Resolving Missing Hardware Descriptions for Fail-Safe Module 6ES7336-4GE00-0AB0 via S7 F-Configuration Pack
When the fail-safe analog input module SM 336 F-AI 6 x 0/4...20 mA HART (6ES7336-4GE00-0AB0) appears in STEP 7 HW Config without a description, cannot be inserted, or reports configuration errors under ET 200M (IM 153-2), the root cause is an outdated S7 F-Configuration Pack. Fail-safe signal modules do not derive parameter definitions from standard GSD files or STEP 7 Hardware Support Packages (HSP). To resolve the issue, install S7 F-Configuration Pack V5.5 SP7 or higher, ensure S7 F-Systems V6.0 is installed, and set the HW Config catalog profile to 'Standard' or the appropriate PCS 7 release profile.
Table of Contents
- Hardware Architecture of SM 336 F-AI HART Module
- Role of S7 F-Configuration Pack vs Standard GSD/HSP
- Why GSD Files Fail to Provide Safety Parameterization
- Step-by-Step Installation and Catalog Update Workflow
- Fail-Safe Software and Catalog Compatibility Matrix
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Hardware Architecture of SM 336 F-AI HART Module
The SIMATIC S7-300 / ET 200M SM 336 fail-safe analog input module (6ES7336-4GE00-0AB0) provides 6 fail-safe current inputs (0/4...20 mA) with integrated HART communication, supporting safety ratings up to SIL 3 / Cat. 4 / PL e according to IEC 61508 / ISO 13849. The module operates in centralized S7-300F racks or distributed ET 200M stations connected via IM 153-2 (6ES7153-2BA02-0XB0 or 6ES7153-2BA10-0XB0).
Unlike standard analog modules, fail-safe modules require complex safety parameter profiles including PROFIsafe addresses (F_Dest_Add), F-monitoring times, sensor evaluation (1oo1, 1oo2, 2oo3), discrepancy times, and channel-granular passivation settings that standard hardware catalogs cannot interpret.
Role of S7 F-Configuration Pack vs Standard GSD/HSP
Engineers attempting to integrate modern fail-safe modules into legacy engineering stations (e.g. PCS 7 V7.0 SP3 or STEP 7 V5.4/V5.5) often install general GSD files or run Tools > Install Hardware Updates (HSP). However:
- Standard Hardware Updates (HSP) only update standard automation modules and ET 200 interface modules.
- PROFIsafe Modules Require S7 F-Configuration Pack: The S7 F-Configuration Pack (
F-ConfigPack) contains the specialized parameter dialogs, safety checksum calculation routines, and safety property pages required by the S7 F-Systems engineering environment. - When an older F-ConfigPack (such as SP3) is installed, newly released module MLFBs like
6ES7336-4GE00-0AB0cannot be parsed. The module either fails to appear in the catalog, or appears as a raw hex identifier devoid of text descriptions.
Why GSD Files Fail to Provide Safety Parameterization
Installing an ET 200M GSD file (SIEM801E.GSD) into STEP 7 HW Config allows third-party PROFIBUS masters or standard configurations to recognize the rack. However, in native STEP 7 / PCS 7 S7 F-Systems installations, GSD-based slaves cannot execute native S7 F-Systems safety driver generation.
The S7 F-Systems compiler requires native STEP 7 slave object definitions so that the Safety Matrix and F-driver wizards can instantiate F_AI_HRT channel driver blocks and bind PROFIsafe telegrams directly to the safety program runtime groups.
Step-by-Step Installation and Catalog Update Workflow
Follow this procedure to properly install the module and restore complete hardware descriptions:
- Close All SIMATIC Applications: Close SIMATIC Manager, HW Config, CFC, and NetPro.
- Download S7 F-Configuration Pack:
- Download the latest compatible S7 F-Configuration Pack (e.g. V5.5 SP7, V5.5 SP11, or V5.5 SP13) from Siemens Industry Online Support. - Execute Installation:
- RunSetup.exewith administrative privileges.
