Migrating SIMATIC Route Control from PCS 7 V7.1 SP1 to V8.2: Intermediate Steps and Database Upgrade Strategies
A direct, one-step migration from SIMATIC Route Control (RC) V7.1 SP1 to V8.2 is not supported by standard Siemens setup wizards because the underlying software architectures span major generational leaps in Windows OS (32-bit to 64-bit), Microsoft SQL Server (2005 to 2014), and database schemas. To successfully migrate Route Control across this gap, engineers must utilize an intermediate migration step—typically PCS 7 V8.0 SP2 or V8.1. The workflow requires converting the STEP 7 multiproject and Route Control Wizard configuration in the intermediate environment, upgrading the Route Control Center (RCC) database schema, updating the AS library blocks to RC V8.2, and applying RC upgrade licensing.
Table of Contents
- Generational Architecture Gap: Route Control V7.1 SP1 vs V8.2
- Why Direct Migration Is Not Documented in Single Manuals
- The Recommended Multi-Step Migration Route (V7.1 -> V8.0/8.1 -> V8.2)
- Route Control Engineering and Database Schema Conversion
- AS Block Library Updating and OS Client-Server Synchronization
- Comparative Upgrade Matrix: Route Control Across PCS 7 Generations
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Generational Architecture Gap: Route Control V7.1 SP1 vs V8.2
SIMATIC Route Control (RC) is the PCS 7 optional software package responsible for dynamic routing, pathfinding, and element control (valves, pumps, pipes, tanks) in liquid and solids transport systems. Migrating an existing plant from PCS 7 V7.1 SP1 to V8.2 represents a generational technological leap:
- Operating System Transition: PCS 7 V7.1 SP1 ran exclusively on 32-bit platforms (Windows XP Professional SP3 / Windows Server 2003 R2). PCS 7 V8.2 runs exclusively on 64-bit platforms (Windows 7 Enterprise SP1 64-bit / Windows Server 2012 R2 Standard 64-bit).
- Database Engine Transition: Route Control V7.1 relied on Microsoft SQL Server 2005. Route Control V8.2 relies on Microsoft SQL Server 2014 SP1. Direct in-place database schema attachment across three SQL generations is rejected by the Microsoft SQL engine.
- Route Control Server Architecture: The internal IPC and COM/DCOM interfaces between the Route Control Server (
rcs_server.exe) and WinCC were completely rewritten between V7.1 and V8.2 to support modern 64-bit security contexts.
Why Direct Migration Is Not Documented in Single Manuals
Engineers attempting this migration frequently search for a dedicated guide titled 'How to Migrate Route Control V7.1 SP1 to V8.2' and find none. Siemens product documentation for optional packages (Route Control, SIMATIC BATCH, CEMAT) intentionally documents only n-1 to n upgrades (e.g., V8.1 to V8.2). Multi-version jumps across major OS and software paradigms are covered by the comprehensive system upgrade manuals:
- PCS 7 Software Update with Utilization of New Functions (Entry ID: 109736706)
- PCS 7 Software Update without Utilization of New Functions (Entry ID: 109736696)
These system guides establish the mandatory prerequisite of bridging generational database gaps through an intermediate software version.
The Recommended Multi-Step Migration Route (V7.1 -> V8.0/8.1 -> V8.2)
To safely bridge the database and OS gap, the industry-standard migration pathway employs an intermediate engineering VM:
- Phase 1: Project Archive in V7.1 SP1: Perform a complete archive of the STEP 7 multiproject including Route Control data. Export the Route Control database (
*.rcdor SQL backup) from Route Control Engineering. - Phase 2: Intermediate Upgrade in PCS 7 V8.0 SP2 or V8.1:
- Restore the project onto an intermediate 64-bit engineering station running PCS 7 V8.0 SP2 (SQL Server 2008 R2) or V8.1 (SQL Server 2014).
- Open SIMATIC Manager and allow STEP 7 to execute the internal project format conversion.
- Open Route Control Engineering and execute the Route Control Wizard. The wizard converts legacy V7.1 route configurations and updates the internal database schema to V8.x format.
- Compile and save the multiproject. - Phase 3: Final Upgrade in PCS 7 V8.2:
- Transfer the upgraded project to the final PCS 7 V8.2 Engineering Station.
- Run the Route Control Wizard in V8.2 to finalize the project structure.
