Resolving Ghost Station Names ('OS_BOA') in WinCC Runtime Tag Logging and Archive Selection
The appearance of an unfamiliar station name such as 'OS_BOA' in the WinCC Runtime Selection of Archives/Tags on a Single Station system is caused by residual server data packages (.pck), obsolete computer names in the WinCC Computer Editor, or leftover metadata from a cloned project or previous multi-user engineering setup. In WinCC Explorer, open 'Server Data', delete any obsolete or orphaned server data packages, verify under the 'Computer' editor that only the local workstation name is defined as a server, and execute a full project save and reorganization to purge ghost station entries from the internal WinCC SQL database.
Table of Contents
- Why Ghost Stations Appear in WinCC Tag Logging Dialogs
- The Role of Server Packages and Project Cloning Residuals
- Auditing Computer Editor and Server Data in WinCC Explorer
- Step-by-Step Procedure to Remove Ghost Archive Servers
- WinCC Station Registration and Metadata Comparison
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Why Ghost Stations Appear in WinCC Tag Logging Dialogs
In SIMATIC PCS 7 and WinCC, operators and engineers accessing archive trend controls, user archives, or report generators interact with the Selection of Archives/Tags dialog. This dialog populates its tree view by querying the internal WinCC configuration database for registered archive providers.
In a Single Station system where the project is named OS_RMS, an engineer may be startled to find a second server listed, such as OS_BOA, containing duplicate or empty archive structures. Even though OS_BOA does not physically exist on the plant network, WinCC treats it as an active archive source, confusing operators and cluttering runtime trend selection screens.
The Role of Server Packages and Project Cloning Residuals
This defect typically originates from one of three engineering workflows:
-
Cloned or Migrated Project Baseline: The current project was originally cloned from another facility, demo project, or older engineering multiproject where
OS_BOAwas a server node or client. -
Orphaned Server Data Packages: In WinCC Explorer under Server Data, a server package (
OS_BOA.pck) was loaded at some point in the past. Even if the remote PC is disconnected, WinCC retains the package definitions in the SQL Server tablesCC_AlgServerDataandCC_TagServerData. -
Multi-Station Computer Editor Entries: If someone created a client or server computer object named
OS_BOAunder the WinCC Computer editor, the runtime window manager assumes a distributed system.
Auditing Computer Editor and Server Data in WinCC Explorer
To determine where the ghost station is registered:
- Open WinCC Explorer directly on the OS station.
- Expand the Computer icon in the tree. On a Single Station project, only one computer name should exist: the exact Windows hostname of the local machine. If
OS_BOAis listed as a client or redundant partner, it must be removed. - Expand Server Data. If an entry named
OS_BOAexists, WinCC is actively importing tag logging and alarm logging dictionaries from that fictitious server package.
Step-by-Step Procedure to Remove Ghost Archive Servers
Follow this sequence to cleanly remove the ghost server:
- Deactivate WinCC Runtime: Completely exit runtime and close WinCC Explorer.
- Launch WinCC Explorer: Open the project in configuration mode.
- Delete Orphaned Server Packages: Expand Server Data. Right-click
OS_BOA, select Delete, and confirm the deletion. - Clean Computer Editor: Expand Computer. If
OS_BOAappears as an additional station, right-click and select Delete. - Clean Physical Packages Folder: In Windows File Explorer, browse to
<ProjectPath>\<OS_Directory>\Packages\. Delete any physical files namedOS_BOA.pckorOS_BOA.dcf. - Reset Project Type if Necessary: If the project was erroneously configured as a 'Multi-User Project', right-click the project root in WinCC Explorer, select Properties, and ensure the project type is set to Single-User Project.
- Recompile OS: In SIMATIC Manager, perform an OS Compile (Changes only) to update the runtime database.
WinCC Station Registration and Metadata Comparison
The following table compares where station names reside in WinCC and how they impact archive selection:
<Project>\Packages\*.pckCC_Config_...\MCACHEPATHVerification
Verify that the ghost server has been eradicated through the following steps:
- Activate WinCC Runtime on the OS station.
- Open a graphic picture containing the WinCC Online Trend Control.
- Open the trend properties dialog, select Tag / Archive Selection, and expand the archive tree.
- Verify that only the true project server
OS_RMSis listed and thatOS_BOAhas vanished completely. - Confirm that archive tags log and display data normally without communication errors in WinCC Channel Diagnosis.
Limitations and Operational Precautions
Consider these operational rules when managing WinCC project metadata:
-
Never Edit SQL Server Tables Directly: Do not attempt to delete rows manually from SQL Server database tables via SQL Server Management Studio; always use the WinCC Explorer interface to ensure relational integrity.
-
Multi-Client Warning: If the system is actually a multi-client OS station that queries multiple real OS Servers, ensure you do not delete legitimate server packages required for plant operations.
-
Backup Before Deletion: Create a project backup using the WinCC Project Duplicator or SIMATIC Manager Archive before removing computer and package objects.
Engineer FAQ
Where does WinCC store the server package files on disk?
Server package files are stored in the project subfolder <OS_Project_Directory>\Packages\ with the extension .pck.
Can an OS Client access archives without a server package?
No, OS Clients require server packages to discover which OS Server hosts the Tag Logging and Alarm Logging databases.
What happens if two computers have the same name in the WinCC Computer Editor?
WinCC will reject the project startup or trigger runtime licensing conflicts, warning that the local computer name is not registered.
Technical References
- SIMATIC Process Control System PCS 7 OS Process Control Manual (Entry ID: 109780813)
- WinCC V7.3 / V7.4 System Manual: Server Data and Multi-User Architectures
- SIMATIC PCS 7 Engineering System Compendium Part A - Configuration Guidelines
- Siemens Technical Guidelines: Managing Computer Names and Packages in WinCC
Related Articles
- Resolving OS Compilation Error 302:309: Server Data Unable to be Created
- Configuring Multi-Client OS Stations with Cross-Multiproject Access
- Managing System @ Pictures in SIMATIC PCS 7 WinCC: OS Project Editor
Related Tags
- WinCC Tag Logging
- Server Data
- Ghost Station
- Single Station
- PCK File
- Computer Editor