Make PCS 7 Stations Visible Through the Terminal Bus
When SIMATIC Shell discovers PCS 7 stations over the management NIC but not the terminal-bus NIC, select the correct terminal-bus network adapter in SIMATIC Shell on the Engineering Station and confirm that the terminal-bus addresses resolve to the intended stations. If terminal-bus multicast must cross routed subnets, configure an appropriate SIMATIC Shell multicast proxy on a reachable PC. The reported engineer resolved this installation with host-name entries and adapter priority, but that result is topology-specific.
Table of Contents
- Select the Terminal-Bus Adapter
- Check Name Resolution and Subnet Boundaries
- Configure a Multicast Proxy When Needed
- Troubleshoot Discovery
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Select the Terminal-Bus Adapter
Siemens' PCS 7 PC Configuration manual describes configuring the communication module used for the terminal bus. In SIMATIC Shell settings, select the adapter that has the Engineering Station's terminal-bus IP address, then initialize network communication when prompted. Make sure the selected NIC is the terminal bus, not the management network or plant bus.
Check Name Resolution and Subnet Boundaries
Ping success by IP does not prove that station names resolve to the intended terminal-bus addresses or that SIMATIC Shell multicast discovery crosses the network path. Confirm each station's terminal-bus IP and name mapping and test name resolution from the Engineering Station. The source's successful resolution used entries in the Windows hosts file and changed interface metrics so the terminal-bus adapter had higher priority; apply such changes only with network administration approval and the site's address plan.
Configure a Multicast Proxy When Needed
Siemens documents a multicast proxy for networks where routers do not forward multicast traffic between subnets. The proxy must be a specific PC reachable in the other network segment; it is not an arbitrary unused IP. Select the multicast proxy in SIMATIC Shell on the relevant stations according to the PCS 7 PC Configuration procedure. A proxy is relevant to routed multicast and should not be added as a generic fix for every multi-NIC station.
Troubleshoot Discovery
- Record the terminal-bus IP, subnet mask, gateway, DNS/hosts mapping, and adapter metric for the ES and each station.
- In SIMATIC Shell, select the NIC assigned to the terminal bus and initialize communication.
- Check that station hostnames resolve to terminal-bus addresses from the ES.
- Confirm multicast routing or configure the documented proxy where subnets are routed and multicast is not forwarded.
- Repeat discovery in SIMATIC Shell and check whether the OS station can be selected in STEP 7/PCS 7 engineering.
- Keep plant-bus, terminal-bus, and management traffic separated according to the approved network design.
Verification
With the intended terminal-bus adapter selected, verify that the OS and other stations appear in SIMATIC Shell and that PCS 7 engineering can locate the expected OS station through that network. Confirm that remote-support and plant-bus communications still use their intended interfaces.
Limitations and Operational Precautions
The forum's hosts and interface-metric solution is a reported result for one three-network topology; it does not prove a universal discovery procedure. Incorrect metrics or host mappings can redirect other communications. The source contains a duplicated phrase for terminal bus where one network may have meant plant bus, so confirm the actual topology.
Engineer FAQ
Select the terminal-bus NIC in SIMATIC Shell, verify terminal-bus name resolution, and use a multicast proxy only when routed subnets block multicast. The forum's hosts-file and adapter-priority fix is topology-specific.
Technical References
- Siemens, PCS 7 – PC Configuration (V9.1), terminal-bus communication and SIMATIC Shell settings: https://support.industry.siemens.com/cs/attachments/109794377/ps7pck_b_en-US.pdf
- Siemens, PCS 7 Virtualization, §6.3.5 “Communication over multiple subnets,” explaining terminal-bus multicast proxy configuration: https://support.industry.siemens.com/cs/attachments/109737277/Manual_PCS7V81SP1_Virtualization_en.pdf
Related Articles
Related Tags
SIMATIC Shell, terminal bus, multicast proxy, network adapter