Resolving SIMIT Virtual Controller CPU 410-5H Substitution and MLFB Mismatch on Download
When compiling a simulation model containing an AS 410-5H in early SIMIT Virtual Controller (VC) releases, SIMIT displays a warning that the CPU 410 is unsupported and will be substituted by a CPU 417-4. Subsequent hardware configuration downloads from SIMATIC Manager fail with an MLFB order number mismatch error because the offline project targets a CPU 410-5H (6ES7410-5HX08-0AB0) while the emulator presents a CPU 417-4 (6ES7417-4XT05-0AB0). To resolve this, engineers must bypass the Hardware Configuration download and execute 'Download Changes' or 'Charts Only' from the CFC Editor, or upgrade to SIMIT V9.1 SP1 / V10.0, which provides native, fully certified emulation of the CPU 410-5H platform.
Table of Contents
- SIMIT Virtual Controller Emulation Architecture
- Root Cause of CPU 410-5H Substitution and MLFB Collisions
- Workarounds and Migration to Native CPU 410 Support
- Procurement Schedule for SIMIT Virtual Controller
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
SIMIT Virtual Controller Emulation Architecture
The SIMIT Virtual Controller (VC) emulates the behavior of SIMATIC S7-300, S7-400, and S7-410 controllers on a Windows PC. Unlike S7-PLCSIM which runs as a single desktop application, SIMIT VC executes multiple virtual controllers simultaneously as real-time Windows services communicating over virtual Ethernet interfaces.
In early releases (SIMIT V8.x through early V9.1), the Virtual Controller kernel emulated the S7-400 V5.x instruction set. Because the CPU 410-5H features specialized firmware and System Expansion Card (SEC) licensing structures, early SIMIT compilers automatically substituted CPU 410 instances with a generic high-capacity CPU 417-4.
Root Cause of CPU 410-5H Substitution and MLFB Collisions
The table below details the conflict occurring during the download sequence:
6ES7410-5HX08-0AB0).6ES7417-4XT05-0AB0).Download Changes / Charts Only).Workarounds and Migration to Native CPU 410 Support
Depending on the installed SIMIT release, two solutions exist:
Method 1: Download Charts Only from CFC (No Hardware Download)
If using legacy SIMIT without native CPU 410 support:
- In SIMATIC Manager, do not download the Hardware Configuration (
HW Config) to the virtual controller. - Open the Continuous Function Chart (CFC) editor.
- In CFC, click the Download icon (or select
PLC->Download...). - In the download dialog, select Changes only (or Entire program - Charts only).
- The CFC compiler bypasses the hardware MLFB handshake and successfully downloads all FBs, FCs, DBs, and run sequences into the virtual CPU 417 memory.
Method 2: Upgrade to SIMIT V9.1 SP1 / V10.0 (Native Support)
Siemens added native CPU 410-5H firmware emulation in SIMIT V9.1 SP1 and SIMIT V10.0:
- SIMIT VC natively recognizes MLFB
6ES7410-5HX08-0AB0. - Full HW Config downloads, communication connections, and redundant AS 410-5H pairs can be downloaded directly from SIMATIC Manager without substitution warnings.
Procurement Schedule for SIMIT Virtual Controller
The following Equipment Schedule specifies the relevant order numbers for SIMIT VC licensing:
Software Packages:
- SIMIT Engineering V9.1 (Software Media): 6DL8913-0AK10-0AB5
- SIMIT Virtual Controller (1 VC License): 6DL8913-0BL00-0AB5
- SIMIT Virtual Controller (5 VC Pack): 6DL8913-0BN00-0AB5
- SIMIT V9.1 to V10.0 Upgrade Package: 6DL8913-0AE00-0YB5
[!IMPORTANT]
Commercial Accuracy Disclaimer: SIMIT Virtual Controllers are licensed per emulated controller instance. Simulating a redundant AS 410-5H automation station requires two Virtual Controller licenses. Final software entitlements and MLFBs must be validated against the applicable Siemens ST PCS 7 Catalog and authorized distributor quotations.
Verification
To verify that the simulation operates correctly:
- Start the SIMIT simulation project containing the Virtual Controller.
- Confirm that the virtual controller status indicator transitions to solid green RUN.
- In CFC, initiate a download of charts: verify download reaches 100% completion without error.
- Open CFC Online Test mode: verify live process values and block executions update dynamically.
- Inject a simulated field input from SIMIT: confirm the CFC logic responds immediately.
Limitations and Operational Precautions
Operational boundaries when virtualizing CPU 410 controllers:
- HW Config Features Omitted: When using CPU 417 substitution, specific CPU 410 features (such as onboard PROFINET system redundancy R1 and System Expansion Card PO limits) are not emulated.
- Redundant AS 410-5H Coupling: Simulating bumpless CPU redundancy switchover requires SIMIT V10.0 or higher with paired virtual controllers.
- Classic S7-PLCSIM Alternative: If SIMIT VC licenses are unavailable, classic S7-PLCSIM V5.4 can be used, as it accepts CPU 410 programs without checking hardware MLFBs.
Engineer FAQ
Why does SIMIT replace CPU 410 with CPU 417 in older versions?
Earlier SIMIT Virtual Controller kernels did not include the specific firmware definitions and PROFINET interfaces of the CPU 410-5H, substituting the closest high-memory S7-400 processor (CPU 417-4).
How can I download to the virtual controller if HW Config fails with an order number mismatch?
Do not download HW Config. Download only the charts from the CFC Editor (Download Changes or Charts only). CFC bypasses hardware order number checks.
Which SIMIT version officially introduced native CPU 410-5H emulation?
Native CPU 410-5H emulation was officially introduced in SIMIT V9.1 SP1 and expanded in SIMIT V10.0.
Does SIMIT Virtual Controller emulate the CPU 410 System Expansion Card (SEC)?
In native CPU 410 emulation (SIMIT V10+), the Virtual Controller automatically allocates maximum memory capacity (2,600 POs) without requiring physical SEC licenses.
Technical References
- Siemens SIMATIC SIMIT V9.1 / V10.0 Virtual Controller User Manual (A5E40871144)
- Siemens SIMATIC PCS 7 CPU 410-5H Process Controller Manual (A5E02148107)
- Siemens Industry Online Support Entry ID 109756881: Emulating CPU 410-5H in SIMIT
Related Articles
- Troubleshooting Forcing and Signal Exchange Failures in SIMIT with Classic S7-PLCSIM
- Simulating SIMATIC FM 458-1 DP High-Speed Controllers in SIMIT V9.1
- Activating Sequential Function Chart (SFC) Sequence Test Mode with S7-PLCSIM