Resolving 'Initialization Failed' on SIMATIC WinCC Explorer Launch in PCS 7 V8.1
The error 'Initialization failed' upon opening SIMATIC WinCC Explorer in PCS 7 V8.1 typically indicates an incompatible Microsoft Windows security patch (such as Meltdown/Spectre updates KB4056897 or KB4056894), a stopped Microsoft SQL Server instance (MSSQL$WINCC), missing Windows user group assignments, or a broken AS/OS Engineering component installation. To resolve the issue, install the latest Siemens PCS 7 V8.1 SP1 update (Upd9 or higher) or WinCC V7.3 Upd14 to restore DCOM/RPC compatibility, verify that the 'MSSQL$WINCC' Windows service is started, and ensure the active user belongs to the 'SIMATIC HMI' and 'SQLServerMSSQLUser$$WINCC' local groups.
Table of Contents
- WinCC Explorer Initialization Architecture
- Impact of Microsoft Windows Security Patches (Meltdown/Spectre)
- Microsoft SQL Server Instance Verification
- Windows User Group Permissions and DCOM Hardening
- Step-by-Step Diagnostic and Remediation Workflow
- Troubleshooting Matrix for WinCC Explorer Startup Failures
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
WinCC Explorer Initialization Architecture
When SIMATIC WinCC Explorer (WinCCExplorer.exe) launches, it initializes several core runtime subsystems before displaying the project tree:
- Component Object Model (COM) Registration: Binds to internal WinCC COM servers (
CCProjectMgr.exe,CCClient.dll). - Microsoft SQL Server Connection: Connects to the local database instance
MSSQL$WINCCusing Windows authentication. - STEP 7 Integration Layer: In a PCS 7 engineering environment, queries the AS/OS Engineering COM interfaces to determine multiproject association.
If any of these subsystems fail to respond within the startup timeout window, WinCC Explorer aborts with the modal dialog Initialization failed.
Impact of Microsoft Windows Security Patches (Meltdown/Spectre)
In early 2018, Microsoft issued urgent operating system security patches addressing speculative execution vulnerabilities (Meltdown and Spectre, such as KB4056897, KB4056894, and cumulative rollups for Windows 7 / Server 2008 R2). These updates introduced strict kernel memory isolation and altered internal DCOM/RPC security boundaries.
In unpatched releases of WinCC V7.2 and V7.3 (PCS 7 V8.1), these Windows updates blocked the internal RPC communication between WinCCExplorer.exe and the WinCC database management service, triggering immediate Initialization failed errors. Siemens resolved this across SIMATIC PCS 7 by issuing dedicated compatibility updates (PCS 7 V8.1 SP1 Upd9 and WinCC V7.3 Upd14).
Microsoft SQL Server Instance Verification
WinCC cannot initialize if its underlying database engine is inaccessible:
- Open Windows Services (
services.msc) and locate the service named SQL Server (WINCC) (MSSQL$WINCC). - Verify that the service status is Running and Startup type is Automatic.
- If the service is stopped or crashes upon startup, inspect the SQL Server error logs located at
C:\Program Files\Microsoft SQL Server\MSSQL11.WINCC\MSSQL\Log\ERRORLOG.
Windows User Group Permissions and DCOM Hardening
WinCC requires strict membership in local Windows security groups created during installation:
- Open Computer Management (
compmgmt.msc) and navigate to Local Users and Groups > Groups. - Confirm that the currently logged-on user account is an explicit member of:
1.SIMATIC HMI
2.SIMATIC NET
3.SQLServerMSSQLUser$<ComputerName>$WINCC - If the user account was recently added or modified, a complete Windows sign-out or computer restart is mandatory to re-issue the Windows security access token.
Step-by-Step Diagnostic and Remediation Workflow
Follow this sequential troubleshooting procedure:
- Check Windows Installed Updates:
- In Control Panel > Programs and Features > View installed updates, check for recently installed security KBs. - Apply Siemens Compatibility Updates:
- Install the latest Cumulative Update for PCS 7 V8.1 (SIOS Entry ID 18752994 / 109756832). - Reset WinCC Communication Cache:
- Open a command prompt as Administrator and executeCCResetCC.vbsfrom the WinCC bin folder (C:\Program Files (x86)\Siemens\WinCC\bin). - Re-register Core COM DLLs:
- Run the Siemens toolRegister-DLL.bator reinstall the AS/OS Engineering setup package from the PCS 7 installation media.
Troubleshooting Matrix for WinCC Explorer Startup Failures
The table below correlates root causes with diagnostic indicators and remedies:
Verification
Confirm successful resolution of WinCC Explorer startup:
- Click the Windows Start menu and launch SIMATIC WinCC Explorer.
- Confirm that WinCC Explorer launches to its primary interface without displaying initialization errors.
- Open a sample or plant project; confirm that the Graphics Designer, Tag Management, and Alarm Logging editors load.
- Open SIMATIC Manager and verify that right-clicking an OS station and selecting
Open Objectlaunches WinCC Explorer seamlessly.
Limitations and Operational Precautions
Adhere to the following engineering precautions:
- Validate Windows Updates Prior to Deployment: Never enable automatic Windows Updates on production PCS 7 servers. Always verify update compatibility against the official Siemens Compatibility Tool before installing patches.
- Do Not Modify SQL Server Configuration: Do not alter SQL Server instance settings, database names, or collation settings directly via SQL Server Management Studio (SSMS), as this will permanently invalidate WinCC integration.
- Backup Projects Before Resetting: Always create a complete archive of the PCS 7 multiproject before running cleanup scripts or re-installing AS/OS components.
Engineer FAQ
Can I fix 'Initialization failed' by uninstalling the latest Windows update?
While temporarily rolling back the problematic Windows update will allow WinCC to launch, it leaves the system vulnerable to security exploits. The officially recommended solution is installing the Siemens update (e.g. WinCC V7.3 Upd14) which supports the security patch.
Why must the Windows user be in both SIMATIC HMI and SQL Server user groups?
The SIMATIC HMI group grants access to WinCC COM/DCOM interfaces and shared memory. The SQLServerMSSQLUser group grants database authentication rights to the local WinCC Microsoft SQL Server instance.
What does the CCResetCC.vbs script do?
CCResetCC.vbs terminates all lingering background WinCC processes (such as CCProjectMgr, CCHmiData, and CCClick) and cleans up orphaned shared memory handles, allowing WinCC to initialize cleanly.
Technical References
- Compatibility of Microsoft Security Patches with SIMATIC WinCC: SIOS Entry ID 18752994
- SIMATIC PCS 7 V8.1 Software Updates and Service Packs: https://support.industry.siemens.com/cs/ww/en/view/109756832
- WinCC V7.3 Installation and System Requirements Guide: https://support.industry.siemens.com/cs/ww/en/view/102601737
Related Articles
- Resolving WinCC OS Server Startup Failures and License Database Corruption
- Troubleshooting 'New Project Wizard' Failures to Launch in SIMATIC PCS 7
- Consequences of Duplicate Computer Names on OS Client and Server Stations
Related Tags
- WinCC V7.3
- PCS 7 V8.1
- Initialization Failed
- Microsoft SQL Server
- Security Patches
- SIMATIC HMI