Preserving Historical Tag Logging Archives When Moving Plant Hierarchy Folders
Moving a Plant Hierarchy (TH) folder containing archived measuring points does not destroy historical Tag Logging data if 'Included in the tag name' is disabled in Plant Hierarchy Settings. In that standard configuration, archive tag names and their internal SQL database IDs remain based solely on chart and block pin names; the modification date and internal ID in Tag Logging do not change upon OS compilation, preserving continuous historical trend curves. However, if 'Included in the tag name' is enabled, moving the folder alters the tag's fully qualified path, prompting WinCC to create a new archive tag and stranding historical records under the retired tag name.
Table of Contents
- Plant Hierarchy Naming Rules and WinCC Archive Tag Identity
- Impact of Moving Folders on Tag Logging SQL Databases
- Pre-Move Verification Procedure in Plant Hierarchy Settings
- Plant Hierarchy Tag Naming Options and Archive Impact Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Plant Hierarchy Naming Rules and WinCC Archive Tag Identity
In SIMATIC PCS 7, the Plant Hierarchy (TH) organizes charts, pictures, and reports into technological plant areas. When an analog measuring point (such as MonAnL) is configured with the archive attribute, the OS compiler creates an archive tag inside WinCC Tag Logging and maps it into the historical Microsoft SQL Server database (<ProjectName>#<ArchiveName>).
The naming convention of this archive variable depends on a global setting configured in SIMATIC Manager:
- Path Not Included in Tag Name: The WinCC variable name consists strictly of the CFC chart name and the block output pin (e.g.
XX17BTSR/PV_Out#Value). - Path Included in Tag Name: The WinCC variable name prepends the full technological folder path (e.g.
Plant/ZLT/Building17/XX17BTSR/PV_Out#Value).
Understanding which mode is active is critical when reorganizing plant folders (e.g. moving Building 17 from area ZLT to area Microbiology to adjust operator authorization levels).
Impact of Moving Folders on Tag Logging SQL Databases
When a hierarchy folder is moved within SIMATIC Manager:
-
Case A (Path Excluded - Standard): Because the tag name does not contain the folder names, its string identity is unaltered. During the subsequent delta OS Compile, the compiler compares the offline ES tags against the WinCC database, finds an exact name match, and leaves the internal archive record and its SQL identifier (
ArchiveTagID) intact. Existing runtime trends and historical curve groups continue logging and displaying historical data seamlessly. -
Case B (Path Included): Because the folder relocated, the fully qualified tag path changes (e.g. from
.../ZLT/...to.../Microbiology/...). During OS Compile, WinCC considers the old tag deleted and generates a brand-new archive tag with a new internal SQL ID. While existing archive segments containing historical data under the old ID are not physically deleted from disk, runtime trend controls configured to follow the new tag name will only display data starting from the compilation timestamp forward.
Pre-Move Verification Procedure in Plant Hierarchy Settings
Before reorganizing hierarchy folders in a live or commissioned plant, execute this verification procedure:
- Inspect Plant Hierarchy Settings:
- In SIMATIC Manager, select the plant hierarchy root folder.
- Navigate to Options -> Plant Hierarchy -> Settings....
- Inspect the checkbox: Included in the tag name (Im Namen von Variablen / Bausteinen enthalten).
- If this checkbox is unchecked, moving folders will not rename tags or disrupt SQL archives. - Validate in a Project Copy:
- Save a backup copy of the project.
- Move the target folder in the copy.
- Run a delta OS Compile.
- Open WinCC Explorer -> Tag Logging in the copy.
- Inspect the Modification Date (Änderungsdatum) and properties of the archive tag. If the date and ID are unchanged, the move is safe. - Adjust User Authorizations: If moving the folder was done solely to change operator access rights, configure the new area rights in WinCC User Administrator, ensuring operators in the new area have appropriate viewing permissions.
Plant Hierarchy Tag Naming Options and Archive Impact Matrix
The following table summarizes the impact of moving hierarchy folders based on project configuration settings:
<ChartName>/<Block>.<Pin><Area>/<Unit>/<ChartName>/<Block>.<Pin>[!NOTE]
Commercial Accuracy Notice: Reorganizing Plant Hierarchy containers and adjusting Tag Logging archive associations > are standard engineering operations within SIMATIC PCS 7 (6ES7658-1EX58-0YA5). No additional WinCC archive tag licenses > or Process Objects are consumed when relocating existing measuring points.
Verification
Confirm that historical process data remains continuous after relocating the folder:
- Tag Logging Inspection: After delta OS Compile, open WinCC Tag Logging on the OS. Confirm that the target process variable retains its original archive tag name and internal ID.
- Runtime Trend Validation: Open WinCC Runtime, navigate to the relocated measuring point faceplate, and select the trend view. Confirm that trend curves display unbroken data spanning before and after the engineering change.
- Process Historian Check: If a SIMATIC Process Historian is deployed, verify that archive packets continue to stream to the active segment without generating duplicate tag entries.
Limitations and Operational Precautions
Adhere to these precautions during Plant Hierarchy restructuring:
- Avoid Changing Chart Names: Even if 'Included in the tag name' is unchecked, changing the name of the CFC chart itself will alter the tag name and create a new archive variable.
- Full OS Compile Hazards: Performing an Entire OS Compile does not erase existing Tag Logging archives, but ensure that the option 'With memory reset' is never selected.
- KKS / Measuring Point Consistency: Maintain plant labeling standards (KKS / DIN) when moving technological containers to avoid confusion across operating teams.
Engineer FAQ
Does moving a hierarchy folder erase previously recorded archive data in SQL?
No. Previously recorded archive segments on disk are never deleted by moving a folder. However, if the tag is renamed, runtime trend controls will not link to the historical data recorded under the old tag name.
How can I tell if 'Included in the tag name' is active in my project?
In SIMATIC Manager, go to 'Options -> Plant Hierarchy -> Settings...' and inspect the checkbox 'Included in the tag name'. Alternatively, check if your WinCC tag names contain slash characters representing folder levels.
Can I reconnect old historical data if a tag was renamed during a move?
Yes, but it requires configuring the trend control to display an archive curve pointing to the retired tag name or using SQL migration tools to remap archive IDs.
Does moving a folder change the WinCC user access rights automatically?
Moving a chart to a new technological area assigns the block's WinCC faceplates to that area. Operators whose user accounts lack authorization for that new area will no longer be permitted to operate the block.
Technical References
- SIMATIC PCS 7 Plant Hierarchy Configuration Manual (Entry ID 109754986)
- WinCC V7.4 Tag Logging Function Manual (Entry ID 109736223)
- SIMATIC PCS 7 Operator Station OS Compilation Guide (Entry ID 109780813)
- Siemens Industry Online Support FAQ on Plant Hierarchy Renaming (Entry ID 109756824)
Related Articles
- Aligning Plant Hierarchy and Picture Hierarchy in SIMATIC PCS 7 V9.0
- Displaying Curve Names and Live Values in WinCC TrendControl
- Configuring WinCC User Administrator Security and Role-Based Permissions