Resolving Greyed Out OS Server Assignment in SIMATIC Manager OS Clients
In SIMATIC PCS 7 multiprojects, the checkbox to assign an OS Server to an OS Client being greyed out or unselectable in SIMATIC Manager (under 'Assign OS Server...') occurs when the target OS Server has not generated its Server Data package (*.pck) or when project path relocation invalidated package pointers. OS Clients require server data packages to resolve remote tags, alarms, and picture trees. To resolve this issue, right-click the OS Server's WinCC Application in Component View, select 'Generate server data' (or recompile the OS with server data generation enabled), return to the OS Client, and assign the now-selectable server package.
Table of Contents
- Client-Server Architecture and Server Data Packages (*.pck)
- Root Causes of Greyed-Out Server Assignment Checkboxes
- Client-Server Engineering Workflow and Package Status Matrix
- Step-by-Step Procedure to Generate Server Data and Assign Clients
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Client-Server Architecture and Server Data Packages (*.pck)
In a SIMATIC PCS 7 distributed architecture, Operator Stations operate in a multi-client client-server relationship. Dedicated OS Servers interface directly with automation controllers (AS) to acquire process tags, manage alarms, and log trends. OS Clients (WinCC Appl. Client) do not communicate directly with PLCs; they display graphics, trends, and faceplates by querying data through their assigned OS Servers.
To establish this connection, the OS Client requires a Server Data Package (<Project_Name>.pck). The package is an exported database descriptor containing server network names, database IDs, available archive tags, and message class definitions. Without a valid server data package, an OS Client cannot bind to an OS Server.
Root Causes of Greyed-Out Server Assignment Checkboxes
When an engineer right-clicks an OS Client in SIMATIC Manager and selects Assign OS Server..., the dialog displays all available server packages across the multiproject. If the checkbox for the target server is greyed out or missing:
- Uncompiled Server Data: The OS Server has never generated its server data, or the existing
.pckfile was deleted during project maintenance. - Project Path Relocation: If the multiproject was moved to a new drive letter or renamed without regenerating server data, the internal path pointer in SIMATIC Manager points to an invalid directory, forcing the UI to disable the checkbox.
- Uncompiled OS Server: If the OS Server project contains uncompiled changes (indicated by an orange station icon), the system disallows assigning uncompiled packages to clients.
Client-Server Engineering Workflow and Package Status Matrix
The table below contrasts OS Server data states, file extensions, and client assignment behaviors in SIMATIC Manager:
<Server_Name>.pck<OS_Server_Path>\packages\.pckWinCC Appl. Client.pck packages.Step-by-Step Procedure to Generate Server Data and Assign Clients
- Generate Server Data on OS Server:
- In SIMATIC Manager, switch to Component View.
- Locate the target OS Server PC Station -> expand to theWinCC Applicationobject.
- Right-click the OS Server object -> select Generate server data.
- Confirm execution: SIMATIC Manager compiles server definitions and generates the.pckfile in the OS project folder. - Verify Server Package Creation:
- Open Windows Explorer: navigate to<Multiproject>\<OS_Server_Folder>\packages.
- Confirm the presence of<Server_Project_Name>.pckwith the current system timestamp. - Assign Server Package to OS Client:
- In SIMATIC Manager Component View, navigate to the OS Client PC Station.
- Right-click the OS Client object -> select Assign OS Server....
- In the Assignment dialog, the checkbox for the target OS Server is now fully enabled.
- Check the checkbox next to the target OS Server and click OK. - Configure Standard Server (If Multi-Server Project):
- Open WinCC Explorer on the OS Client.
- In the tree, right-click Server Data -> Standard Server....
- Define standard server defaults for Alarms and Split Screen Wizard if multiple OS Servers exist. - Download OS Client: Execute
PLC -> Downloadfrom SIMATIC Manager to transfer the updated client configuration.
Verification
Verify client-server integration through the following steps:
1. In SIMATIC Manager, reopen Assign OS Server... on the OS Client: confirm that the target OS Server displays a solid green checkmark.
2. Open WinCC Explorer on the OS Client: expand Server Data: confirm that the OS Server package is loaded.
3. Activate WinCC Runtime on the OS Client: verify that process screens open seamlessly, displaying live tags and alarms streamed from the OS Server without server connection errors.
Limitations and Operational Precautions
Whenever an OS Server undergoes an AS-OS compilation that adds new process tags or modifies alarm classes, server data is regenerated. In redundant OS Server architectures, ensure that server data generation reflects both redundant partners (Master and Standby). Crucially, downloading updated server data packages to an OS Client does not require restarting the active OS Servers, ensuring continuous plant visibility during client updates.
Engineer FAQ
Technical References
- SIMATIC PCS 7 OS Process Control System - Operator Station Configuration Manual
- SIMATIC WinCC V7.4 System Manual - Client/Server Systems
- Siemens Technical Support: Configuring OS Clients and Server Data in PCS 7 (SIOS Entry ID 109748966)
Related Articles
- Resolving Database Context Does Not Exist Error During PCS 7 OS Download
- Configuring PC Stations in Station Configuration Editor and NetPro for OS Downloads
- Troubleshooting WinCC Redundancy Error 410E and Plant Bus Connection Drops
Related Tags
- OS Client
- OS Server
- Server Data
- Assign OS Server
- WinCC Client
- PCS 7 Engineering