Resolving Process Object View Error 300 - 14 Database Disconnection in SIMATIC PCS 7
In SIMATIC PCS 7 (V9.0 SP3 / V9.1), opening or browsing the Process Object View (POV) that aborts with Error (300:14) 'The application has no connection to the database' is caused by desynchronized IPC pipe connections or broken socket handles between STEP 7 and the underlying Sybase SQL Anywhere database engine. This condition frequently occurs after resuming suspended virtual machines (VMware/Hyper-V) or following sudden network disconnects. To resolve this, terminate orphaned database processes ('s7ussapx.exe', 'dbeng*.exe'), perform a full computer restart, and execute 'Save As... with Reorganization (slow)' on the multiproject.
Table of Contents
- Executive Summary
- Architecture and Fundamental Mechanics
- Step-by-Step Implementation Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Executive Summary
Process Object View (POV) is the central engineering workbench in SIMATIC PCS 7 for bulk parameterization, signal interconnection, and hierarchy management across large multiprojects. During engineering sessions, particularly on virtualized engineering stations (e.g., VMware Workstation, ESXi, or Microsoft Hyper-V), engineers occasionally encounter a sudden failure: selecting a chart, hierarchy folder, or parameter tab halts with the error dialog: Process Object View (300:14): The application has no connection to the database.
This error occurs because STEP 7 relies on an embedded Sybase SQL Anywhere database server engine to manage the engineering data dictionary. When a host virtual machine is suspended (paused) and later resumed, or when network shares experience temporary dropouts, the active inter-process communication (IPC) pipe between the SIMATIC Manager front-end and the local database server breaks. The client process cannot re-establish authentication against the existing database session, locking out the project. This guide outlines the immediate recovery steps, process termination rules, and project reorganization procedures required to eliminate Error 300:14.
Architecture and Fundamental Mechanics
The STEP 7 and Process Object View architecture utilizes a client-server relational database model behind the graphical interface:
-
The Sybase SQL Anywhere Relational Engine:
- Behind the STEP 7 project directory structure (*.s7p,*.mcp), project cross-references, block parameters, and hierarchy definitions are stored in Sybase SQL Anywhere databases (.dband transaction log.logfiles).
- The database server executable (dbeng*.exeordbsrv*.exe) runs locally or as a background service.
- Communication between the engineering application (s7tgtopx.exe,s7ussapx.exe) and the database engine occurs via local Named Pipes or loopback TCP sockets. -
The Suspension / Resumption Disconnect Trap:
- When a virtual machine hosting PCS 7 is suspended, the OS kernel freezes memory state and CPU execution.
- Upon resuming the VM, Windows network sockets and local IPC pipe handles frequently experience desynchronization: the database server process registers an abandoned client connection, while the client application attempts to reuse stale socket handles.
- When Process Object View executes a SQL query to load block instances, the request fails, triggering exception code(300:14): The application has no connection to the database. -
Database Locking and Stale Lock Files:
- If SIMATIC Manager is forcibly closed while the database connection is broken, lock files (e.g., temporary.ldf,.dcf, or Sybase lock structures) remain on disk.
- Subsequent attempts to reopen the project encounter locked tables, perpetuating the disconnection error until the database engine is completely restarted and caches are purged.
Step-by-Step Implementation Procedure
Follow these steps to recover from Error (300:14) and restore Process Object View access:
-
Close SIMATIC Applications:
- Close Process Object View, CFC Editor, SFC Editor, and SIMATIC Manager.
- If any window hangs or refuses to close, use Task Manager to terminate the unresponsive applications. -
Terminate Orphaned Database and STEP 7 Processes:
- PressCtrl + Shift + Escto open Windows Task Manager.
- Switch to the 'Details' tab.
- Look for and terminate any lingering instances of the following processes:s7ussapx.exe(Process Object View server)s7tgtopx.exe(AS-OS / CFC compiler engine)dbeng*.exe/dbsrv*.exe(Sybase SQL Anywhere database engine)CCDataMgr.exe/WinCC*(if WinCC components were active)- Right-click each process and select 'End task'.
-
Restart the Operating System:
- Perform a complete, clean restart of Windows (do NOT use suspend, hibernate, or fast startup).
- Rebooting releases all locked file handles, resets named pipes, and guarantees a pristine network socket environment. -
Reopen and Reorganize the Multiproject:
- After rebooting, launch SIMATIC Manager.
- Open the multiproject.
- Select 'File > Save As...'.
- In the 'Save As' dialog, check the radio button 'with Reorganization (slow)'.
- Specify a new project target directory and click 'OK'.
- Allow the reorganization to sweep the Sybase database tables, rebuild indices, and remove corrupted cross-reference pointers. -
Verify Process Object View Functionality:
- Open the newly reorganized project.
- Navigate to 'View > Process Object View' (or pressCtrl + Alt + P).
- Browse through the plant hierarchy, CFC charts, and parameters to confirm that data loads without error.
Verification
- In SIMATIC Manager, open Process Object View: verify that all tabs ('General', 'Blocks', 'Parameters', 'Signals', 'Messages') load data seamlessly.
- Filter by hierarchy folder: confirm that charts and blocks populate without delay.
- Make a test parameter change in POV (e.g., modify an alarm limit comment) and click 'Save': verify that the change commits cleanly to the database.
- Perform a consistency check ('Options > Plant Hierarchy > Check Consistency'): confirm zero database connectivity errors.
Limitations and Operational Precautions
Never suspend or pause virtual machines running SIMATIC PCS 7 while online monitoring, AS-OS compiling, or database editing is active; always shut down the guest operating system cleanly. In VMware environments, disable VMware Shared Folders on project directories to avoid file-locking conflicts. System licenses and engineering station configurations should be verified through an authorized Siemens distributor or the Siemens Industry Mall.
Engineer FAQ
What causes Error (300:14) in Process Object View?
Broken IPC named pipes or socket communication between the STEP 7 engineering interface and the local Sybase SQL Anywhere database engine.
Why does this error frequently occur after resuming a VMware virtual machine?
Suspending and resuming freezes and unfreezes the OS, causing network socket timeouts and broken inter-process database handles.
Does 'Save As with Reorganization (slow)' repair the database?
Yes. It rebuilds internal Sybase database pages, purges obsolete cross-reference records, and repairs index tables.
Can I prevent this error on virtualized engineering stations?
Yes, by always cleanly shutting down the guest OS instead of suspending the VM, and avoiding dynamic network adapter changes while STEP 7 is open.
What background process manages Process Object View?
s7ussapx.exe manages Process Object View application services.
Technical References
- SIMATIC Process Control System PCS 7 Engineering System (V8.2 / V9.0 / V9.1) Manual
- SIMATIC Process Object View User Guide
- Siemens Industry Online Support FAQ 109749318 - Resolving Database Connection Errors in STEP 7
Related Articles
- Managing and Bulk-Deleting Plant Hierarchy Folders Across Multiprojects in PCS 7 Process Object View
- Resolving Error 15124 During OS Compile After Renaming an S7 CPU in PCS 7
- Resolving PCS 7 V8.0 SP2 Installation Errors 0xc0000006 and SQL Bootstrapper Crash on VMware
Related Tags
- Process Object View
- Error 300:14
- Database Connection
- Sybase SQL
- VMware
- PCS 7 V9.0 SP3