Route Control Engineering and Database Schema Conversion
During the Route Control upgrade process, the internal engineering database undergoes critical transformations:
- Route Control Wizard Execution: In SIMATIC Manager, right-click the project and select
SIMATIC Route Control -> Configure. The wizard validates that all Route Control elements (locations, partial routes, elements, modes) conform to the new relational database constraints. - Route Control Center (RCC) Views: The graphical client layouts in Route Control Center are converted to modern OCX controls compatible with WinCC V7.4.
- Consistency Check: Run
Options -> Consistency Checkinside Route Control Engineering. Resolve any orphaned locations or deprecated signal linkages before proceeding to AS compilation.
AS Block Library Updating and OS Client-Server Synchronization
Once the engineering database is converted, the controller and operator station tiers must be aligned:
- Master Data Library AS Blocks: Replace the legacy Route Control V7.1 blocks in your Master Data Library with the updated blocks from the PCS 7 Route Control Library V8.2 (
RC_IF_CFG,RC_ROUTE,RC_PE,RC_SE). - Update Block Types: In SIMATIC Manager, execute
Options -> Charts -> Update Block Typesacross all target AS programs. This updates block interfaces while preserving existing parameter interconnections. - OS Server Data and WinCC Controls: In the OS Server WinCC projects, re-run the OS Project Editor to update Route Control system pictures and scripts (
@RC_*.pdl). Re-generate and load server packages onto all OS Clients.
Comparative Upgrade Matrix: Route Control Across PCS 7 Generations
The following table compares Route Control system requirements across versions:
Verification
Validate successful Route Control migration through the following steps:
- In SIMATIC Manager on PCS 7 V8.2, open Route Control Engineering and verify that all routes, partial routes, and elements load without database error prompts.
- Execute
Route Control -> Compile and Downloadto AS and verify 0 errors in the compilation log. - Perform an OS Compilation and download to the Route Control Server.
- Launch Route Control Center (RCC) in WinCC Runtime and verify that the server connects, displaying all locations with live dynamic states.
- Execute a test route request from source to destination; verify pathfinding, valve alignment, and route start sequencing.
Limitations and Operational Precautions
Adhere to the following migration precautions:
- Never Attempt Direct SQL Attachment: Never copy the raw SQL database files from V7.1 directly into SQL Server 2014; the schema version mismatch will corrupt the Route Control catalog.
- Commercial Upgrade Licensing: Upgrading to RC V8.2 requires Siemens upgrade licenses (e.g.
SIMATIC Route Control Upgrade Package V7.1 -> V8.x). Confirm routes capacity licenses in Automation License Manager prior to site commissioning. - S7-300 Controller Support: Note that Route Control V8.2 phased out legacy S7-300 block execution; route control blocks must reside in S7-400 or CPU 410-5H controllers.
[!NOTE]
Commercial Accuracy Disclaimer: Software order numbers (MLFBs), package structures, and hardware capacity prerequisites vary across PCS 7 versions > and hardware platforms. System integrators must confirm exact software entitlements and licensing requirements against the official Siemens > Catalog CA 01 and obtain an authorized Siemens distributor quotation prior to purchasing.
Engineer FAQ
Are my existing Route Control route counts and license tags preserved during the upgrade?
Yes, but you must procure the official Siemens Route Control Upgrade License package to authorize the existing route capacity on PCS 7 V8.2.
Can I run Route Control V8.2 on an S7-300 controller?
No. Route Control V8.2 requires execution in S7-400 or CPU 410-5H controllers; legacy S7-300 controllers running RC V7.1 must be upgraded or interfaced as external I/O.
Do I need to re-enter all partial routes and plant elements in Route Control Engineering?
No. Running the Route Control Wizard in the intermediate and target versions converts all existing elements, partial routes, and control strategies automatically.
Technical References
- SIMATIC Process Control System PCS 7 SIMATIC Route Control V8.2 Manual (Entry ID: 109736706)
- PCS 7 Software Update with Utilization of New Functions (Entry ID: 109736706)
- PCS 7 Software Update without Utilization of New Functions (Entry ID: 109736696)
- Siemens Industry Online Support (SIOS) Route Control Migration FAQ (Entry ID: 109746516)
Related Articles
- Batch Editing Sequential Function Charts (SFC) and SFC Types
- Resolving Ghost Station Names in WinCC Runtime Tag Logging
- Upgrading S7-400H CPU 417-4H to CPU 410-5H with F-Safety
Related Tags
- SIMATIC Route Control
- PCS 7 Migration
- Route Control Wizard
- Database Schema Upgrade
- SQL Server 2014
- Intermediate Upgrade