Mass Engineering in SIMATIC PCS 7: Tool Evolution, Plant Automation Accelerator, and Best Practices
In SIMATIC PCS 7, mass engineering (bulk generation of charts from I/O schedules) has evolved across software generations: legacy Import/Export Assistant (IEA) handles tabular CSV parameterization; Advanced ES (AES) was discontinued in PCS 7 V8.2; and Siemens COMOS paired with Plant Automation Accelerator (PAA) serves as the modern standard. Best practice establishes Control Module Types (CMT) in the Master Data Library and executes bidirectional synchronization.
Table of Contents
- Mass Engineering Objectives and Industrial Scale
- Tool Evolution: IEA, Advanced ES, and Plant Automation Accelerator
- Step-by-Step Bulk Engineering Workflow Using Control Module Types
- PCS 7 Mass Engineering Tools Comparison Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Mass Engineering Objectives and Industrial Scale
Modern industrial facilities (such as major oil refineries, pulp and paper complexes, or wastewater treatment facilities) contain thousands of physical I/O instruments and hundreds of recurring equipment patterns (pumps, block valves, control valves, transmitters).
Manually drawing individual Continuous Function Charts (CFC) for 1,500 motors and 800 control valves is economically unviable and introduces severe human error:
* Typographical errors in I/O addresses and tag names.
* Inconsistent alarm priority assignments across plant units.
* Excessive engineering hours spent performing repetitive tasks.
To achieve high efficiency, engineering teams deploy Mass Engineering (also known as Bulk Engineering). In SIMATIC PCS 7, mass engineering automates the generation, parameterization, and updating of hundreds of CFC charts directly from standardized instrumentation schedules or electrical spreadsheets.
Tool Evolution: IEA, Advanced ES, and Plant Automation Accelerator
Siemens has provided multiple generations of mass engineering tools across PCS 7 releases:
-
Import/Export Assistant (IEA - Classic Standard):
* Native, built-in feature of the SIMATIC PCS 7 Engineering System.
* Utilizes Process Tag Types (PTT) in the Master Data Library and text/CSV import files.
* Allows mass assignment of device names, I/O addresses, comments, and setpoints from Microsoft Excel. -
Advanced ES (AES - Discontinued):
* Introduced in PCS 7 V8.0 as an add-on based on COMOS technology for tabular editing.
* Discontinued Notice: Advanced ES was officially discontinued as of PCS 7 V8.2 and is no longer supplied with media packages or supported in modern releases. -
Modern Integrated Standard: Siemens COMOS & Plant Automation Accelerator (PAA):
* The contemporary Siemens standard across PCS 7 V8.2, V9.x, and beyond.
* Leverages Control Module Types (CMT), Equipment Modules (EM), and AutomationML (AML) data exchange.
* Provides complete bidirectional synchronization: changes made in electrical P&IDs flow automatically into PCS 7 HW Config and CFC, while field commissioning changes synchronize back into engineering documentation.
Step-by-Step Bulk Engineering Workflow Using Control Module Types
1. Establish Master Typicals in the Master Data Library
- Open the Master Data Library (MDL) of your PCS 7 multiproject.
- In the Plant View, create a Control Module Type (CMT) (e.g.
CMT_Motor_Lean). - Place technological blocks (e.g.
MotL,Pcs7DiIn,Pcs7DiOu). - In the CMT configuration table, designate which block pins are Configurable Attributes (e.g.
PV_In.Valuehardware address,FbkRun.Value,Command.Value).
2. Generate and Populate the Mass Data Exchange Sheet
- If using Import/Export Assistant (IEA):
* Right-click the Process Tag Type and select Plant Hierarchy > Create Import/Export File....
* Open the generated.csvor tab-delimited text file in Microsoft Excel.
* Populate columns with field data: Tag Name, Unit Path, I/O Addresses (IW 512,QW 512), and High/Low Alarm Limits. - If using Plant Automation Accelerator (PAA):
* Import the plant instrumentation schedule directly into PAA.
* Map instrument types to CMT typicals in the PAA engineering tree.
3. Execute Mass Instantiation
- In SIMATIC Manager, select Plant Hierarchy > Import Process Tags....
- Select your completed Excel/CSV file.
- The wizard validates addresses, detects duplicates, and automatically generates all corresponding CFC charts across the Plant Hierarchy.
- Execute Chart > Compile > Entire Program with Generate module drivers enabled.
PCS 7 Mass Engineering Tools Comparison Matrix
Verification
- Prepare an IEA import file containing 50 motor tag definitions (
PMP_001toPMP_050). - Execute Import Process Tags in SIMATIC Manager.
- Confirm the utility completes with 0 Errors, creating 50 new CFC charts in the Plant Hierarchy.
- Open chart
PMP_025; confirm that I/O addresses, block comments, and tag descriptors match the spreadsheet row. - Compile the Chart folder; confirm module drivers generate cleanly with 0 Errors.
Limitations and Operational Precautions
- Avoid Advanced ES for New Projects: Do not design new mass engineering workflows around SIMATIC PCS 7 Advanced ES; software discontinuation prevents migration to PCS 7 V8.2 or V9.x.
- Syntax Rigor in Spreadsheets: In CSV import files, ensure delimiter consistency (comma vs. semicolon) and eliminate illegal special characters in tag names (
/,\,?,*,"). - Licensing Requirements: The Import/Export Assistant is included in standard PCS 7 Engineering licenses, while PAA and COMOS require separate commercial software licenses.
Engineer FAQ
What is the difference between Process Tag Types (PTT) and Control Module Types (CMT)?
PTT is the legacy PCS 7 templating technology. CMT was introduced in PCS 7 V8.0 to support modular sub-components, optional blocks, and seamless integration with PAA and COMOS.
Can I modify an instantiated chart without breaking its link to the template?
Yes. With CMTs, instance-specific variations can be configured. When updating templates, the system updates common structural logic while preserving instance-specific parameter overrides.
Where can I find sample mass engineering templates?
Siemens provides sample mass engineering projects and Excel typical mapping sheets on Siemens Industry Online Support (SIOS) under application example entry ID 109737945.
Technical References
- SIMATIC Process Control System PCS 7 Engineering System Manual (V8.1 / V8.2)
- SIMATIC PCS 7 Plant Automation Accelerator (PAA) Operating Manual
- SIMATIC Process Control System PCS 7 Compendium Part A - Configuration Guidelines
- Siemens Industry Online Support: Mass Engineering in PCS 7 (SIOS Entry ID 109780813)
Related Articles
- Master Data Library Templates: Copying APL Typicals and Multi-Instance Synchronization
- Standard Best Practices for Creating a New Multiproject in SIMATIC PCS 7
- Software Tools for Designing a SIMATIC PCS 7 DCS Plan
Related Tags
- Mass Engineering
- Bulk Engineering
- IEA
- PAA
- Control Module Types
- COMOS