection attached toSelFp1, and extracts the chart name and block instance name of the connected partner. -
Any Valid Output Pin Functions Correctly:
* Because the OS compiler extracts the block identity from the pointer structure, any valid technological output pin on the target block satisfies the jump requirement.
* ConnectingCountOh.Out,CountOh.HoursOut, orCountOh.Ms_ReleasetoMotL.SelFp1yields the identical runtime behavior: the motor faceplate generates a jump button leading directly toCountOh. -
Engineering Best Practice Recommendation:
* While technically any pin works, standard engineering best practice dictates connectingCountOh.OutorCountOh.HoursOut.
* Connecting the primary technological output maintains visual clarity in CFC charts, making it immediately evident to reviewing engineers that the two blocks are functionally paired.
Step-by-Step Interconnection and OS Compilation Procedure
1. Instantiate the Operating Hours Block in CFC
- Open the CFC chart containing your motor block (
MotL). - From the APL Library, drag and drop
CountOh(FB1864) onto the chart. - Name the instance appropriately (e.g.
PMP_101_OH).
2. Connect Motor Run Feedback to CountOh
- Connect the motor running feedback signal (
MotL.FbkRunOutor drive feedback) to inputCountOh.In. - Configure
CountOhparameters:
*HoursLimit: Target operating hours threshold for maintenance (e.g.,5000.0hours).
*Interval: Tracking interval.
*Reset: Connect reset logic or leave available for faceplate operator commands.
3. Wire the Faceplate Jump Connection
- In the CFC chart, locate input pin
SelFp1on theMotLblock. - If
SelFp1is not visible, select theMotLblock, press Alt + Return (Object Properties), navigate to the I/Os tab, findSelFp1, and uncheck the Invisible box. - Draw a connection line from
CountOh.Out(orCountOh.HoursOut) toMotL.SelFp1.
4. Execute OS Compilation
- In SIMATIC Manager, select the OS station.
- Select PLC > Compile and Download Objects.
- Choose OS, select Scope: Changes only (or Entire project), and run compilation.
- The OS compiler generates the faceplate jump metadata in the WinCC
@internal tag tables.
5. Test in WinCC Runtime
- Activate WinCC Runtime.
- Click the motor block icon to open the
MotLfaceplate. - Observe the upper toolbar area of the faceplate: a new button showing the
CountOhsymbol appears. - Click the button; confirm the
CountOhfaceplate opens adjacent to the motor faceplate.
Auxiliary Technology Block and Faceplate Jump Matrix
SelFp1CountOhCountOh.Out or CountOh.HoursOutCountScLCountScL.OutMonAnLMonAnL.OutTotalLTotalL.OutIntlk02 / Intlk04SelFp1)Permit/Intlock inputsVerification
- Open the CFC chart; verify the interconnection line from
CountOh.OuttoMotL.SelFp1is solid and active. - Perform an OS compile; confirm compilation finishes with 0 Errors and 0 Warnings.
- Open WinCC Runtime on an OS Client or Server.
- Click the motor icon to open the standard faceplate.
- Verify the Block Jump 1 icon is illuminated in the faceplate header.
- Click the Block Jump button; verify the
CountOhfaceplate opens cleanly, showing accumulated operating hours and cycle counts.
Limitations and Operational Precautions
- Interlock Blocks Exception: Never connect interlock blocks (
Intlk02,Intlk04,Intlk08) toSelFp1. APL motor blocks have dedicated interlock inputs (Permit,Intlock,Protect) that natively generate dedicated interlock jump buttons. UsingSelFp1for interlocks wastes an auxiliary navigation slot. - Maximum Jump Buttons: Standard APL motor faceplates provide two generic jump inputs:
SelFp1andSelFp2. A maximum of two custom auxiliary faceplates can be linked via this mechanism. - OS Compilation Required: Changes to
SelFp1in CFC do not appear in WinCC Runtime until an OS compilation is executed. Online changes without OS compilation leave the jump button non-functional.
Engineer FAQ
Why is SelFp1 hidden by default on some APL blocks?
To keep CFC block displays compact, secondary parameters like SelFp1 and SelFp2 are set to 'Invisible' by default. You can make them visible via block Object Properties.
Can I connect a block located in a different CFC chart to SelFp1?
Yes. CFC supports inter-chart cross-references. Connecting SelFp1 across charts creates a sheet margin pointer, and the OS compiler will correctly resolve the remote chart and block name.
Can I customize the tooltip or label on the faceplate jump button?
Yes. The button tooltip is automatically derived from the connected block's configured OS comment or technological descriptor in CFC Object Properties.
Technical References
- SIMATIC Process Control System PCS 7 Advanced Process Library (APL) Function Manual (V8.1)
- SIMATIC Process Control System PCS 7 OS Process Control System Manual
- Siemens Industry Online Support: Faceplate Navigation and Block Jumps in APL (SIOS Entry ID 109780813)
- NAMUR NE 107 Diagnostic and Maintenance Integration in Process Automation
Related Articles
- Understanding 'Generate Module Drivers' in SIMATIC PCS 7
- Configuring Maintenance Station Basic and Standard in SIMATIC PCS 7
- APL Signal Status Propagation and Quality Code Architecture