Resolving 'Can't Create New Project Due to Internal Plant Hierarchy Error' (2772:106) in PCS 7
In SIMATIC PCS 7, the error '2772:106: An error occurred during internal plant hierarchy execution' encountered when attempting to create a new project using the PCS 7 New Project Wizard is caused by damaged Technological Hierarchy (TH) database templates, Microsoft SQL Server (WINCC instance) service interruption, or missing Windows user security permissions. The New Project Wizard relies on the Technological Hierarchy engine to create default area folders and OS containers. To resolve, verify that the logged-in Windows user belongs to the local 'Administrators' and 'SIMATIC HMI' user groups, confirm that the SQL Server (WINCC) service is running, and bypass the wizard by creating the Multiproject manually via 'File -> New -> Multiproject'. Alternatively, repair the PCS 7 Technological Hierarchy installation using the PCS 7 setup media.
Table of Contents
- Executive Summary
- Architecture and Fundamental Mechanics
- Step-by-Step Implementation Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Executive Summary
Engineers new to SIMATIC PCS 7 frequently encounter a frustrating roadblock during initial software evaluation: launching SIMATIC Manager and attempting to create a starter project via the 'PCS 7 'New Project' Wizard' halts abruptly with error code 2772:106 ('Internal plant hierarchy error'). Because the failure prevents the wizard from generating even an empty project scaffold, beginners assume the entire installation is broken. This technical article analyzes the background services required by the PCS 7 New Project Wizard, explains why Technological Hierarchy initialization fails, and provides the step-by-step procedures to bypass or permanently resolve the error.
Architecture and Fundamental Mechanics
The PCS 7 New Project Wizard relies on multiple underlying engineering services:
1. The Technological Hierarchy (TH) Architecture:
- PCS 7 projects are strictly organized around the Plant Hierarchy (PH / TH), structuring control logic into Areas, Units, and Equipment Modules.
- The Technological Hierarchy is an independent software component (S7THAX.DLL / S7JTH.EXE) that maintains relational folder mappings and binds CFC charts to WinCC picture trees.
2. Wizard Execution Mechanics and SQL Dependency:
- When the New Project Wizard runs with 'PCS 7 OS' checked, it does not merely create folder directories; it instantiates an S7 Program, creates hierarchical Plant Hierarchy folders, and initiates a Microsoft SQL Server database for the WinCC OS.
- If the local Microsoft SQL Server (WINCC) service is stopped, disabled, or locked by antivirus software, the wizard cannot create the underlying database tables, throwing error 2772:106.
3. Windows User Group and Security Rights:
- Creating and registering plant hierarchy databases requires elevated operating system privileges.
- The active user must belong to local Windows groups:
a. Administrators
b. SIMATIC HMI
c. Siemens TIA Engineer
- If a standard user without SIMATIC HMI rights runs the wizard, database registration fails.
Step-by-Step Implementation Procedure
-
Verify Windows User Security Groups:
a. Open WindowsComputer Management(runcompmgmt.msc).
b. Navigate toLocal Users and Groups -> Groups.
c. Inspect the Administrators and SIMATIC HMI groups.
d. Confirm that your current Windows user account is a member of both groups.
e. If newly added, Log off Windows and log back in to apply the updated security token. -
Verify Microsoft SQL Server (WINCC) Service State:
a. Open WindowsServices(runservices.msc).
b. Locate the service SQL Server (WINCC).
c. Confirm that the service status is Running and Startup Type is Automatic.
d. If stopped, right-click and selectStart. Also verifySQL Server Browseris running. -
Bypass Wizard by Creating Multiproject Manually:
a. Open SIMATIC Manager.
b. Close the New Project Wizard if it opens automatically.
c. From the main menu, selectFile -> New....
d. In the 'New Project' dialog, switch to the Multiproject tab.
e. Name the project (e.g.,Plant_Master_MP) and choose a local directory (e.g.,C:\Siemens\Step7\s7proj).
f. Click 'OK' to create an empty Multiproject scaffold. -
Manually Insert Project and Plant Hierarchy:
a. In SIMATIC Manager, select the Multiproject node.
b. SelectInsert -> Multiproject -> Create in Multiproject....
c. Create a standard User Project (e.g.,Plant_AS_Prj).
d. In the newly created project, right-click and selectInsert New Object -> SIMATIC 400 Station.
e. Right-click the project and selectInsert New Object -> Plant Hierarchy -> Hierarchy Folder.
f. Confirm that the Plant Hierarchy folder creates cleanly without error 2772:106. -
Repair Technological Hierarchy (TH) Installation (If Error Persists):
a. If manual hierarchy folder creation also throws errors, mount the PCS 7 installation media.
b. RunSetup.exeand select 'Modify / Repair'.
c. Select the component Technological Hierarchy (TH) and complete the repair installation.
d. Restart the computer.
Verification
- In SIMATIC Manager, open the manually created Multiproject: verify that Plant Hierarchy folders can be inserted and renamed.
- Insert a new CFC chart inside a Plant Hierarchy folder: confirm the chart opens in CFC Editor without database alerts.
- Run the PCS 7 New Project Wizard: confirm it completes successfully, creating an AS station, OS station, and plant hierarchy scaffold without error 2772:106.
Limitations and Operational Precautions
Never store PCS 7 projects on mapped network drives, USB flash drives, or cloud-synced folders (OneDrive, Dropbox). Projects must reside on local physical NTFS drives with short path lengths.
Engineer FAQ
What causes error 2772:106 when creating a new PCS 7 project?
It is caused by Microsoft SQL Server (WINCC) being stopped, damaged Technological Hierarchy database templates, or missing SIMATIC HMI user permissions.
Can I create a PCS 7 project without using the New Project Wizard?
Yes. You can manually create a Multiproject via File -> New -> Multiproject, and manually insert AS stations, OS stations, and Plant Hierarchy folders.
What Windows user groups are required to create PCS 7 projects?
The user must belong to local Administrators and the SIMATIC HMI user group.
Why does PCS 7 require Microsoft SQL Server for project creation?
The WinCC OS component created by the wizard requires SQL Server to build runtime and configuration databases.
Can PCS 7 projects be saved on network shares?
No. PCS 7 projects must be stored on local NTFS hard drives; storing on network drives causes database locking errors.
Technical References
- SIMATIC Process Control System PCS 7 Engineering System Manual
- SIMATIC PCS 7 Plant Hierarchy Configuration Manual
- Siemens Industry Online Support Entry 109780813 (PCS 7 Installation and User Rights Guidelines)
Related Articles
- Technical Differences Between PLC Configure and PLC Download for PC Stations in SIMATIC Manager
- Resolving PCS 7 V9.0 SP1 Chart Compilation Error 4297:15613 Following Safety Block Insertion
- Impact Analysis and Execution Guidelines for Mass Moving CFC Charts
Related Tags
- Error 2772:106
- Plant Hierarchy
- Technological Hierarchy
- New Project Wizard
- SIMATIC HMI
- SQL Server