Migrating Legacy SEND_R and REC_R Communication Blocks to Modern PCS 7 APL Blocks
In SIMATIC PCS 7 V8.0 and higher, the classic communication blocks SEND_R (FB209) and REC_R (FB210) from the PCS 7 Standard Library V7.1 were removed from the default Basis Library and moved to DVD 2 under Additional Products. To implement cross-controller S7 communication in modern PCS 7 projects, migrate to the native Advanced Process Library (APL) communication blocks Snd_AnaVal (FB1894) and Rcv_AnaVal (FB1895), or deploy standard S7 communication blocks BSEND (SFB12) and BRCV (SFB13) configured in NetPro.
Table of Contents
- Decoupling of the PCS 7 Standard Library and Transition to APL
- Cross-Controller Communication Block Selection Matrix
- Installing Legacy Standard Library V7.1 from Additional Products Media
- Migrating to Native APL Blocks (Snd_AnaVal / Rcv_AnaVal)
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Decoupling of the PCS 7 Standard Library and Transition to APL
In SIMATIC PCS 7 V7.1, automation engineers relied extensively on the PCS 7 Standard Library (often called the Classic or Standard Library), which included function blocks such as SEND_R (FB209) and REC_R (FB210) located in the COMM family for transmitting REAL process values over configured S7 connections.
Beginning with SIMATIC PCS 7 V8.0, Siemens transitioned entirely to the Advanced Process Library (APL). During this transition:
1. The classic PCS 7 Standard Library was decoupled from the primary installation image and placed onto DVD 2: Additional Products under the directory \Additional_Products\PCS7LIBRARY__V7.1+SP3.
2. The core system manuals (such as the PCS 7 Basis Library V8.0 Manual) continued to list SEND_R and REC_R in their appendix tables solely for resource load estimation (CPU scan time, work memory, and communication instances) to aid engineers migrating legacy projects.
3. Because the blocks are not installed in the default APL or Basis Library catalogs, searching for FB209 or FB210 in a fresh PCS 7 V8.0/V8.1 installation yields no results.
To maintain engineering consistency, plants must either install the legacy library package as an interim bridge or upgrade their cross-controller architectures to native APL communication blocks.
Cross-Controller Communication Block Selection Matrix
Evaluate available communication blocks for cross-controller data exchange in PCS 7:
ST) HandlingSEND_R / REC_RFB209 / FB210Snd_AnaVal / Rcv_AnaValFB1894 / FB1895Value + ST byte)Snd_DigVal / Rcv_DigValFB1896 / FB1897Value + ST byte)BSEND / BRCVSFB12 / SFB13USEND / URCVSFB8 / SFB9Engineering notice: APL communication blocks preserve NAMUR NE 107 signal status bytes across network boundaries.
Installing Legacy Standard Library V7.1 from Additional Products Media
If legacy plant standards require retaining SEND_R and REC_R on PCS 7 V8.0 / V8.1:
- Locate Installation Media:
* Insert or mount PCS 7 V8.0 / V8.1 DVD 2 (Additional Products).
* Navigate to the folder:
DVD_2\Additional_Products\PCS7LIBRARY__V7.1+SP3 - Execute Library Setup:
* Right-clickSetup.exeand select Run as Administrator.
* Follow the installation wizard to install the legacy blocks into STEP 7. - Open and Retrieve Blocks in SIMATIC Manager:
* In SIMATIC Manager, select File > Open > Libraries.
* Open PCS 7 Library V7.1.
* Locate theBlocksfolder, findSEND_R(FB209) andREC_R(FB210), and copy them into your project's master data library.
* Update the CFC block catalog to instantiate them.
Migrating to Native APL Blocks (Snd_AnaVal / Rcv_AnaVal)
To upgrade to modern APL communication blocks in PCS 7 V8.1 and higher:
- Configure S7 Connection in NetPro:
* Open NetPro.
* Create a bilateral S7 Connection between Controller A and Controller B.
* Note the local connection ID (e.g.,W#16#0001).
* Download NetPro network configurations to both AS stations. - Instantiate APL Driver Blocks in CFC:
* In Controller A, insertSnd_AnaVal(FB1894) into a cyclic chart (OB 35).
* ParameterizeIDwith the NetPro connection handle.
* Connect process values (e.g.,MonAnL.PV_Out) to inputsIn01throughIn16.
* In Controller B, insertRcv_AnaVal(FB1895) with the matching connection ID.
* Connect outputsOut01throughOut16directly to downstream interlocks or controllers. - Automatic Status Propagation:
* Unlike legacySEND_R,Snd_AnaValtransmits both the floating-point value and the Signal Status (ST = 16#80,16#60,16#00). If Controller A's sensor fails, Controller B's faceplate immediately detects the bad quality code without requiring custom alarm bits.
Verification
Verify cross-controller communication:
1. Online in Controller A CFC: Force a test value (e.g., 45.67) on Snd_AnaVal.In01.Value.
2. Online in Controller B CFC: Confirm that Rcv_AnaVal.Out01.Value registers 45.67 within one communication cycle.
3. Disconnect the plant bus cable between the two controllers: Confirm that Rcv_AnaVal flags Error = 1 and sets signal status ST = 16#00 (Bad), causing downstream APL blocks to enter fail-safe substitute states.
Limitations and Operational Precautions
- Legacy Standard Library V7.1 is not supported in PCS 7 V9.0 and higher; continuing to use
FB209andFB210creates technical debt and prevents upgrading to CPU 410-5H firmware. - Ensure S7 connection quotas on S7-400 CPUs are not exceeded; each configured S7 connection consumes one connection resource handle.
- Do not trigger
BSENDorSnd_AnaValin rapid OB 30 (10 ms) cycles without throttled send clocks, as this saturates the CP 443-1 communication buffer.
Engineer FAQ
Why did the PCS 7 Basis Library manual list SEND_R if the block was missing?
The Basis Library manual included SEND_R and REC_R in its resource consumption appendix to assist engineers migrating older V7.1 projects. The table documented memory footprints, not catalog inclusion.
Can Snd_AnaVal communicate with a legacy S7-300 PLC?
No. Snd_AnaVal utilizes proprietary APL structure packing. For communicating with S7-300 or third-party PLCs, use standard BSEND/BRCV or PUT/GET.
How many analog values can Snd_AnaVal transmit per block?
Snd_AnaVal transmits up to 16 structured analog values (Value + Signal Status) in a single coordinated S7 communication packet.
Technical References
- SIMATIC Process Control System PCS 7 Basis Library V8.0 Manual (A5E32106015)
- SIMATIC PCS 7 Advanced Process Library (APL) Manual (A5E32106040)
- Siemens Support Entry 68113421: Resource Load and Block Migration Tables
Related Articles
- Selecting and Migrating Block Libraries for SIMATIC PCS 7 V8.1: APL vs. Standard Library
- Integrating SIMATIC S7-1200 Controllers into PCS 7 via S7 Communication and Open OS
- Interpreting Quality Codes and Resolving Shaded Attention Icons on WinCC I/O Fields in PCS 7 APL
Related Tags
- SEND_R
- REC_R
- Snd_AnaVal
- Rcv_AnaVal
- APL Migration
- Standard Library
- S7 Communication
- PCS 7 V8.0