- Confirm the installation target binds to the existing STEP 7 / PCS 7 installation directory. - Update HW Config Catalog:
- Open SIMATIC Manager and launch HW Config.
- SelectOptions > Update Catalog(Extras > Katalog aktualisieren).
- Under the hardware catalog window, locate the Profile dropdown.
- Switch the profile fromPCS7_V70(or legacy version) toStandardif the module does not appear under the legacy filter. - Insert Module:
- Navigate toPROFIBUS DP > ET 200M > IM 153-2 > SM-336 F-AI 6 x 0/4...20mA HART(6ES7336-4GE00-0AB0).
- Drag and drop the module into an available slot; verify that the full hardware description and parameter dialog tabs appear.
Fail-Safe Software and Catalog Compatibility Matrix
The table below details software compatibility requirements for fail-safe ET 200M modules:
Verification
Verify successful hardware detection and safety parameterization:
- In HW Config, double-click the inserted
6ES7336-4GE00-0AB0module. - Confirm that the Object Properties window opens with full descriptive tabs:
General,Addresses,Parameters, andF-Parameters. - In the
F-Parameterstab, verify thatF_Dest_AddandF_SILcan be assigned without error dialogs. - Execute
Station > Save and Compilein HW Config; ensure no syntax or parameter errors are generated. - In CFC, open an F-chart, instantiate the channel driver block (
F_CH_AI), and verify symbolic interconnection to the module input.
Limitations and Operational Precautions
Review the following technical precautions regarding fail-safe module integration:
- F-ConfigPack Compatibility: Always verify the compatibility of newer F-ConfigPack releases against the installed version of S7 F-Systems and operating system (Windows XP, Windows 7, or Windows 10).
- Catalog Profile Filtering: In PCS 7 engineering, filtering catalogs strictly by release profiles (e.g.
PCS7_V70) hides newer modules released after that PCS 7 version. Using modules under theStandardprofile requires verifying driver support. - Commercial Procurement Guardrail: When specifying fail-safe hardware, always verify exact MLFBs (
6ES7336-4GE00-0AB0) and ensure required isolation modules (6ES7195-7HA00-0XA0) and active bus modules are included in the hardware schedule.
Engineer FAQ
Can I use GSD files to configure the 6ES7336-4GE00-0AB0 in PCS 7 S7 F-Systems?
No. GSD files only provide standard fieldbus communication parameters and lack the PROFIsafe safety parameter dialogs and driver wizard hooks required by S7 F-Systems. The module must be configured using the native F-ConfigPack.
Why does the module appear under the 'Standard' catalog profile but not under 'PCS7_V70'?
The PCS7_V70 catalog profile is a restricted filter created when PCS 7 V7.0 was frozen. Modules released after that version are omitted from the filtered view. Selecting 'Standard' reveals all installed hardware.
Is SM 336-4GE00 supported in redundant ET 200M configurations?
Yes, SM 336 fail-safe modules can be installed in redundant ET 200M stations using active bus modules (6ES7195-7HA00-0XA0) with redundant IM 153-2 interface modules.
Technical References
- SIMATIC Automation Systems S7-300 Fail-Safe Signal Modules Manual: https://support.industry.siemens.com/cs/ww/en/view/12490443
- SIMATIC S7 F-Configuration Pack Download and Release Notes: https://support.industry.siemens.com/cs/ww/en/view/15208817
- SIMATIC S7 F-Systems - Configuring and Programming: https://support.industry.siemens.com/cs/ww/en/view/109780765
Related Articles
- Channel-Granular vs Module-Granular Passivation for Fail-Safe and High-Availability Modules in PCS 7
- Backward Compatibility and Driver Wizard Support for ET 200S Modules in Legacy PCS 7
- Configuring DP-PA Link and Field Instruments in SIMATIC PDM via S7-400 Routing
Related Tags
- 6ES7336-4GE00-0AB0
- F-ConfigPack
- S7 F-Systems
- ET 200M
- HW Config
- Fail-Safe Modules