RealVNC Enterprise Support and Cybersecurity Constraints in SIMATIC PCS 7 V9.0 Remote Architectures
In SIMATIC PCS 7 V9.0, remote desktop access using RealVNC is officially released and supported by Siemens, specifically using RealVNC Enterprise Edition (VNC Connect). RealVNC is approved for remote monitoring, diagnostic maintenance, and operator control of OS Clients and Engineering Stations. However, Siemens cybersecurity guidelines enforce strict constraints: only one active remote session is permitted per station, the connection must inherit the console session of the locally logged-on user rather than spawning a parallel session, and audio transmission is disabled. Validate software licensing and versions via the Siemens Compatibility Tool and an authorized Siemens distributor or the Siemens Industry Mall.
Table of Contents
- Executive Summary
- Architecture and Fundamental Mechanics
- Step-by-Step Implementation Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Executive Summary
Process manufacturing plants increasingly require secure remote operations—allowing off-site plant specialists, process engineers, and on-call technicians to access PCS 7 Operator Stations (OS) and Engineering Stations (ES) from corporate offices or mobile devices. While Microsoft Remote Desktop (RDP) is commonly used in enterprise IT, standard RDP opens disconnected virtual sessions that interfere with WinCC Runtime graphics rendering and can blind physical control room monitors. Siemens officially tests, certifies, and supports RealVNC Enterprise Edition for PCS 7. This technical guide outlines the official release status, configuration prerequisites, and mandatory industrial cybersecurity rules.
Architecture and Fundamental Mechanics
The remote access architecture in SIMATIC PCS 7 enforces distinct operational boundaries between RDP and RealVNC:
1. Why Standard Microsoft RDP is Restricted on WinCC Stations:
Standard RDP creates a new virtual display session (Session ID > 1) and locks the physical console monitor (Session 0). WinCC Runtime relies on hardware-accelerated direct DirectX/GDI rendering bound to the physical console. Using RDP causes screen refresh freezes, faceplate rendering delays, and blinds the physical operator sitting in the control room.
2. The RealVNC Console Shadowing Architecture:
RealVNC Enterprise Edition operates via direct desktop capture (Console Shadowing). The remote viewer captures the exact pixel buffer rendered on physical Session 0. Control room operators and remote specialists view the identical screen simultaneously, ensuring that local personnel maintain full situational awareness.
3. Siemens Official Certification and SIOS Guidance:
Siemens certifies RealVNC under SIOS Application Guideline Entry ID 102843424 ('Process visualization on mobile devices') and Entry ID 55422236 ('Accessing WinCC and PCS 7 with RealVNC'). The Siemens Compatibility Tool (kompatool) itemizes released RealVNC server and viewer builds for each PCS 7 version.
4. Cybersecurity and IEC 62443 Compliance:
- Encryption: 256-bit AES end-to-end encryption must be enforced in RealVNC Server properties.
- Network Demilitarized Zone (DMZ): RealVNC traffic should terminate at a central jump host or VPN gateway in the Industrial DMZ, never directly bridging corporate LAN to the Terminal Bus.
Step-by-Step Implementation Procedure
-
Verify RealVNC Version in Siemens Compatibility Tool:
a. Accesssupport.industry.siemens.com/kompatool.
b. Query 'SIMATIC PCS 7 V9.0' and check the released version of 'RealVNC VNC Connect Enterprise' (e.g., VNC Connect 6.x / 7.x).
c. Procure valid commercial RealVNC Enterprise licenses through authorized channels. -
Install RealVNC Server on Target PCS 7 Stations:
a. Log in to the target OS Client or Engineering Station as Administrator.
b. Run the RealVNC Server installer: select 'Enterprise Mode' (Service-mode installation).
c. In licensing, enter your enterprise license key. -
Configure Hardened Security Settings in RealVNC Server:
a. Open RealVNC Server Options -> 'Security' tab.
b. Set Encryption to 'Always maximum' (256-bit AES).
c. Set Authentication to 'Windows password' or 'Single Sign-On' to integrate with plant Active Directory domain security.
d. Under 'Users & Permissions', grant remote control rights exclusively to authorized automation engineers. -
Configure Display and Session Constraints:
a. Under 'Connections' tab, set 'Maximum connections = 1' to enforce the Siemens single-session policy.
b. Check 'Prompt local user to accept connection' if control room operator authorization is required before granting remote access.
c. Disable audio transmission in RealVNC options. -
Network Hardening and Firewall Configuration:
a. Configure local Windows Firewall on the PCS 7 station to permit inbound traffic on TCP port5900strictly from the designated DMZ Jump Host IP address.
b. Disallow any direct routing from external internet connections.
Verification
- Connect from the authorized DMZ jump host using RealVNC Viewer to the OS Client IP address.
- Enter authorized Windows domain credentials: confirm secure 256-bit AES connection establishes.
- Verify on the physical monitor in the central control room: confirm the screen remains live and mirrors the remote viewer without locking out the local operator.
- Click an analog faceplate: verify that response times are crisp and values update in real-time.
Limitations and Operational Precautions
Never install RealVNC Server directly on an S7-400 AS controller (which runs proprietary firmware) or on safety-critical SIL3 engineering nodes without strict administrative authorization; remote write commands must comply with plant operating procedures.
Engineer FAQ
Does SIMATIC PCS 7 V9 support RealVNC?
Yes. Siemens officially supports RealVNC Enterprise Edition (VNC Connect) across PCS 7 V8, V9, and V10 versions.
Why is RealVNC preferred over Microsoft RDP for WinCC?
RealVNC mirrors the physical console session (Session 0) without locking the control room monitor, whereas RDP creates a virtual session that interferes with WinCC Runtime rendering.
Can multiple remote users connect to the same OS station simultaneously?
No. Siemens guidelines strictly permit only one active remote session per PCS 7 station to prevent conflicting operator commands.
What TCP port does RealVNC use by default?
TCP Port 5900 is the standard port for VNC communication.
Can audio alarms be heard through RealVNC?
No. Audio transmission is not supported over RealVNC connections in PCS 7 environments.
Technical References
- Siemens Industry Online Support Entry 102843424 (Process Visualization on Mobile Devices)
- Siemens Industry Online Support Entry 55422236 (Accessing WinCC and PCS 7 with RealVNC)
- SIMATIC PCS 7 Industrial Security Concept and Compendium Part F
Related Articles
- Operational Impact and Hardening for Windows SMB Port 445 in PCS 7 Environments
- Troubleshooting 7-15 Second Faceplate Opening Delays on Redundant OS Clients
- Operating System Compatibility Guide: Running SIMATIC PCS 7 V9.0 on Windows 10 Enterprise LTSC
Related Tags
- RealVNC
- Remote Access
- PCS 7 V9.0
- Cybersecurity
- Console Mirroring
- WinCC Remote