Resolving 'Project Language Not Compatible' Error When Opening SIMATIC PCS 7 Projects on Another PC
In SIMATIC PCS 7 and STEP 7, the error 'The project contains data of a language that is not installed on your computer' occurs when a project created on a computer with a specific regional language or codepage (such as Turkish, Russian, German, or Dutch) is opened on an Engineering Station lacking that Windows language pack. To quickly resolve this, navigate to the project directory in Windows Explorer, open the Global folder, and delete or rename the metadata file named Language. When reopened, SIMATIC Manager automatically regenerates this file matching the local computer's installed regional language.
Table of Contents
- Why SIMATIC Manager Enforces Project Language Compatibility
- The Role of the
LanguageMetadata File in the Global Directory - Comparison Table - Methods for Resolving Language Incompatibility
- Step-by-Step Recovery and Codepage Realignment Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Why SIMATIC Manager Enforces Project Language Compatibility
When sharing SIMATIC PCS 7 or STEP 7 projects between multinational engineering teams, system integrators, and plant sites, engineers frequently encounter a project opening lockout:
The project contains data of a language that is not installed on your computer.
Do you want to open the project with language English (United States)?
Or worse, a fatal blocking dialog:
The project cannot be opened because the required project language
is not installed on your operating system.
This error occurs because classic STEP 7 (V5.5 / V5.6) and PCS 7 engineering databases were architected prior to complete universal Unicode adoption. Projects encode symbols, block comments, and plant hierarchy strings using specific regional Windows non-Unicode character sets (such as Windows-1252 for Western Europe, Windows-1254 for Turkish, or Windows-1251 for Cyrillic).
When a project is created, SIMATIC Manager stamps the project's primary engineering language and active Windows system locale into an internal tracking file.
The Role of the Language Metadata File in the Global Directory
Within every STEP 7 / PCS 7 project folder, there is a subfolder named Global. Inside Global, the operating system maintains a small metadata file simply named Language (without a file extension):
* This file records the binary codepage ID, language identifier (LCID), and default translation table used when the project was last saved.
* When SIMATIC Manager attempts to open the project on a new PC, it compares the LCID stored inside Global\Language against the languages currently installed in the host Windows operating system.
* If the host PC lacks the matching language pack or non-Unicode system locale, STEP 7 halts initialization to prevent potential character corruption of database strings.
The Zero-Risk Deletion Solution
Because the Language file only stores a session preference pointer and does not contain the actual user program logic, function blocks, or CFC charts:
* Deleting or renaming Global\Language causes SIMATIC Manager to treat the project as language-unassigned.
* Upon opening, SIMATIC Manager automatically queries the destination computer's active Windows language (e.g., English US) and generates a fresh, fully compatible Language file matching the local PC!
Comparison Table - Methods for Resolving Language Incompatibility
The following table compares different approaches to resolving language compatibility errors in PCS 7.
Global\LanguageStep-by-Step Recovery and Codepage Realignment Procedure
To clear the language incompatibility block and successfully open the PCS 7 project, execute the following steps:
-
Close SIMATIC Manager:
* Ensure SIMATIC Manager and all engineering tools (CFC, SFC, HW Config) are completely closed. -
Locate the
Global\LanguageFile:
* Open Windows Explorer.
* Navigate to the project root directory (e.g.,D:\Projects\Plant_Project\).
* If the project is a Multiproject, open each contained sub-project folder.
* Open theGlobalfolder.
* Locate the file namedLanguage(File type: File, typically 1 KB to 4 KB in size). -
Rename or Delete the File:
* Rename the file toLanguage.old(or delete it directly).
* If working with a Multiproject, repeat this for the Master Data Library'sGlobalfolder and each AS project'sGlobalfolder. -
Reopen the Project in SIMATIC Manager:
* Launch SIMATIC Manager.
* Select File -> Open and browse to the.s7por.s7mproject file.
* The project opens smoothly without any language incompatibility dialogs.
* SIMATIC Manager automatically writes a newLanguagefile configured for your local Windows system locale. -
Set Default Project Language to English (United States):
* To prevent future issues when sharing with other engineers:
* In SIMATIC Manager, select Options -> Manage Multilingual Texts -> Change Language.
* Select English (United States) as the default project language.
* Check Always open project in current language.
* Click OK.
Verification
Confirm that the project is fully accessible and functionally healthy:
- Verify Project Hierarchy Navigation:
* In SIMATIC Manager, click through Component View and Plant View.
* Confirm that all folders, charts, and hardware objects display clearly without question marks (???) or gibberish character substitution. - Open HW Config and CFC Charts:
* Open HW Config; confirm that rack definitions load cleanly.
* Open a CFC chart and inspect block names, comments, and parameter values. - Verify File Regeneration:
* In Windows Explorer, check<Project_Dir>\Global\.
* Confirm that a newLanguagefile has been created with the current timestamp.
Limitations and Operational Precautions
- Foreign Character Set Display: While deleting
Global\Languageallows the project to open, text strings originally entered in Cyrillic, Chinese, or Arabic will appear as accented Latin characters or question marks unless the appropriate Windows Language Pack is installed on the operating system. - Never Delete the Entire
GlobalFolder: Only delete the specific file namedLanguage. TheGlobalfolder contains other essential database indices (s7finfo, cross-reference pointers) that must never be purged. - Archiving Best Practice: Always archive projects using SIMATIC Manager (File -> Archive); raw zip utilities can preserve stale file locks.
Engineer FAQ
Does deleting the Language file delete any PLC program code or block logic?
No. The Language file stores only the character codepage preference and default language pointer for the engineering editor. It contains zero logic, zero DB values, and zero CFC chart data.
Why does SIMATIC Manager ask 'Do you want to open in English US'?
If the project language exists in Windows but is not the active system locale, STEP 7 offers to translate the session view to English US. Clicking Yes opens the project safely.
Can this error occur with WinCC projects?
WinCC projects handle languages differently via the Text Distributor and WinCC Text Library. This specific Global\Language error is strictly an S7 / SIMATIC Manager database mechanism.
How do I prevent this error when sending projects to international clients?
Before archiving, set the default project language to 'English (United States)' under Options -> Manage Multilingual Texts -> Change Language, and check 'English (United States)' as the default language for display.
Technical References
- SIMATIC S7-400 Automation System STEP 7 V5.5 User Manual
- SIMATIC Process Control System PCS 7 Engineering System Guidelines
- Siemens Industry Online Support Entry ID 109780813 (STEP 7 Project Administration)
Related Articles
- How to Change the Default Project Language in SIMATIC PCS 7 and STEP 7 Multiprojects
- Automating Multiproject Backups and Version Archiving in SIMATIC PCS 7 via Version Trail
- Cross-Referencing and Monitoring I-O Signals and Graphic Tag Connections in SIMATIC PCS 7 and WinCC