Resolving Pcs7AnIn Process Value Scaling Shifts When NamurOff Is Enabled in PCS 7 V9.1

Resolving Pcs7AnIn Process Value Scaling Shifts When NamurOff Is Enabled in PCS 7 V9.1

In SIMATIC PCS 7 V9.0 SP3 through V9.1 SP2 UC1, setting NamurOff = 1 on the APL analog channel driver block Pcs7AnIn causes the output PV_Out.Value to display the full scale range instead of the scaled process value when connected to non 4-20mA signals (such as thermocouples, RTDs, or voltage inputs). This functional change stems from updated standardization algorithms; resolution requires maintaining NamurOff = 0 for temperature inputs or configuring the hardware driver Mode parameter to 16#202.

Table of Contents

Role of Pcs7AnIn and NAMUR NE43 Limit Monitoring

In SIMATIC PCS 7 Advanced Process Library (APL), the Pcs7AnIn block (FB1869) serves as the primary analog input channel driver:
* It reads raw 16-bit integer values from analog input modules (PIW), converts them to engineering units (REAL), applies quality code evaluation, and outputs the structured variable PV_Out.
* NAMUR NE43 Standard: Defines diagnostic failure levels for standard 4–20 mA current loops:
* Current between 3.8 mA and 20.5 mA is treated as valid measuring range.
* Current between 3.6 mA and 3.8 mA indicates measuring range undershoot.
* Current between 20.5 mA and 21.0 mA indicates measuring range overshoot.
* Current $< 3.6 ext{ mA}$ (wire break) or $> 21.0 ext{ mA}$ (short circuit) triggers bad signal status (ST = 16#00).
* The parameter NamurOff allows engineers to disable NAMUR evaluation for non-standard transmitters: setting NamurOff = 1 disables NE43 limits so signals across the entire raw converter range (0 to 27648) are scaled linearly.

Analysis of the Functional Change Between PCS 7 V9.0 SP2 and V9.1

In earlier library builds (PCS 7 V9.0 SP2 and prior):
* Setting NamurOff = 1 had no adverse effect on non 4–20 mA signals such as Resistance Temperature Detectors (RTD: Pt100/Ni1000) or Thermocouples (TC: Type J/K). The block correctly recognized temperature modes and scaled the reading according to the module's 0.1 °C resolution.
* Beginning in PCS 7 V9.0 SP3 and continuing into PCS 7 V9.1 SP2 UC1, Siemens corrected the standardization formula in Pcs7AnIn to address scaling inaccuracies when NamurOff = 1.
* The Side Effect: If NamurOff = 1 is inadvertently enabled on a thermocouple or RTD channel, the updated standardization algorithm bypasses temperature-specific scaling routines and applies the linear full-span formula:
$$ ext{PV_Out.Value} = ext{Scale.High} - ext{Scale.Low}$$
As a result, the faceplate and CFC output display a constant value representing the scale span (e.g., 100.0 or 500.0) rather than the live measured temperature.

Root Cause: Standardization Algorithm Response to NamurOff on Temperature Signals

The issue arises from how Pcs7AnIn interprets the combination of Mode and NamurOff:
* For RTD and Thermocouple modules, Siemens analog cards report temperature values directly in tenths of a degree (e.g., raw integer 250 corresponds to 25.0 °C).
* The driver determines signal processing using the Mode input parameter, typically populated automatically by the PCS 7 Driver Generator (Generate Module Drivers):
* Mode = 16#0201: 4–20 mA current with NAMUR NE43.
* Mode = 16#0202: Temperature measurement (RTD/TC standard).
* When NamurOff = 1 is forced, the internal logic treats the input as a generic unstandardized transmitter, ignoring the intrinsic 0.1 °C scaling and substituting the configured Scale difference.

