Resolving Process Object View Grid Malfunctions in Parameters and Signals Tabs
The malfunction in SIMATIC PCS 7 Process Object View (POV) where the Signals tab incorrectly displays parameters instead of I/O signals occurs when the serialized grid view state in the Windows User Registry becomes corrupted or when operating under an uncertified Windows 10 build (such as Windows 10 Enterprise 2016 LTSB on baseline PCS 7 V9.0). To resolve this, close SIMATIC Manager and delete the corrupted registry layout key under HKEY_CURRENT_USER\Software\Siemens\STEP 7\2.0\Applications\s7thapax, reset POV view filters to Standard, and install SIMATIC PCS 7 V9.0 Service Pack 1 to ensure full table compatibility.
Table of Contents
- Process Object View Architecture and Registry View State Caching
- Root Causes: Registry View Corruption and Windows 10 Build Incompatibility
- Diagnostic Matrix for Process Object View Grid Failures
- Step-by-Step Procedure to Clear POV Registry Cache and Restore Tabs
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Process Object View Architecture and Registry View State Caching
In SIMATIC PCS 7, the Process Object View (POV) (s7thapax.exe) provides a multi-tab engineering spreadsheet allowing bulk manipulation of automation assets. Each tab (General, Blocks, Parameters, Signals, Messages, Picture Objects, Archive Tags) queries specific database schemas inside the STEP 7 project.
To provide a consistent user experience, POV serializes user interface customizations—such as adjusted column widths, column visibility, custom sorting, and active filter criteria—into the Windows Registry under the current user's profile (HKEY_CURRENT_USER). On every application launch, POV reconstructs its GUI grid according to these cached binary registry keys.
Root Causes: Registry View Corruption and Windows 10 Build Incompatibility
Two compounding issues trigger the corruption where the Signals tab displays the Parameters schema:
- Corrupted Registry Grid Serialization: When SIMATIC Manager terminates abnormally (system crash, forced Task Manager end-task, or power dip), the binary serialization stream written by
s7thapax.exeis truncated. The column pointer array for theSignalstab becomes misaligned, causing the grid controller to map the cached schema of Tab 3 (Parameters) onto Tab 4 (Signals). Because this is stored in the user profile, the defect persists across all projects. - Unreleased Windows 10 Editions: Baseline SIMATIC PCS 7 V9.0 was certified exclusively for Windows 10 Enterprise 2015 LTSB. Running baseline V9.0 on Windows 10 Enterprise 2016 LTSB or newer SAC builds induces Microsoft Common Controls (
comctl32.dll) rendering bugs. Siemens formally resolved these grid control defects in PCS 7 V9.0 SP1.
Diagnostic Matrix for Process Object View Grid Failures
The table below details symptoms, root causes, and corrective actions for Process Object View grid malfunctions:
HKCU\...\Applications\s7thapaxView -> Filter -> Standard / Reset.View -> Filter -> Clear Filter.Step-by-Step Procedure to Clear POV Registry Cache and Restore Tabs
- Close All Siemens Engineering Applications:
- Save your work and exit SIMATIC Manager, CFC, and WinCC Explorer.
- Open Windows Task Manager: ensure processess7tgtopx.exeands7thapax.exeare completely terminated. - Delete Corrupted POV Registry Settings:
- Open the Windows Registry Editor (regedit.exe) as the active user.
- Navigate to the following path:
text HKEY_CURRENT_USER\Software\Siemens\STEP 7\2.0\Applications\s7thapax
- Right-click the keys7thapax(or its sub-keysSettings/View) and select Delete.
- Note: Deleting this key does not alter project engineering data; it simply clears cached column layout preferences. - Relaunch SIMATIC Manager and Reset Filters:
- Open SIMATIC Manager and open your multiproject.
- Open Process Object View: selectView -> Filter...-> click Standard (Reset Defaults).
- Select the Signals tab: confirm that the grid cleanly populates with peripheral addresses, signal names, and I/O directions. - Upgrade to PCS 7 V9.0 SP1 (Preventative Action):
- If operating on Windows 10 Enterprise 2016 LTSB, install SIMATIC PCS 7 V9.0 Service Pack 1 to ensure full OS qualification and prevent grid serialization re-corruption.
Verification
Verify POV functionality through the following checks:
1. Click the Parameters tab: verify that block inputs/outputs and numerical values display accurately.
2. Click the Signals tab: confirm that the table header displays signal-specific columns (Signal, Chart, Block, I/O, Address, Data Type).
3. Open multiple distinct projects: verify that the Signals tab remains correctly formatted without reverting to parameter schemas.
Limitations and Operational Precautions
Exercise caution when editing the Windows Registry. Always export a backup of the HKEY_CURRENT_USER\Software\Siemens branch before modifying keys. Furthermore, avoid utilizing registry cleaner utilities or running automated profile virtualization software that arbitrarily deletes or rewrites Siemens application keys during user logoff.
Engineer FAQ
Technical References
- SIMATIC PCS 7 Process Object View Function Manual (A5E39140314)
- SIMATIC PCS 7 V9.0 SP1 Software Compatibility Matrix and Installation Guide
- Siemens Technical Support: Resetting Process Object View Layout and Settings (SIOS Entry ID 109748974)
Related Articles
- Optimizing Process Object View Performance and Bulk Excel Pasting in PCS 7
- Cross-Referencing Field I-O Addresses and Finding Points of Use in PCS 7 CFC
- Resolving SQL Server 2014 Installation Failures During PCS 7 Setup on Windows 10