Resolving SFC Execution Error (ExecErr) and Collective Error (CollErr) Following CPU Warm Restart
Following a CPU warm restart or temporary voltage loss in SIMATIC PCS 7 V8.2, active SFC Types assert ExecErr (Execution Error) and CollErr (Collective Error) while locking out automatic commands from SIMATIC BATCH because the SFC runtime enters an interlocked CPU restart recovery state. The SFC evaluates instance data consistency: if consistent (indicated by a green resume symbol), the error clears only when an operator or recovery logic executes a 'Resume', 'Stop', or 'Abort' command; if inconsistent (indicated by a red backwards reset arrow), a 'Reset' command is mandatory. Executing the appropriate recovery command resets CPU_Restart, clears ExecErr and CollErr, and restores SIMATIC BATCH control.
Table of Contents
- SFC Runtime State Machine and CPU Restart Behavior
- Consistent vs Inconsistent Instance Data Evaluation
- Recovery Command Matrix for Restarted SFC Phases
- Step-by-Step Recovery and Restart Parameterization Procedure
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
SFC Runtime State Machine and CPU Restart Behavior
In SIMATIC PCS 7, Sequential Function Charts (SFC and SFC_Type / FB247) govern multi-step sequential automation compliant with ISA-88 and NAMUR standards. When integrated with SIMATIC BATCH, SFC instances execute batch recipe phases.
When an AS controller undergoes a warm restart (e.g., following a plant voltage dip, power cycle, or CPU memory reinitialization), the SFC runtime intercepts the transition. To prevent dangerous autonomous machinery movement or batch contamination upon power restoration, the runtime blocks all automatic progression. It sets output CPU_Restart = TRUE, asserts ExecErr and CollErr, and halts batch phase execution until operational recovery is acknowledged.
Consistent vs Inconsistent Instance Data Evaluation
Upon controller startup, the SFC engine evaluates the internal data integrity of each active instance:
1. Consistent Data (Green Resume Symbol): The step numbers, target setpoints, and elapsed timers in the instance DB remained intact throughout the power interruption (e.g., supported by CPU backup battery or retentive work memory). The SFC can safely resume execution from the interrupted step or execute an orderly stop.
2. Inconsistent Data (Red Backwards Reset Arrow): Step tracking or step pointer integrity was corrupted or lost during power cycling. The runtime considers step conditions invalid. Progression is prohibited; the phase can only be returned to the initial state via an explicit Reset command.
Recovery Command Matrix for Restarted SFC Phases
The table below details SFC restart recovery modes, visual status symbols, and required operator commands:
ExecErr?Resume (Run), Stop, AbortExecErr, CollErr, and CPU_Restart.ResetExecErr and purges active step data.ExecErr = 1.StartExecErr remains 0.Step-by-Step Recovery and Restart Parameterization Procedure
- Identify Blocked SFC Instance: In the WinCC SFC Visualization overview or SIMATIC BATCH Control Center, locate the interlocked SFC phase reporting execution error.
- Inspect Data Integrity State: Open the SFC faceplate or SFC Editor online:
- If a Green Resume Arrow is displayed: Click Resume to continue batch processing, or click Stop / Abort to terminate the batch safely.
- If a Red Reset Arrow is displayed: Click Reset. The phase transitions toIdle. - Clear BATCH Server Control Lock: In SIMATIC BATCH Control Center, right-click the blocked recipe unit -> select
Release unitorResume batch. WithExecErr = 0, SIMATIC BATCH re-acquires control of the SFC phase. - Configure Automated Restart Properties (Preventative Engineering):
- In the SFC Type Editor, selectOptions -> SFC Type Properties -> Characteristics.
- Inspect parameter Restart on power recovery:- Configure whether the phase should automatically hold, abort, or attempt automatic resumption without operator prompt according to plant safety regulations.
- Compile and Download Changes: Save SFC Types, compile CFC changes, and download to the AS in RUN mode.
Verification
Verify recovery and restart handling through the following steps:
1. In CFC test mode on the SFC block, confirm that outputs CPU_Restart = FALSE, ExecErr = FALSE, and CollErr = FALSE.
2. In WinCC OS Runtime, confirm that the SFC faceplate status bar shows Running or Idle without red error banners.
3. In SIMATIC BATCH Control Center, verify that the batch status transitions from Held (Interrupted) back to In Progress with recipe steps advancing normally.
Limitations and Operational Precautions
Never automate unconditional automatic resumption (Auto-Resume) on chemical batch reactors or high-temperature processes. If a power dip interrupts agitation, exothermic thermal runaways can develop; restarting pumps or heaters automatically without verifying field temperature and agitation states violates process safety standards (IEC 61511). Always ensure inconsistent data scenarios are routed to a verified safe shutdown state.
Engineer FAQ
Technical References
- SIMATIC PCS 7 SFC for S7 Programming and Operating Manual (A5E39140302)
- SIMATIC BATCH V8.2 Engineering and Operation Manual
- Siemens Technical Support: Behavior of SFCs After S7 CPU Restart (SIOS Entry ID 109748952)
Related Articles
- Activating Sequential Function Chart (SFC) Sequence Test Mode with S7-PLCSIM
- Locating and Monitoring SFC Type Instances in Continuous Function Chart (CFC)
- Resolving Missing Step OS Comments and Tooltips in PCS 7 SFC Visualization