Installing SIMATIC PCS 7 Industry Library (IL) V9.1 SP1 on an Engineering Station running PCS 7 V9.1 SP2 fails when the base software package (SIMATIC PCS 7 Industry Library V9.1) has not been previously installed. Siemens service packs for Industry Library are delta update patches rather than full standalone installers. Because Industry Library is a commercial licensed product, the base V9.1 installation media cannot be downloaded for free from Siemens support and must be obtained via official purchase through the Siemens Industry Mall or Online Software Delivery (OSD).

Table of Contents

Commercial Licensing and Service Pack Architecture of Industry Library

The SIMATIC PCS 7 Industry Library (IL) expands the standard Advanced Process Library (APL) by providing dedicated technological blocks and HMI faceplates for building automation, food and beverage, water/wastewater, and Comfort Panel integration:
* Delta Patch vs. Full Installation Package:
* Downloadable packages on the Siemens Industry Online Support (SIOS) portal titled Service Pack 1 for SIMATIC PCS 7 Industry Library V9.1 are update-only installers.
* The installer inspects Windows registry keys under HKLM\SOFTWARE\Siemens\PCS7\IndustryLibrary. If the core base product IL V9.1 is absent, the installer aborts with an error stating that the prerequisite base version is missing.
* Commercial Procurement Policy:
* While standard PCS 7 Update Collections (UCs) and minor library bug fixes are freely downloadable for registered users with valid support access, the Industry Library base product is a commercial software package.
* Base installation media (DVD or OSD download) must be ordered through Siemens Industry Mall under article number 6DL5410-....
* Panel Integration Role:
* PCS 7 IL is critical when integrating SIMATIC Comfort Panels into a PCS 7 plant. It supplies WinCC Comfort/TIA Portal faceplate libraries and matching AS communication blocks (LBP_ blocks) designed to operate synchronously with S7-400 and S7-410 controllers.

Step-by-Step Procedure to Install Base IL and Service Packs

Follow this procedure to establish a compliant Industry Library installation on PCS 7 V9.1.

Prerequisites

  • SIMATIC PCS 7 V9.1 (or V9.1 SP2) already installed and functional.
  • Official installation media for SIMATIC PCS 7 Industry Library V9.1 Base.
  • Downloaded update package for SIMATIC PCS 7 Industry Library V9.1 SP1 (or SP2).
  • Administrative privileges on the Engineering Station.

Step 1: Install the Base Industry Library Software

  1. Mount the official installation DVD or ISO image for SIMATIC PCS 7 Industry Library V9.1.
  2. Run Setup.exe with administrative elevation.
  3. Select the required components:
    * IL for PCS 7 (AS and OS): Installs CFC block libraries and WinCC faceplates.
    * IL for WinCC Comfort / TIA Portal: Installs panel faceplate libraries.
  4. Follow the setup wizard to completion and reboot the computer when prompted.

Step 2: Install Industry Library Service Pack 1

  1. Extract the downloaded Industry Library V9.1 SP1 update archive.
  2. Launch Setup.exe as Administrator.
  3. The setup installer detects the existing IL V9.1 base installation and proceeds without prerequisite error dialogs.
  4. Complete the installation and reboot the system.

Step 3: Install Required License Keys

  1. Launch Automation License Manager (ALM).
  2. Transfer the following license keys to the local drive:
    * SIMATIC PCS 7 Industry Library Engineering
    * SIMATIC PCS 7 Industry Library Runtime (for each target AS controller).
  3. Confirm status Valid in ALM.

Step 4: Integrate Blocks into PCS 7 Master Data Library

  1. In SIMATIC Manager, open File -> Open -> Libraries.
  2. Open the PCS 7 Industry Library V9.1.
  3. Copy the required technological blocks into your project's Master Data Library.
  4. In SIMATIC Manager, select Options -> Block Types and transfer the blocks to your AS chart folders.

Verification

  • In SIMATIC Manager, open Help -> About -> Installed Software. Verify that SIMATIC PCS 7 Industry Library appears with version V9.1 SP1.
  • In CFC, open a chart, insert an Industry Library block (e.g., LBP_OpAnalog or LBP_MotL), and verify that compilation completes with 0 errors.
  • Open WinCC Explorer: verify that Industry Library graphics and faceplate files appear in the GraCS folder.
  • Open Automation License Manager: verify that the IL engineering license is actively booked.

Limitations and Operational Precautions

  • AS Runtime Licensing: Each automation station executing Industry Library blocks requires an AS Runtime License. Exceeding licensed controller counts triggers non-compliance licensing popups.
  • TIA Portal Version Alignment: When using IL for Comfort Panels, the installed Industry Library version on the TIA Portal engineering PC must match the IL block version on the PCS 7 Engineering Station.
  • Do Not Mix Incompatible Service Packs: Do not install Industry Library V9.0 service packs on PCS 7 V9.1; library interfaces are strictly tied to specific PCS 7 core versions.

Engineer FAQ

  • Why can't I download the base version from Siemens Support?
    Base releases of Siemens add-on libraries (such as Industry Library, CEMAT, and BATCH) are commercial software products requiring purchase; only delta service packs and bug fix updates are hosted on public support pages.
  • Can Industry Library blocks run alongside standard APL blocks?
    Yes. Industry Library is built directly upon the APL framework and follows identical design rules, color palettes, and interlocking principles.
  • Can an MP 277 panel use Industry Library?
    No. Industry Library panel faceplates are designed specifically for modern SIMATIC Comfort Panels engineered in TIA Portal WinCC Comfort.
  • Is Industry Library compatible with PCS 7 V9.1 SP2?
    Yes. Industry Library V9.1 SP1 is fully compatible with PCS 7 V9.1 SP2. Check SIOS for subsequent update collections (e.g., IL V9.1 SP1 Upd1).
  • What components are included in the IL package?
    The package includes AS blocks for S7-400/410, WinCC faceplates for OS runtime, and TIA Portal global library faceplates for Comfort Panels.

Technical References

  • Siemens Industry Online Support Entry ID 109801081: Delivery Release - SIMATIC PCS 7 Industry Library V9.1.
  • Siemens System Manual: SIMATIC PCS 7 Industry Library Function Manual and Panel Integration.
  • Siemens Industry Mall: Product Catalog for SIMATIC PCS 7 Add-on Packages.

Related Articles

Related Tags

  • PCS 7
  • Industry Library
  • Service Pack
  • Comfort Panel
  • Licensing
  • APL
  • Installation
  • Industrial Automation
20 respuestas