Remediation Workflow: Parameterizing NamurOff and Mode for Non 4-20mA Channels

To restore correct temperature scaling on Pcs7AnIn instances in PCS 7 V9.1:
1. Reset NamurOff to Default (Recommended):
* In the CFC chart, locate all Pcs7AnIn blocks connected to RTD, Thermocouple, or direct voltage inputs.
* Verify the input parameter NamurOff.
* Set NamurOff = 0 (or FALSE).
* Because NAMUR NE43 applies exclusively to 4–20 mA current loops, setting NamurOff = 0 does not cause premature failure on temperature channels; the module's native wire-break diagnostics handle sensor faults.
2. Verify Module Driver Mode Interconnection:
* Ensure the Mode input pin of Pcs7AnIn is interconnected to the corresponding OMODE_xx output of the diagnostic driver block (MOD_D1, MOD_HA, or MOD_PA).
* In SIMATIC Manager, execute CFC -> Compile -> Changes Only with the checkbox Generate module drivers enabled.
* Confirm that the driver generator sets Mode = 16#0202 for temperature cards.
3. Download Changes to AS: Perform a delta download in RUN mode. The output PV_Out.Value immediately returns to the live temperature measurement.

Verification

  • In CFC dynamic test mode, inspect Pcs7AnIn.PV_Out.Value: verify that it displays the correct live temperature (e.g., 24.6 °C).
  • In WinCC OS runtime, open the analog monitoring faceplate (MonAnL): verify that the bar graph and digital readout match field calibration calibrators.
  • Disconnect the thermocouple lead in the field: verify that Pcs7AnIn.Bad asserts (Bad = 1), PV_Out.ST drops to 16#00, and the WinCC faceplate indicates a wire break.

Limitations and Operational Precautions

  • Never set NamurOff = 1 globally across all analog input blocks in a master data library; only apply NamurOff = 1 to specific 0–20 mA or non-NAMUR current loops.
  • If migrating a project from PCS 7 V9.0 to V9.1, review all analog input block parameters before commissioning to prevent undetected scale range freezes.
  • Disconnecting the Mode pin from the module driver generator prevents automatic detection of hardware card parameter changes.

Engineer FAQ

  • What is the primary purpose of the NamurOff parameter on Pcs7AnIn?
    It disables NAMUR NE43 limit monitoring (3.6 mA to 21 mA) for non-standard current loops, allowing full 0 to 27648 raw scaling.
  • Why did NamurOff = 1 work on thermocouples in PCS 7 V9.0 SP2?
    In V9.0 SP2, the standardization logic ignored the NamurOff setting when temperature mode was detected; V9.0 SP3 corrected the standardization algorithm, exposing this behavior.
  • What value should NamurOff have for RTD and Thermocouple sensors?
    It should always be set to 0 (default).
  • What raw integer value does an S7-400 RTD card output for 150.5 °C?
    The card outputs raw integer 1505 (representing temperature in tenths of a degree Celsius).
  • How does Pcs7AnIn know what type of hardware card is connected?
    Via the Mode parameter, which is automatically parameterized by the PCS 7 Driver Generator during compilation.
  • What does Mode = 16#0202 signify on Pcs7AnIn?
    It signifies a temperature measurement channel with standard RTD or Thermocouple linearization.
  • What happens to PV_Out if a thermocouple experiences a wire break?
    The analog card transmits raw value 16#7FFF, causing Pcs7AnIn to set Bad = 1 and PV_Out.ST = 16#00.
  • Can NamurOff be modified online in RUN mode?
    Yes, NamurOff is a dynamic block parameter that can be modified online without stopping the CPU.
  • Does Pcs7AnIn support custom thermocouple linearization curves?
    Linearization is handled in the hardware module; Pcs7AnIn scales the linearized values delivered by the card.
  • Where is the documentation for the V9.0 SP3 NamurOff correction published?
    In the official Siemens Readme for SIMATIC PCS 7 Advanced Process Library V9.0 SP3 under block improvements.

Technical References

  • SIMATIC PCS 7 Advanced Process Library (APL) Function Manual (V9.0 SP3 / V9.1)
  • Siemens Industry Online Support Entry: Pcs7AnIn Standardization and NamurOff (Entry ID 298924)
  • NAMUR NE43: Standardization of the Signal Level for the Failure Information of Digital Transmitters
  • SIMATIC S7-400 Automation System Module Data Manual