Migrating a SIMATIC PCS 7 ES-OS Single Station to a Redundant OS Server Pair and Dedicated ES
To migrate an existing SIMATIC PCS 7 V8.1 ES/OS Single Station to a high-availability client-server architecture with a dedicated Engineering Station (ES) and a redundant OS Server pair (Master and Standby), engineers must restructure the PCS 7 Multiproject. This involves adding two SIMATIC PC Stations configured with WinCC Application and WinCC Application (stby), converting the existing Single-User WinCC project into a Multi-User Project, configuring the WinCC Redundancy Editor, updating NetPro named connections, reassigning the Plant Hierarchy OS assignment, generating Server Data, and replicating the project via the Project Duplicator.
Table of Contents
- Architecture Transformation: Single Station to Redundant Client-Server
- Multiproject Reconfiguration and Station Definition
- Comparison of Single Station vs Redundant OS Server Configurations
- Step-by-Step Procedure to Convert and Deploy the Redundant OS Pair
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Architecture Transformation: Single Station to Redundant Client-Server
An ES/OS Single Station combines engineering software (STEP 7, CFC, SFC, PDM) and operator station runtime (WinCC Explorer, Graphics Runtime, Alarm Logging) on a single physical IPC. While cost-effective for small facilities, a Single Station presents a single point of failure and prohibits concurrent engineering during continuous operation.
Migrating to a redundant OS architecture with a dedicated ES provides 24/7 high availability. The architecture requires:
1. Dedicated ES: Retains engineering licenses and multiproject databases, communicating with AS controllers over the Plant Bus and with OS servers over the Terminal Bus.
2. OS Server Master (OS1): Executes active data acquisition, process alarming, and historical archiving, hosting a multi-user WinCC project.
3. OS Server Standby (OS2): Operates in continuous warm standby, continuously synchronizing process tags, alarm states, and archive segments with OS1 across a dedicated network redundancy connection.
4. OS Clients: Operator consoles loaded with client projects that access the redundant server pair via generated Server Data packages.
Multiproject Reconfiguration and Station Definition
The conversion requires structural adjustments in the SIMATIC Manager Component View and Plant View:
- PC Station Definitions: The original single-station PC Station (
WinCC Appl. Single) is decommissioned or repurposed as the dedicated ES. Two new SIMATIC PC Stations are created:OS_SRV1containingWinCC Appl.and CP 1623 (6GK1162-3AA00), andOS_SRV2containingWinCC Appl. (stby). - NetPro Communication: Named S7 connections (
S7-Verbindung) must be routed from the AS controller (e.g. CPU 410-5H,6ES7410-5HX08-0AB0) to both OS servers individually. - Project Duplicator: The engineering project is authored and compiled on the ES, and the Project Duplicator tool transfers identical runtime databases to both physical server IPCs (e.g., SIMATIC IPC647D,
6AG4112-2KA40-0BX0).
Comparison of Single Station vs Redundant OS Server Configurations
The following table compares the structural, network, and operational differences between the architectures:
WinCC Appl. Single)WinCC Appl. + 1 WinCC Appl. (stby))Step-by-Step Procedure to Convert and Deploy the Redundant OS Pair
Follow this rigorous engineering procedure to execute the migration:
-
Multiproject Backup and Hardware Station Insertion:
- Create a complete project archive usingFile -> Archive.
- In SIMATIC Manager Component View, right-click the Multiproject and insert two new SIMATIC PC Stations:OS_SERVER_1andOS_SERVER_2.
- Open HW Config forOS_SERVER_1. Insert aWinCC Appl.into Slot 1 and aCP 1623(orIE General) into Slot 2.
- Open HW Config forOS_SERVER_2. Insert aWinCC Appl. (stby)into Slot 1 and the corresponding network card into Slot 2.
- Save and compile HW Config for both stations. -
Configure NetPro S7 Connections:
- Open NetPro. SelectOS_SERVER_1 / WinCC Appl.and insert a new S7 connection to the AS controller. Repeat forOS_SERVER_2.
- SelectNetwork -> Save and Compile. Download the network configuration to the AS controller during a scheduled window. -
Convert WinCC Project Type and Configure Redundancy:
- Open the WinCC project ofOS_SERVER_1in WinCC Explorer.
- Open Project Properties. Change the Project Type from Single-User Project to Multi-User Project.
