Restoring Missing Interlock Bypass Icons on CEMAT Motor Faceplates in PCS 7
When upgrading from the standard PCS 7 Advanced Process Library (APL) to CEMAT Minerals V8.2, the prominent interlock bypass indicator (bold letter 'B') on motor block icons disappears because CEMAT drive blocks (C_DRV_1D) handle interlock evaluation and visualization through dedicated CEMAT status words rather than APL bypass bits. To restore visible bypass indication, verify that the motor block icon variant selected in CFC corresponds to a CEMAT symbol configured with the bypass display layer, and ensure that upstream interlock blocks (C_INTERL, C_INT_L, or C_ANNUNC) have interlock bypassing authorized. Alternatively, map the CEMAT bypass status bit to the Extended Status Display in the WinCC Graphics Designer.
Table of Contents
- Visualization Architecture: APL vs CEMAT Minerals
- Why the APL 'B' Indicator Does Not Display in Standard CEMAT
- Comparison of APL and CEMAT Bypass Visualization Mechanisms
- Step-by-Step Procedure to Restore Bypass Visualization
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Visualization Architecture: APL vs CEMAT Minerals
In SIMATIC PCS 7, the Advanced Process Library (APL) and the industry-specific CEMAT Minerals library (used extensively in cement, mining, and aggregates) employ different human-machine interface (HMI) philosophies.
In APL, standard technological blocks (MotL, VlvL) display prominent operational state badges directly on block icons. When an interlock or safety signal is bypassed, APL renders a high-visibility badge (such as a bold letter 'B' or wrench symbol) in the top-right corner of the block icon to alert operators immediately.
In CEMAT Minerals V8.2, motor visualization is centered around the C_DRV_1D block. CEMAT separates operational alarms, interlocks, and maintenance flags into specialized multi-word status registers (STATUS1, STATUS2, STATUS3). If the block icon template deployed in WinCC does not link to the specific CEMAT maintenance/bypass bit, the bypass state remains invisible until an operator opens the detailed diagnostic window.
Why the APL 'B' Indicator Does Not Display in Standard CEMAT
The loss of the bypass badge during migration or new development stems from architectural differences:
-
Different Block Icon Templates: APL uses templates from
@PCS7Typicals_APL.pdl(e.g.,@MotL/1), whereas CEMAT uses specialized templates from@PCS7Typicals_CEMAT.pdl(e.g.,@C_DRV_1D/1,@C_DRV_1D/2). -
Different Signal Origins: In APL, parameter
BypProtorIntlk08.Bypassfeeds directly into the block icon's Extended Status Display. In CEMAT, interlocks originate from dedicated modules (C_ANNUNC,C_MEASUR,C_INTERL,C_INT_L), and bypass status is transmitted via the collective maintenance status word (MAINT/STATUS3). -
Icon Variant Selection: Basic CEMAT block icons omit the maintenance overlay to reduce visual clutter in massive cement plants where hundreds of drives operate simultaneously.
Comparison of APL and CEMAT Bypass Visualization Mechanisms
The table below contrasts how interlock bypass status is handled and displayed across APL and CEMAT Minerals.
MotL / MotRevLC_DRV_1D / C_DRV_2DIntlock, Protect) or Intlk08C_INTERL, C_INT_L, C_ANNUNC)BypProt (BOOL) / Intlk08.BypActBYPB_L (BOOL) or operator authorization on C_INTERL@PCS7Typicals_APL.pdl@PCS7Typicals_CEMAT.pdl / @Template_CEMAT.pdlStatus2 bit decoded via dynamic wizardSTATUS3 / MAINT bitmask decoded via CEMAT scriptsStep-by-Step Procedure to Restore Bypass Visualization
Follow this procedure to enable visible bypass indicators on CEMAT motor block icons:
-
Select the Appropriate CEMAT Block Icon Variant:
- In the CFC chart containingC_DRV_1D, open the block object properties.
- Under theAttributestab, locate attributetype(e.g.,@C_DRV_1D/1).
- Change the type attribute to an icon variant that supports maintenance/bypass visualization (such as@C_DRV_1D/2or custom variant). -
Configure Upstream CEMAT Interlock Blocks:
- Ensure that interlocks feedingC_DRV_1Duse CEMAT interlock blocks (C_INTERLorC_INT_L).
- Verify that parameterBYPB_Lis enabled or operator bypass authorization is permitted in the CEMAT system parameters. -
Customize Extended Status Display in
@PCS7Typicals_CEMAT.pdl:
- In WinCC Graphics Designer, open@PCS7Typicals_CEMAT.pdl.
- Locate the target@C_DRV_1Dblock icon and open its Extended Status Display properties.
- Add an icon state layer bound to the bypass bit of the motor's status tag (.STATUS3or.MAINT).
- Assign the bitmap image depicting the bold 'B' or maintenance symbol. -
Update Block Icons in Process Pictures:
- In SIMATIC Manager, select the plant hierarchy folder and runOptions -> Plant Hierarchy -> Create/Update Block Icons.
- Confirm the update to apply the modified graphic template across all WinCC process screens.
Verification
Verify bypass display operation through the following steps:
1. In WinCC Runtime, open the faceplate for a test motor and activate an interlock bypass on its associated C_INTERL block.
2. Verify that the motor block icon on the process screen instantly displays the bypass indicator badge.
3. Remove the bypass condition: confirm that the badge clears immediately.
4. Verify that bypassing the interlock logs an audit entry in the WinCC Alarm Logging sequence archive.
Limitations and Operational Precautions
Modifications to @PCS7Typicals_CEMAT.pdl must be managed carefully. Never modify the factory template in the installation directory; always edit the copy residing in the local project's GraCS directory. During system upgrades or CEMAT hotfix installations, factory templates can overwrite custom modifications unless properly archived. Additionally, always follow plant management of change (MOC) procedures before modifying operator-facing safety indicators.
Engineer FAQ
Can I use standard APL block icons with CEMAT C_DRV_1D blocks?
No. APL block icons expect APL-specific structure tags (Status1, Status2, OS_Perm), whereas CEMAT uses proprietary status words. Using an APL icon with a CEMAT block results in non-functioning faceplates.
Where are the CEMAT typical pictures located?
CEMAT typical templates are stored in @PCS7Typicals_CEMAT.pdl and @Template_CEMAT.pdl inside the WinCC project GraCS folder.
Does CEMAT support user-definable bypass authorizations?
Yes. CEMAT allows administrators to restrict interlock bypassing to authorized operator levels using WinCC User Administrator permissions.
Technical References
- SIMATIC PCS 7 Minerals (CEMAT) V8.2 System Manual
- SIMATIC PCS 7 CEMAT Engineering Manual - Block Icons and Faceplates
- Siemens Technical Forum: Adding Bypass Display to CEMAT Motor Blocks (SIOS Entry ID 193066)
Related Articles
- Configuring Local Mode Operation and Interlock Bypassing in CEMAT and APL
- Assigning and Changing APL Block Icon Variants in Continuous Function Chart (CFC)
- Preventing Block Icon Layer Reset to Layer 0 During Create and Update Block Icons
Related Tags
- CEMAT
- C_DRV_1D
- Block Icons
- Bypass Icon
- APL Migration
- WinCC Graphics