Licensing and Network Requirements for Redundant AS Communication from Standard PCs in PCS 7
To establish plant bus communication between standard, non-Siemens commercial PCs (such as generic Engineering Stations or OS Servers) and a redundant AS controller pair (e.g., dual CPU 410-5H or S7-400H with CP 443-1) without Siemens CP 1623 communication processors, you must install the 'SOFTNET-IE S7 REDCONNECT' license on each PC station. Standard BCE (Basic Communication Ethernet), SOFTNET-IE S7 Lean, or standard SOFTNET-IE S7 licenses do not support fault-tolerant 4-way redundant S7 connections. Each PC communicating redundantly over commercial network interface cards requires its own dedicated REDCONNECT license.
Table of Contents
- Executive Summary
- Architectural and System Mechanics
- Step-by-Step Engineering and Implementation Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Executive Summary
In SIMATIC PCS 7 process plants, high-availability controllers (S7-400H / CPU 410-5H) use redundant communication paths to guarantee that no single network or CPU failure interrupts supervisory control. When deploying PCS 7 OS Servers or Engineering Stations on commercial server hardware equipped with standard network cards (NICs) rather than Siemens specialized CP 1623 / CP 1628 industrial Ethernet processors, engineers frequently wonder if basic communication licenses suffice. This article clarifies the licensing boundaries of SIMATIC NET, explains why standard BCE and SOFTNET-IE S7 cannot establish fault-tolerant S7 connections, details the SOFTNET-IE S7 REDCONNECT package, and outlines network configuration requirements.
Architectural and System Mechanics
Redundant S7 communication architecture operates under specific protocol and licensing rules:
- Fault-Tolerant S7 Connection (4-way Redundancy): In a redundant AS configuration, a single logical S7 connection consists of four underlying physical sub-connections (Subnet A/B from PC to Subnet A/B on CPU/CPs). If any single cable, switch, or controller rack fails, the connection switches transparently in milliseconds.
- HARDNET vs SOFTNET Communication:
- HARDNET-IE S7 REDCONNECT: Requires dedicated Siemens communication hardware (CP 1623 / CP 1628) with onboard protocol processors. Offloads network processing from the PC CPU.
- SOFTNET-IE S7 REDCONNECT: Executes protocol stacks in software on the PC host CPU using standard commercial network interface cards (BCE concept).
- Licensing Non-Compliance of Basic Packages:
- SOFTNET-IE S7 Lean: Limited to 8 non-redundant S7 connections. Completely rejects redundant S7 connections.
- Standard SOFTNET-IE S7: Supports up to 64 non-redundant S7 connections, but cannot arbitrate 4-way fault-tolerant connection pairs.
- BCE (Basic Communication Ethernet): Legacy driver framework for single S7 connections; cannot sustain redundant S7 failover.
Step-by-Step Engineering and Implementation Procedure
Step 1: Audit Communication Architecture in NetPro
- Open NetPro on the Engineering Station.
- Select the SIMATIC PC Station (OS Server or ES).
- Inspect the connection table: redundant connections to AS 410-5H / S7-400H are defined as 'S7 connection fault-tolerant'.
- Confirm that the interface type assigned in the PC Station HW Config is 'IE General' (representing standard commercial NICs).
Step 2: Procure SOFTNET-IE S7 REDCONNECT Licenses
Procure one SOFTNET-IE S7 REDCONNECT license for each physical PC station communicating over fault-tolerant S7 connections:
- For example, SOFTNET-IE S7 REDCONNECT V16 (MLFB: 6GK1704-0HB16-0AA0) or the applicable version matching your installed SIMATIC NET release (V16, V17, etc.).
[!NOTE]
Validate exact MLFB and SIMATIC NET version compatibility with your Siemens catalog or distributor quotation prior to purchasing.
Step 3: Install Licenses via Automation License Manager
- Open Automation License Manager (ALM) on each target PC station.
- Transfer the
SOFTNET-IE S7 REDCONNECTlicense key from the License USB stick to driveC:. - Check license status to ensure no trial or expiration limitations exist.
Step 4: Configure Station Configuration Editor
- On the PC station, open the Station Configuration Editor.
- Ensure the two physical network adapters assigned to the plant bus are configured as 'IE General' in matching rack slots as defined in STEP 7 HW Config.
- In Simatic Shell, select the terminal bus network adapter.
- Download the PC station configuration from NetPro.
Verification
To verify redundant communication:
1. Open SIMATIC NET diagnostic tool 'Communication Settings' -> 'Diagnostics' -> 'Connections'.
2. Verify that the fault-tolerant S7 connection reports status 'ESTABLISHED' with all active subpaths operational.
3. In ALM, verify that the SOFTNET-IE S7 REDCONNECT license is actively checked out by the SIMATIC NET runtime process.
4. Disconnect one plant bus network cable; verify that process data in WinCC runtime continues updating without alarm delays.
Limitations and Operational Precautions
Operational precautions:
- SOFTNET-IE S7 REDCONNECT utilizes host CPU processing power. On heavily loaded systems with hundreds of thousands of process variables, Siemens recommends HARDNET (CP 1623) to eliminate CPU communication overhead.
- Standard NICs must have energy-saving modes ('Green Ethernet', 'Energy Efficient Ethernet') disabled in Windows Device Manager to prevent intermittent connection drops.
- Both physical NICs connected to redundant subnets must operate at identical link speeds (100 Mbps or 1 Gbps).
Engineer FAQ
Q: Can I use SOFTNET-IE S7 Lean for redundant controllers?
A: No. SOFTNET-IE S7 Lean strictly supports non-redundant single S7 connections up to 8 connections only.
Q: Is a REDCONNECT license required for OS Clients?
A: No. OS Clients communicate with the OS Server over the terminal bus and do not communicate directly with the AS controller over the plant bus.
Q: What is the difference between HARDNET and SOFTNET REDCONNECT?
A: HARDNET requires Siemens CP 1623/1628 PCI-Express cards with onboard coprocessors. SOFTNET uses standard commercial Ethernet cards with protocol processing performed by the PC CPU.
Q: How many fault-tolerant connections does SOFTNET-IE S7 REDCONNECT support?
A: SOFTNET-IE S7 REDCONNECT supports up to 16 fault-tolerant S7 connections depending on the SIMATIC NET version.
Q: What happens if REDCONNECT license is missing in ALM?
A: SIMATIC NET displays periodic license deficit warning popups, and the system operates in non-licensed trial mode with potential logging restrictions.
Technical References
- SIMATIC NET Industrial Communications Commissioning PC Stations - Manual and Instructions
- SIMATIC PCS 7 Licenses and Configuration Limits
- Siemens Industry Mall - SIMATIC NET Software
Related Articles
- Replacing CPU 410-5H Across Plant Bus and CP 443-1 Communication Processors in PCS 7 V8.1
- Troubleshooting WinCC OS Secondary Server Download Stalls and Database Context Errors in PCS 7
- Step-by-Step Procedure for Replacing One CPU in a Redundant AS 410-5H System During RUN
Related Tags
REDCONNECT, SOFTNET-IE S7, Redundant AS, SIMATIC NET, Plant Bus Licensing