- Open the Redundancy editor in WinCC Explorer. Check Activate Redundancy.
- Enter the computer name ofOS_SERVER_2in the 'Redundant Partner Server' field.
- Select the network adapter on the Terminal Bus for connection checking, and enable automatic synchronization after partner recovery. -
Reassign Plant Hierarchy and Compile AS-OS:
- In SIMATIC Manager Plant View, right-click the root Plant Hierarchy folder, selectProperties, and reassign the target OS from the old single station toOS_SERVER_1.
- Right-click the OS object underOS_SERVER_1and selectCompile. Choose 'Entire OS' with 'With memory reset' to map all S7 tags to the new multi-user structure.
- In WinCC Explorer onOS_SERVER_1, right-click Server Data and selectGenerate. -
Deploy Project to OS Server 2 via Project Duplicator:
- Close the WinCC project on the ES.
- In Windows, launchTools -> Project Duplicator(from Siemens WinCC tool menu).
- Specify the source project path (OS_SERVER_1.mcp) and target project UNC path (\\OS_SERVER_2\WinCC_Project\). Click Duplicate.
- Verify that the duplicator automatically adapts computer names and redundancy parameters for Server 2.
Verification
Verify system migration and redundancy operation through the following steps:
1. Start WinCC Runtime on OS_SERVER_1. Confirm successful AS-OS communication and dynamic tag updates.
2. Start WinCC Runtime on OS_SERVER_2. Confirm internal redundancy tags: @RedundancyServerState must report 1 (Master) on OS1 and 2 (Standby) on OS2.
3. Verify archive synchronization: Generate a test alarm or process tag change on OS1, disconnect OS2 network cable, reconnect, and verify that the Redundancy Control window indicates 'Archive synchronization completed'.
4. Open an OS Client, download server packages, and confirm that process graphics display without connection errors.
Limitations and Operational Precautions
- Software Licensing and Process Object Verification: Migrating from Single Station to a Redundant Server pair requires distinct runtime licenses: two WinCC Server runtime licenses, an OS Redundancy package (
6AV6371-1CA07-5AX0), and identical AS RT / OS RT PO counts on both servers. Procurement must be verified prior to commissioning. - Terminal Bus Decoupling: Redundant OS servers must have dedicated network interfaces for the Terminal Bus (OS-to-Client and OS-to-OS) and Plant Bus (OS-to-AS). Never bridge these subnets on a single network adapter.
- Computer Name Matching: The Windows computer names of the physical IPCs must exactly match the SIMATIC PC Station computer names configured in SIMATIC Manager; otherwise, WinCC Runtime cannot launch.
Engineer FAQ
Do I need to re-engineer all my graphics screens when migrating to redundant servers?
No. The graphic pictures (*.pdl), global scripts, and alarm configurations remain 100% reusable. Reassigning the Plant Hierarchy and compiling AS-OS updates all tag connections to the new Multi-User server structure automatically.
Why does WinCC Project Duplicator fail during migration?
Project Duplicator typically fails if the source project is currently open in WinCC Explorer, if Windows sharing and security permissions (read/write access for user group SIMATIC HMI) are not granted on the target server folder, or if network name resolution via DNS/NetBIOS is failing.
What happens to existing historical trend data during the migration?
Historical archives stored on the old single station reside in Microsoft SQL Server database segments (*.mdf / *.ldf). They can be exported using the WinCC Archive Configuration backup tool and attached to the new OS Server archive directory using the 'Restore' function.
Technical References
- SIMATIC Process Control System PCS 7 Minimal Configurations (Entry ID 24023824)
- SIMATIC PCS 7 Compendium Part A - Configuration Guidelines (A5E45063013-AA)
- SIMATIC HMI WinCC V7.4 WinCC: Working with WinCC Manual (A5E37536408-AB)
- Siemens Industry Online Support Manual: Setting up redundant OS Servers in PCS 7 (Entry ID 109760737)
Related Articles
- CPU 410-5H System Expansion Card (SEC) PO Upgrade Rules in PCS 7 V8.0 vs V8.1
- Resolving Greyed-Out Picture Tree Navigation and Area Authorization Errors on PCS 7 OS Clients
- Why SIMATIC PCS 7 V9.0 Requires Windows 10 Enterprise LTSB Instead of Windows 10 Pro
- Remote Engineering and Maintenance Architecture for SIMATIC PCS 7